USER PROGRAMMED E320 MESSAGES
In addition to selecting the lockout alarm messages for the E320 Expansion Module from a menu
selection via the ED510 display, the user can also program any message (up to 40 characters in
length) for the individual terminals of the E320 using a dumb terminal (or PC with communication
software) and the appropriate interface cables. Refer to bulletin E-3201 for complete details.
PROGRAM SETUP
The sub-menu PROGRAM SETUP allows the user to review the various operational settings of the
programmer module (e.g. programmer type, purge timing, etc.). The
MODE
key is used to enter the
PROGRAM SETUP sub-menu, and the
SCRL
key is used to advance through the sub-menu.
Press
Screen Displays
Description
SCRL
AUTO 45
SCRL key advances through the historical information until “Program
PROGRAM SETUP >
Setup” is displayed. Control has released to auto modulation, flame
signal strength = 45.
MODE
AUTO 45
Programmer Type is an EP113.
PROGRAMMER EP113
SCRL
AUTO 45
Software Engineering code of the programmer module is code 21.
ENGR CODE NO. 21
SCRL
AUTO 45
Amplifier module is an EUV1 or an ERT1.
AMP=EUV1 OR ERT1
SCRL
AUTO 45
Purge timing (selected by dipswitches # 3, 4, 5) is 30 seconds.
PURGE TIME 0:30
SCRL
AUTO 45
The control will lockout (non-recycle) when the running interlock circuit
RECYCLE 3-P = N
(3-P) is opened during the firing cycle. (selected by dipswitch #1).
SCRL
AUTO 45
Terminal 5 is selected for intermittent operation (selected by
TERMINAL 5 = INTMT
dipswitch #2).
SCRL
AUTO 45
Proven 3-P Open To Start is enabled (selected by dipswitch #6).
PROVE 3-P OPEN=Y
SCRL
AUTO 45
Flame Failure Response Time (FFRT) = 1 second (maximum).
FLAME FAIL TIME 1s
SCRL
AUTO 45
Unit Address is 00. Refer to programmer bulletin to modify Unit
UNIT ADDRESS #00
Address.
MODE
AUTO 45
MODE key returns to run message.
FLAME SIGNAL