20
£
It is imperative the shield of this cable is connected to the display unit’s metal housing. This should
be achieved as follows:
1.
Cut back approximately 4" (100mm) of overall insulation.
2.
Open the braided shield adjacent to the remaining insulation and pull all 6 cores through the
opening.
3.
Fold the shield back down the insulated cable.
4.
Fit sleeving to the braid to insulate the earth cable formed by the braid.
5.
Fit adhesive lined heatsink to cover the folded back screen and hold the earth sleeving.
6.
Adjust the earth connection as required (length must not exceed 4” (100mm) to reach either
4mm securing/earthing studs and fit a suitable crimp ring terminal.
7.
The shields of all cables must be connected at the main unit by cutting back the insulation where
the cable passes them throughout the cable clamp to ensure a good earth connection is made.