background image

11

©Firefly AB (Oktober 2016)

Alarm Condition - No Fire Present:

A detector in alarm condition when no fire is present may be caused 

by an inadvertent actuation of the manual test . Except for Models 

660-XX0XX and 860-XX0XX, the Model 660 and 860 flame detectors 

feature manually initiated self-test of the optical and electronic 

systems .

Verify the light guides are illuminated . If they are, then check 

the manual test wiring and the test switch for broken, loose, or 

intermittent connections . Repair or tighten any faulty connections . 

If the light guides are not illuminated, then contact your Firefly AB 

representative .

Confidence Condition:

Model 660 and 860 flame detectors are equipped with a fault relay to 

annunciate a change in the operational status of the detector . When 

power is applied to the detector, the fault relay will energize within 2 

seconds . A loss of power will cause the relay to de-energize .

If the fault relay output fails to change state within 2 seconds after 

power-up and the amber LED fails to illuminate, then there may be no 

power reaching the detector’s electronic module . Check the supply 

voltage, the condition of the fuse located at F1 on the PCB and the 

wiring to terminals 8 and 10 . Also, inspect the wiring to the fault relay 

terminals 6 and 7 and the jumper JP1 that sets the fault relay option .

Note: Model 660-0XXXX and 860-XXXXX flame detectors are equipped 

with a 0 to 20 mA option . A loss of power will result in a constant 0 mA 

output .

If the fault relay output continues to be inoperative, isolate the relay 

contacts by disconnecting the external wiring to the fault relay 

terminals . Connect an Ohmmeter across the fault relay terminals and 

monitor for an actuation of the relay . Repair the external wiring if 

necessary .

Fault Condition:

Model 660-0XXXX and 860-XXXXX flame detectors are equipped with 

a 0 to 20 mA output . When the 0 to 20 mA option is not used in your 

application, make sure that the 0 to 20 mA option is “OFF” on the USI . 

If the 0 to 20 mA option is “ON” and at any time the drive line opens or 

the current sense does not equate to what is suppose to be there, it 

will cause the activation of the fault outputs . Check the wire terminal 

15 and insure that a good signal ground is present at terminal 10 or 

11 . To insure that the 0 to 20 mA option causes the fault condition, 

toggle the option on the USI “OFF” and reset the detector by toggling 

the power off then on . If the fault condition continues to be activated, 

then the problem is in a different area .

Model 660-XX1XX and 860-XX1XX flame detectors are equipped with 

automatic self-test in addition to the manual test . Approximately every 

15 minutes the automatic self-test is actuated, and for a brief time 

interval, the optics and electronics are checked for functionality .

The exception to this is for the high-speed setting on 660 models . In 

this configuration (switch 5 “OFF”), self-test is actuated approximately 

every 2 minutes . A failure of the automatic self-test is annunciated 

by the activation of the Fault Outputs . If a detector goes into a fault 

condition, the optical surfaces should be checked for cleanliness . Clean 

sensor windows and light guide ends are necessary for the detector(s) 

to pass self-test .

After the optical surfaces have been inspected and cleaned, reset the 

detector . If the detector is wired for manual test, perform the manual 

test . The typical response time should be from 0 .6 seconds beyond the 

actual fire output time delay .

*WARNING* 

During Manual Test, the fire output will be actuated . 

Always disable extinguishing circuits before testing .

If the detector continues to go into a fault condition following 

a cleaning of the optical surfaces, check the supply voltage and 

wiring at terminals 8 or 9 and 10 or 11 . Look for loose or intermittent 

connections .

During normal operation, the fault outputs will change state on 

power-up . The output will return to its original state if power to the 

detector is removed . If the fault output is intermittent or erratic, check 

the supply voltage and wiring to terminals 8 or 9 and 10 or 11 . Inspect 

the fault relay wiring on the detectors . Repair or tighten any loose 

connections .

For the Model 860, if the UV or IR option is “ON”, the fault relay will be 

flashing at a 1 Hz rate whenever a fault conditions exists .

Manual Test Failure:

*WARNING* 

This test will activate the fire outputs . Always disable 

extinguishing circuits before testing .

A manual test is actuated by connecting the 660-XX1XX or 860-XX1XX 

test circuit terminal 12 to the plus terminal of the detector’s input 

power supply (terminal 8 or 9) .

During manual test, the optical and electronic systems of  a detector 

are checked . Upon successful completion of the test, the fire outputs 

will be activated . Also, the red LED

inside the detector, visible through the UV window, will turn “ON” . The 

typical response time is 0 .6 seconds beyond the actual fire output time 

delay . If the detector fails to respond to a manual test, check to see if 

the USI manual test option is “ON” (switch 1) .

If the detector fails manual test by activating the fault outputs or the 

response time is longer than expected, the optical surfaces of the 

detector may require cleaning . Clean the sensor windows and light 

guide ends . After cleaning, initiate the manual test .

If the detector again fails manual test, check the wiring to the supply 

voltage terminals 8 or 9 and 10 or 11 . The detector may not be 

receiving enough power; the wiring connections may be loose or 

intermittent . If the red LED is illuminated and there is no fire output, 

then check all the connections to the fire alarm panel or annunciating 

devices . A defective test switch may prevent the test circuit from 

initializing . Initiate the manual test by connecting a wire from the test 

switch terminals to the positive terminal of the input power supply . 

Replace the switch if the manual test operates when the wire is 

connected .

UV or IR Warning:

In addition to detecting fire, the Model 860 flame detectors will 

annunciate a warning of potentially hazardous conditions that could 

cause a fire . For example, welding, a process which emits a far greater 

proportion of UV radiation than IR, will cause an actuation of the UV 

or IR Outputs but not the Fire Outputs . For this detector to actuate 

the Fire Outputs, it must sense the simultaneous presence of UV and 

IR in a ratio characteristic of the fire type(s) to which the detector is 

configured .

When the detector senses persistent source of intense UV or IR 

radiation, such as welding, sparks, or radiant heat, the UV or IR Outputs 

will change state . To enable the UV or IR Outputs, the UV or IR option 

(switch 5) must be “ON” . When the UV or IR Outputs are activated, it 

will cause the fault relay to be “OFF” and the amber LED to be“ON” 

constantly . If the 0 to 20 mA option is “ON”, it will set the output to 16 

ma . The UV or IR warning are non-latching outputs and will change 

states if the problem source is removed .

This alarm is used as a tool to help prevent unwanted alarms . An UV 

or IR warning should always be investigated with caution . If possible, 

remove the source of radiation, as a constant presence of UV may 

reduce detector sensitivity and compromise its discrimination ability . 

Inspect the protected area and beyond; UV from sources such as 

welding can be sensed at great distances . If no radiation sources are 

apparent, cover the detector with opaque material to test whether the 

UV or IR warning disappears when the sensor windows are blocked . 

Continue searching for the source of UV or IR, if necessary . If the 

warning does not disappear after blocking the windows, a sensor may 

be faulty and in need of repair .

DMLieferant     

Тел

.: +7 (499) 990-05-50; +7 (800) 775-29-59     dmliefer.ru

Summary of Contents for Omniguard 660 Series

Page 1: ...660 860 SERIES OPTICAL FLAME DETECTORS Installation and operating service manual DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Page 2: ...tricity from an ungrounded source including the human body may damage the electronic circuitry of the Omniguard Series 660 and 860 Flame Detectors Use one or more of the following methods when handlin...

Page 3: ...output Relay contacts rated at 2 Amps 30 VDC Resistive Operating Temperature 40 F to 185 F 40 C to 85 C Storage Temperature 85 F to 212 F 65 C to 100 C Standard Features High Temp Model Relay contact...

Page 4: ...oexistence of UV and IR radiation but also their presence in specific ratios The ratio must conform to the radiation pattern of specific fires see Figure 3 This patented Fire Event Analysis FEA ensure...

Page 5: ...ended for smoldering or electrical fire hazards The following is a partial list of fuels which emit ultraviolet and infrared radiation Response time and detection distances vary Consult Firefly AB app...

Page 6: ...so that it will view the base of the area to be protected 5 Complete the installation by wiring the detector according to the wiring diagram located inside the rear cover Before assembling the detect...

Page 7: ...8 Program 9 Option Off On No Program 9 Denotes factory settings for auto test units only Fig 9 switch configurations for the 660 0xxxx UV Flame detector SPST dip switch S1 located on board p n 71044...

Page 8: ...fails manual test will open when SW7 is on and no loop is present Note The amber LED will be illuminated when relay opens unless there is a loss of power Note Any adjustments to the user options liste...

Page 9: ...acket formation is comprised of the byte definition shown in Table 4 The first byte is the protocol start value for the control packet The second byte represents the detector address high byte which i...

Page 10: ...test A detector that fails auto test due to dirty optical surfaces may be capable of detecting fire but its effectiveness will be limited from 50 to 70 obscuration Cleaning Procedure Locate the follo...

Page 11: ...or 11 Look for loose or intermittent connections During normal operation the fault outputs will change state on power up The output will return to its original state if power to the detector is remove...

Page 12: ...workmanship or materials This warranty shall be valid only if the product is returned within the applicable warranty period to the factory at Stockholm Sweden properly packed and with all transportati...

Page 13: ...0 Latching 1 Non Latching Designation Ultraviolet flame detector To order Model 660 please specify Fire type 0 Hydrocarbon 1 Hydrocarbon Non hydrocarbon Housing material conduit entry 0 Aluminium 3 4...

Page 14: ...14 Firefly AB Oktober 2016 Notes DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Page 15: ...15 Firefly AB Oktober 2016 DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Page 16: ...8 449 25 00 Fax 46 0 8 449 25 01 E mail omniguardsales firefly se www omniguardbyfirefly se Address Heliosgatan 3 120 30 Stockholm Sweden Publication No 1031229 Rev M DMLieferant 7 499 990 05 50 7 800...

Reviews: