Error Messages, Beeps and Flashes 

continued

Beep/Flash Sequence

What it means?

Remedy

Error Modes

Lo – (2secs) – Lo – (2secs) – Lo – (2secs) – etc.
O----------------O----------------O----------------etc.

Indicates Battery Lift is

not screwed down 

properly.

1. Screw down Battery Lift.

HiHiLo………………… 
O-O-O……………………  This pattern may repeat.

Possible fault with Motor.

1. Check Ferrule is not worn or   

damaged. Replace if 

necessary.

2. Perform Full Range Test.

3. Release tension on fixing

Screws and check Dorgard X

2

is positioned flat against door

with no obstructions.

4. Re-insert or if necessary, 

replace Batteries.

5. Check Ferrule is not 

obstructed and that the it

locates centrally in the 

Floorplate’s recess.

HiHiHiHiLoLoLoLo---(4secs)---

HiHiHiHiLoLoLoLo---(4secs)--- etc.

Indicates possible

Plunger movement fault.

See steps 1-5 above.

HiLoLoLo---(4secs)---HiLoLoLo---(4secs)---etc.
O O O O---(4secs)--- O O O O---(4secs)--- etc.

Indicates possible 

problem with Battery 

insertion.

See steps 1-5 above.

HiLo-------(17mins)------HiLo------(17mins)------etc.

(Dorgard X

2

will repeat HiLo 8 times after 68mins).

O O O O--(5secs)-- O O O O--(5secs)-- O O O O--
(5secs)-- etc.

Low Battery mode or 

miscellaneous error.

See steps 1-5 above.

24

Key:  *  LED flash GREEN

O LED flash RED

Summary of Contents for Dorgard X2

Page 1: ...Fitting and Operating Guide Cat A Cat B...

Page 2: ...6 Removing the Link from Dorgard X2 17 Removing a Link from System X 18 Troubleshooting and FAQs 19 Error Messages Beeps and Flashes 23 Errors and Codes 26 Installation Log Location Codes 27 Maintenan...

Page 3: ...System X transmitter have individual MAC addresses which allows each unit to be controlled individually and helps prevent cross chatter Fail to safe The activation of the Dorgard to release its door a...

Page 4: ...e Fitting Screws 4 x Rawl Plugs 1 x Small Plastic Screwdriver 1 x Standard Floorplate 1 x Flat Floorplate 2 x Duracell Procell LR14 C size Batteries 1 x Location Code Sticker 2 x Fire Door Sticker Too...

Page 5: ...d faults or disablements occur on the connected CIE Acoustic actuation is not permitted for this category Dorgard X2 installed and Linked to Hardwired System X complies with this part of the standard...

Page 6: ...losing force of the door 7 Where Dorgard X2 is to be fitted the floor and door surfaces are smooth and flat 8 There is clearance under the fire door for fitting of the Floorplate i e 5mm 9 The fire al...

Page 7: ...ssessment file for future reference BS EN1155 1997 states that a door must not be retained at an open angle of less than 65 degrees It is recommended that the Floorplate be installed to comply with th...

Page 8: ...re not to over tighten the Screw 4 The Dorgard X2 will beep and the LED Green will flash after Battery installation After installing a set of new Batteries the Dorgard X2 unit will fail to safe within...

Page 9: ...2 and System X has an individual MAC addresses ensuring direct association with each product It also means that Dorgard X2 will only communicate to the specific System X it is Linked to i e if a diffe...

Page 10: ...X2 unit lights green The Dorgard X2 is now searching for a TX to Link to 6 When Dorgard X2 has successfully Linked to the System X transmitter its motor will drive allowing the Plunger to be held down...

Page 11: ...hrough the Template 5 Using 2 of the 4 stainless steel Screws supplied fix Dorgard X2 to the fire door at points A and B of the fitting Template This will allow Dorgard X2 to be moved up and down slig...

Page 12: ...in other conditions such as where a wooden floor might deflect as persons walk by If the Dorgard X2 is being installed to replace a previously installed Dorgard where an older Floorplate has been fitt...

Page 13: ...l sitting centrally in the recess of the Floorplate 4 Mark the position of the Floorplates holes on to the floor surface When fitting to carpeted floors trim around the hole position to prevent the ca...

Page 14: ...ring that the Ferrule is still sitting centrally in the recess of the Flat Floorplate 4 Mark the position of the Flat Floorplates holes on to the floor surface When fitting to carpeted floors trim aro...

