67
®
OPTION
DESCRIPTION
VALUES
ALLOWABLE VALUES
2.0
Gas Pressure Select
0- Gas pressure input not used. The gas valve leak test is
not performed and the gas pressure limit values are
ignored.
1- NX1020 gas pressure sensor used. The unit Monitors
the gas pressure (including gas pressure limits) if gas pro-
file is selected but does not perform gas valve proving.
2- NX1020 gas pressure sensor used. The unit monitors
the gas pressure (including gas pressure limits) and per-
forms Gas Valve Proving if a gas profile is selected.
2.1
Gas Pressure Zero
0-999 mBar
2.2
Gas Pressure Span
0-999 mBar
2.3
Gas Pressure Nominal
0-999 mBar
2.4
Gas Pressure Low Limit
0-999 mBar
2.5
Gas Pressure High Limit
0-999 mBar
2.6
Test Volume
0.0-99.9 liters
2.7
Maximum Leak Rate
0.0-99.9 liters/hour
2.8
Vent Valve Select
0- Not used
1- Type NC valve Output energized to open valve (Used for
V.P.S.)
2- Type NO valve Output energized to close valve, powered
at sequence 5.
2.9
Fuel Valve Proof of Closure
0- Deselected, no proof of closure function selected.
1- Gas Valve Main 2 Only checked.
2- Oil Valve Only checked.
3- Both Gas main 2 and oil valve checked.
3.0
Flame Detection Device
0- IR detector
1- Ultraviolet (UV) detector, non self-check.
2- Ultraviolet Self-Check (UVSC) with shutter.
3.1
False Flame Detection Time
0- False flame detection time < 3 seconds
1- False Flame detection time < 30 seconds
3.2
Flame Failure Response Time
0- Flame Failure response time < 1 second (compatibility
with CE products).
1- Flame failure response time < 1 second.
2- Flame failure response time < 2 seconds.
3- Flame failure response time < 3 seconds
3.5
Fan on Early
0-120 seconds
4.0
Safety Time Configuration
0-10 see Table 3, pg. 77
4.1
Ignition Time
0-999 sec
4.2
Low Fire Hold Time
0-999 sec
4.3
Post Purge TIme
0-999 sec
4.4
Extended Oil Pilot
0-20 sec
4.5
Permanent Gas Pilot
0- Disabled
1- Enabled Permanent pilot operation, when firing on gas.
(Intermittent pilot)
COMMISSIONING SHEET