![Firefly Omniguard 660 Series Installation And Operating Service Manual Download Page 3](http://html1.mh-extra.com/html/firefly/omniguard-660-series/omniguard-660-series_installation-and-operating-service-manual_2291601003.webp)
3
©Firefly AB (Oktober 2016)
Description
The Omniguard® 660 and 860 Series Flame Detectors are optically
based, self-contained, microprocessor controlled, ultraviolet/infrared
(UV/IR) and high-speed ultraviolet (UV) flame detectors . The 860 Flame
Detector utilizes the patented Fire Event Analysis (FEA)™ discrimination
technology . These Flame Detectors are compatible with most alarm
panels without the need for a controller . All electronics are housed
within a copper-free aluminum, high temperature, TGIC-Polyester
coated enclosure with a 3/4-14NPT or M20-1 .5 conduit entry .
A stainless steel enclosure is also available .
The 660 and 860 Series Flame Detectors are suitable for use in Class
I, Division 1, Groups B, C and D (explosion-proof) areas and Class II,
Division 1, Groups E, F, and G (dust-ignition-proof) areas or
ll 2 G/D Exd llB + H
2
.T5 or T4 for gas,
Ex tb IIIC T100°C or T135°C Db for dust .
The housings are Type 4X or lP66, dust-tight and watertight . The
detectors are approved for both indoor and outdoor installations .
Standard Features (All Models)
•
Microprocessor Based .
•
User adjustable time delays .
•
User adjustable latching or non-latching fire relays .
•
User adjustable sensitivity .
•
User adjustable NO or NC relay outputs .
•
LED indication: fire (red), fault (amber) .
•
Transient voltage (surge) protection .
•
RS485 addressable user interface .
•
Terminal block accepts 22 to 12 AWG wire .
Standard Features (Industrial Models)
• 0 to 20 mA output .
•
Relay contacts rated at 2 Amps @ 30 VDC (Resistive) .
•
Operating Temperature: -40°F to 185°F (-40°C to 85°C) .
•
Storage Temperature: -85°F to 212°F (-65°C to 100°C) .
Standard Features (High Temp. Model)
• Relay contacts rated at 4 Amps @ 30 VDC (Resistive) .
• Operating Temperature: -40°F to 257°F (-40°C to 125°C) .
Storage Temperature: -85°F to 302°F (-65°C to 150°C) .
Optional Features (All Models)
• Stainless Steel Housing (explosion-proof) .
Approval:
• FM
• SIL 2
• CSA
• Russian Fire Certificate
• IECEx
• ATEX
• EMC
• LVD
• CSFM
Fire Detection Performance (All Models)
• 50 millisecond response to a saturating signal .
• One second typical to a 1 ft . by 1 ft . gasoline and N-heptane fire at
50 feet .
• Two seconds or less to a 2 ft . x 2 ft . fire of JP-4, JP-8, Jet A, Jet B,
AVTUR or AVGAS at 100 feet .
• Three seconds or less to a 10 ft . x 10 ft . fire of JP-4, JP-8, Jet A, Jet B,
AVTUR or AVGAS at 250 feet .
• 120 degree horizontal field-of-view (Figure 1) .
• 80 degree vertical field-of-view . (Figure 2) .
Fire Detection Performance (Model 860-1XXXX)
• 340 milliseconds or less to a silane flame from a 1 .10 inch orifice at
30 feet .
• 2 .9 seconds or less to an 8 inch diameter hydrazine fire at 60 feet .
• 3 .0 seconds or less to a hydrogen flame from a 0 .75 inch diameter
orifice with a flow rate of 1 .5 SCFM at 35 feet .
Response Time (Model 660 High Speed Setting)
• 15 milliseconds to a saturating UV source .
Note: Detector response times and distances can be influenced
by wind, smoke and viewing angle . Consult Firefly AB application
engineers for specific details .
(Fig 1) 660/860 horizontal field of view
(Fig 2) 660/860 vertical field of view
DMLieferant