FLAME SCANNERS
CAUTION: The UV1, UV2, UV8A, UV90 and 45UV3 ultra-violet flame scanners are non-self
checking UV systems and should be applied only to burners that cycle often (e.g.: a minimum
of once per 12 hours) in order for the safety checking circuit to be exercised. If component
checking is required during burner operation for constantly fired burners, utilize the self-
checking ultra-violet flame scanners (45UV5) or the infrared flame scanner (48PT2) which
uses auto-check amplification circuit.
SCANNER SELECTION
FIREYE P/N
BULLETIN
DESCRIPTION
48PT2-1003
48PT2-9003
48PT2-1007
48PT2-9007
SC-103
Infrared 1/2" straight mount 96" (2.4m) cable
Infrared 1/2" 90
q
angle mount 96" (2.4m) cable
Infrared 1/2" straight mount 48" (1.2m) cable
Infrared 1/2" 90
q
angle mount 48" (1.2m) cable
UV1A3
UV1A6
UV8A
UV2
45UV3-1050
UV90-3
UV90-6
UV90-9
SC-102
UV 1/2" straight 36" (0.9m) flex conduit
UV 1/2" straight 72" flex (1.8m) conduit
UV 1/2" 90
q
head 72" (1.8m) unshielded leads
UV 3/8" straight 36" (0.9m) flex conduit
UV 3/4" cast aluminum housing 8' (2.4m) cable
UV non-self checking scanner for frontal or side (90°) viewing. Complete with mounting fixture
and 3’ (900mm) flex conduit.
UV non-self checking scanner for frontal or side (90°) viewing. Complete with mounting fixture
and 6’ (1800mm) flex conduit.
UV non-self checking scanner for frontal or side (90°) viewing. Complete with mounting fixture
and 9’ (2700mm) flex conduit.
45UV5-1007
45UV5-1008
45UV5-1009
SC-101
Self-check UV 1" British thread mounts, 230V, 6’ (1.8m) unshielded leads
Self-check UV 1" British thread mounts, 120V, 6’ (1.8m) unshielded leads
Self-check UV 1" N.P.T. threads, 120V, 6’ (1.8m) unshielded leads
45UV5-1009
UV1A
48PT2-9000
45UV3-1050
UV90