Page 15: ...r closer or the type of floor surface 4 Whilst depressing the Plunger push pull the door gently in the direction of closing 5 Remove your foot and let go of the door To release Dorgard X2 either A Lig...

Page 16: ...n for a minimum of 30 seconds 4 Dorgard X2 will release the fire door in approx 20 seconds 5 When Dorgard X2 is ready to release the door it will sound a Hi Lo warning tone repeated 8 times before rel...

Page 17: ...undetected is greater than during daylight hours To ensure that fire doors are closed at night Dorgard X2 can be set to release at a pre set time and then will not operate as a hold open device until...

Page 18: ...c Screwdriver gently press the Link Button on the front of the Dorgard X2 unit Hold this Button down until the LED located on top of the Dorgard X2 unit lights red and the Dorgard X2 motor drives foll...

Page 19: ...nks 1 On the System X transmitter press Button 1 LINK and Button 3 SCROLL together for 5 seconds to enter erase mode IND is displayed on the LCD 2 Use Button 1 LINK the LCD displays ALL 3 Hold Button...

Page 20: ...D display FIRE when the fire alarm is sounding Check fire alarm sounds for at least 30 seconds Check fire door is free to close unhindered Check that the Plunger has a minimum of 10mm of down travel b...

Page 21: ...k operation of the System X transmitter If installed as a Category B system adjust the sensitivity of the System X transmitter see System X User Guide Check Batteries on Dorgard X2 is unit beeping see...

Page 22: ...t the Ferrule has enough grip on the floor surface i e floor surface is not too slippery If so fit the Floorplate supplied Why does Dorgard X2 not retain the door in an open position Check that the Pl...

Page 23: ...this automatically Why are Receivers working sometimes and dropping out of range at other times Check Aerial on System X transmitter is connected and secure Check signal strength with Full Range Test...

Page 24: ...release its door No action required LoHi LoHi LoHi LoHi LoHi LoHi LoHi LoHi O O O O O O O O LoHi LoHi O O Dorgard X2 has released its door No action required LoLoLoHi Tone and flash sequence is follow...

Page 25: ...inst door with no obstructions 4 Re insert or if necessary replace Batteries 5 Check Ferrule is not obstructed and that the it locates centrally in the Floorplate s recess HiHiHiHiLoLoLoLo 4secs HiHiH...

Page 26: ...Dorgard X2 may have missed its reset command from System X Remove and re insert Batteries in the Dorgard X2 unit 4 Dorgard X2 may have missed 5 Call in messages in a row Check System X unit has not b...

Page 27: ...se faults with Dorgard X2 using System X s Full Range Test function See System X User Guide for more information Below are the error codes which can help diognose the problem with your Dorgard X2 Note...

Page 28: ...8 47 9 48 10 49 11 50 12 51 13 52 14 53 15 54 16 55 17 56 18 57 19 58 20 59 21 60 22 61 23 62 24 63 25 64 26 65 27 66 28 67 29 68 30 69 31 70 32 71 33 72 34 73 35 74 36 75 37 76 38 77 27 Installation...

Page 29: ...121 82 122 83 123 84 124 85 125 86 126 87 127 88 128 89 129 90 130 91 131 92 132 93 133 94 134 95 135 96 136 97 137 98 138 99 139 100 140 101 141 102 142 103 143 104 144 105 145 106 146 107 147 108 1...

Page 30: ...X2 Number Code Serial Number Location 158 198 159 199 160 200 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 19...

Page 31: ...he condition of the Ferrule 2 The Dorgard X2 unit is firmly attached to the door If any items are worn torn or damaged then replace immediately For further assistance contact the Technical Advice line...

Page 32: ...the history of the installation of the Dorgard X2 unit Further log books are available from the Technical Advice line Maintenance Record Serial Number Location Serial Number is on back of Dorgard X2...

Page 33: ...tically activated System X with Dorgard X2 O Category C acoustically activated Dorgard Variations for the recommendations of BS 7273 4 Clause 7 Brief description of release mechanisms method s of actu...

Page 34: ...mful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful...

Page 35: ...34 Notes...

Page 36: ...are functioning If this does not resolve the problem please contact us in writing at the e mail address shown below or telephone the Dorgard X2 Technical Advice line The warranty does not apply to an...

Reviews: