Pressure
SETTINGS
PRESSURE
UNITS
1
Use arrows to set preferred pressure unit system (psi, bar, kPa). Press to con
fi
rm.
SETTINGS
PRESSURE
START
1
Use arrows to set desired pump start pressure. Press to con
fi
rm.
SETTINGS
PRESSURE
STOP
1
Use arrows to set desired pump stop pressure. Press to con
fi
rm.
Note: Pump stop pressure must be set below the pump “churn” pressure (including minimum suction pressure), oth-
erwise the pump will run continuously once started.
SETTINGS
PRESSURE
AUTOMATIC SHUTDOWN DISABLED
1
Use arrows to enable or disable the automatic shutdown disabled feature. Press to con
fi
rm.
Note: Enabling this feature makes the controller “manual stop only”.
SETTINGS
PRESSURE
OVERPRESSURE ALARM
1
Use arrows to enable or disable the overpressure alarm feature. Press to con
fi
rm.
Limit
Use arrows to set the pressure limit for the overpressure alarm. Press to con
fi
rm.
SETTINGS
PRESSURE
RECORDING - DELTA
1
Use arrows to set pressure delta recording limit. Press to con
fi
rm.
HOURLY
Use arrows to enable or disable hourly pressure recording. Press to con
fi
rm.
Note: Pressure will be recorded whenever pressure changes by more than set limit.
Note: Pressure will be recorded every hour, on the hour.
SETTINGS
PRESSURE
CALIBRATION - SET TO ZERO
2
Use arrows to set zero calibration value. Press to con
fi
rm.
SET TO SPAN
Use arrows to set span calibration value. Press to con
fi
rm.
Note: Remove interlock jumper wire when calibration is complete.
Note: Before proceeding, place jumper wire between
fi
eld terminals #1 & 10 to prevent starting of the motor. A cali-
brated pressure gauge will be required to correctly adjust the settings.
Remove/relieve system pressure from the controller sensing line. If gauge shows 0 psi, no adjustments are required;
otherwise set zero calibration to same value as displayed on pressure gauge. (Example: With system pressure removed
the gauge reads 3 psi, set zero calibration value to 3).
Using calibrated gauge, restore pressure to controller sensing line. Adjust span setting to match the value shown on
the gauge.
SETTINGS
PRESSURE
SENSOR
The maximum operating pressure of the installed pressure sensor (transducer) is shown. This value cannot be modi-
fi
ed from this location.
Motor & Power
SETTINGS
MOTOR & POWER
SYS VOLTS
System voltage is shown. This is factory setting and can only be modi
fi
ed by a quali
fi
ed service technician. This setting
is set in Factory/Con
fi
guration menu.
SETTINGS
PRESSURE
RESET TO DEFAULT
2
Use arrows to enable the reset (pressure) to default option. Press to con
fi
rm. All user calibration settings
will be reset to factory defaults and reset setting will revert back to disabled.
14