background image

8

©Firefly AB (Oktober 2016)

Sensitivity Levels

— Model 660 (Table 1): 

Switch positions 3 and 4 adjust the sensitivity 

to four different levels . Level 1 being the most sensitive to UV radiation 

and the most susceptible to false alarms . Level 2 is the factory setting 

and is recommended for most applications . The following are the logic 

levels for the two switch positions:

Table 1 – Model 660 Sensitivity Settings

Sensitivity Level

Position 3

Position 4

1 (Max)                   

Off

Off

2                        

Off

On

3                            

On

Off

4 (Min)                        

On

On

Detection Speed

— Model  660: 

Switch position 5 is used to select two detection speeds . 

The normal speed utilizes a slower sampling rate and automatic self-

test interval . The high-speed setting increases the data sampling rate 

and auto self-test frequency . Toggling switch position 5 “ON” activates 

the normal speed option . Toggling switch position 5 “OFF” activates 

the high-speed option . The normal speed option is the factory setting 

and recommended for most applications .

Industrial or Aircraft Hangar Applications

— Model  860: 

Switch position 3 is used to select the application 

setting . If the detector is to be installed in an industrial environment 

(i .e ., fuel loading rack, compressor building, tank farm), switch position 

3 should be “ON” . If the application is for an aircraft hangar, switch 

position 3 should be “OFF” . The false alarm immunity will be slightly 

diminished from that of the industrial setting .

Fire Event Analysis Level I or II

— Model  860: 

Switch position 4 allows the detector to run the 

Fire Event Analysis (FEA) program of your choice . FEA Level I is for 

installations with normal UV background levels (i .e ., no welding) . FEA 

Level II should be used where detectors are required to detect flames 

while welding or other UV generating sources are present . Turning 

switch 4 “ON” selects FEA Level I . Turning switch 4 “OFF” will provide 

FEA Level II . Level II has slightly diminished false alarm immunity as 

compared with Level I .

Relay Adjustments

— Models 660-0XXXX and 860-XXXXX and Model 660-1XXXX  

There are two relays and Configuration Option Jumpers, JP1 and JP2, 

located on the exposed surface of the printed circuit board (PCB) in the 

housing assembly . Using these jumpers, the relays may be configured 

as normally open or closed . The factory will ship the detectors with the 

following settings .

1 .)  Fire relay (K2) — normally open:
  -will close when there is a fire present beyond the fire time delay 

setting .

    -will close when manual test is activated beyond the length of 

time for the fire delay time setting .

  

Note: 

The red, light emitting diode (LED), will be illuminated when  

    relay closes .

2 .) Fault relay (K1) - normally open:
     -  will close when power is applied (Model 860 after 2 seconds and  

    Model 660 less then a second) .

     -  will open when power is lost (or fuse F1 on process PCB is open) .
     -  will open when detector fails automatic test .
     -  will open when detector fails manual test .
     -  will open when SW7 is on and no loop is present .

  

Note: 

The amber LED will be illuminated when relay opens, unless  

    there is a loss of power .

Note: 

 Any adjustments to the user options listed above should be 

done with the power “OFF” . The detectors will not recognize any 

changes until the microprocessor is reset . Removing the power allows 

a reset to occur .

Caution: 

Upon applying power, insure that the detector remains on for 

at least 5 seconds to allow for complete initialization to take place .

Fire Outputs Latching or Non-Latching

— Models 660 and 860

, switch position 6 selects the latching or non-

latching Fire Outputs option . To select latching, the switch position 6 

must be toggled “ON” . Upon detecting a fire, the Fire Outputs signal 

will remain engaged as long as power remains “ON” or until the 

detector is reset through the RS485 User Interface (UI) . If you select 

non-latching by toggling switch position 6 to “OFF”, the Fire Outputs 

signal will disengage after a fire is extinguished .

Optical Self-Test

— Models 660-XX1XX and 860-XX1XX:

 These models have a “through-

the-lens” optical clarity-checking  feature . The factory setting is for 

automatic test only, switch position 1 is “OFF”, and switch position 2 

is “ON” . (See Figure 5 and 6 for location of the switches and Figures 

7, 8 and 9 that describe the switch settings for the user selectable 

interface .) If the addition of the manual test feature is desired, then 

toggle the switch position 1 to “ON” . If only the manual test feature is 

needed, then toggle the switch position 1 “ON” and switch position 2 

“OFF” . If no optical testing is preferred, then ensure that both of these 

switches are “OFF” .

Models 660-XX0XX and 860-XX0XX 

do not have either the manual or 

the automatic test feature and do not test the lens for optical clarity . 

Switch positions 1 and 2 are non-applicable (N/A) in these detectors .

0 to 20 mA Output

— Models 660-0XXXX and 860-XXXXX

 switch position 7 selects the 0 

to 20 mA output option . If this output is utilized, then switch position 

7 must be “ON” . Otherwise, if this output is not used, switch position 7 

must be kept “OFF” or it will cause the Fault Outputs to turn “ON” . Table 

2 illustrates the order of priority . For the Model 660-0XXXX, priority 2 

and 3 is N/A .

Table 2 – Milliamp Logic Chart

Priority

State

Load Current mA

1                   

Fire

20 ± 0 .2

2                        

Warning UV

16 ± 0 .2

3                            

Warning IR

15 ± 0 .2

4                

Fire Relay Coil Fault

3 ± 0 .2

5

Calibration not complete 

EEPROM Corrupted Fault

2 ± 0 .2

6

Self-Test Fault

1 ± 0 .2

7

Current Loop Fault

0 ± 0 .2

8

Normal

4 ± 0 .2

RS485 User Interface (UI)

The Series 660 and 860 Flame Detectors are equipped with a two 

wire, half-duplex, serial communication interface, which is called the 

“User Interface” (UI) . The RS485 UI will allow up to 31 detectors to 

be networked to a controller (i .e ., customized fire panel or personal 

computer) . The controller will perform the buss arbiter duties, 

because the network is in half-duplex mode . This means that only one 

transmitter is allowed on the network at one time .

DMLieferant     

Тел

.: +7 (499) 990-05-50; +7 (800) 775-29-59     dmliefer.ru

Summary of Contents for Omniguard 660 Series

Page 1: ...660 860 SERIES OPTICAL FLAME DETECTORS Installation and operating service manual DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Page 2: ...tricity from an ungrounded source including the human body may damage the electronic circuitry of the Omniguard Series 660 and 860 Flame Detectors Use one or more of the following methods when handlin...

Page 3: ...output Relay contacts rated at 2 Amps 30 VDC Resistive Operating Temperature 40 F to 185 F 40 C to 85 C Storage Temperature 85 F to 212 F 65 C to 100 C Standard Features High Temp Model Relay contact...

Page 4: ...oexistence of UV and IR radiation but also their presence in specific ratios The ratio must conform to the radiation pattern of specific fires see Figure 3 This patented Fire Event Analysis FEA ensure...

Page 5: ...ended for smoldering or electrical fire hazards The following is a partial list of fuels which emit ultraviolet and infrared radiation Response time and detection distances vary Consult Firefly AB app...

Page 6: ...so that it will view the base of the area to be protected 5 Complete the installation by wiring the detector according to the wiring diagram located inside the rear cover Before assembling the detect...

Page 7: ...8 Program 9 Option Off On No Program 9 Denotes factory settings for auto test units only Fig 9 switch configurations for the 660 0xxxx UV Flame detector SPST dip switch S1 located on board p n 71044...

Page 8: ...fails manual test will open when SW7 is on and no loop is present Note The amber LED will be illuminated when relay opens unless there is a loss of power Note Any adjustments to the user options liste...

Page 9: ...acket formation is comprised of the byte definition shown in Table 4 The first byte is the protocol start value for the control packet The second byte represents the detector address high byte which i...

Page 10: ...test A detector that fails auto test due to dirty optical surfaces may be capable of detecting fire but its effectiveness will be limited from 50 to 70 obscuration Cleaning Procedure Locate the follo...

Page 11: ...or 11 Look for loose or intermittent connections During normal operation the fault outputs will change state on power up The output will return to its original state if power to the detector is remove...

Page 12: ...workmanship or materials This warranty shall be valid only if the product is returned within the applicable warranty period to the factory at Stockholm Sweden properly packed and with all transportati...

Page 13: ...0 Latching 1 Non Latching Designation Ultraviolet flame detector To order Model 660 please specify Fire type 0 Hydrocarbon 1 Hydrocarbon Non hydrocarbon Housing material conduit entry 0 Aluminium 3 4...

Page 14: ...14 Firefly AB Oktober 2016 Notes DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Page 15: ...15 Firefly AB Oktober 2016 DMLieferant 7 499 990 05 50 7 800 775 29 59 dmliefer ru...

Page 16: ...8 449 25 00 Fax 46 0 8 449 25 01 E mail omniguardsales firefly se www omniguardbyfirefly se Address Heliosgatan 3 120 30 Stockholm Sweden Publication No 1031229 Rev M DMLieferant 7 499 990 05 50 7 800...

Reviews: