Error Code
Error
Error Description
00
No Error
Dorgard X
2
operating normally.
01
Batt warning flag
Low Battery level in Dorgard X
2
.
02
Batt low flag
Critically Low Battery level. Dorgard X
2
failed-to-safe.
04
Beacon loss flag
Communication with System X failure.
08
Tamper
Battery Lift not closed.
10
Test fault flag
Dorgard X
2
has missed its self-test command.
20
Plunger fault flag
Plunger movement fault.
40
Motor fault flag
Possible problem with motor.
80
Comms fault flag
Communication with System X timed out.
Errors and Codes
It is possible to diognose faults with Dorgard X
2
using
System X’s Full Range Test function. See System X User
Guide for more information.
Below are the error codes which can help diognose the
problem with your Dorgard X
2
. Note the error code is
displayed on the LCD on the System X transmitter, e.g.
‘
DG:xx
’ where ‘
xx
’ is the error code.
When diognosing a problem with a Dorgard X
2
, the
System X’s LCD will also display the Dorgards X
2
Battery
level and Signal strength. If Signal strength falls below
20% there is a chance of Dorgard X
2
failing due to missed
call-ins. If the Dorgard X
2
misses its call-ins it will
fail-to-safe, within 60 seconds for a category A system, or
60 minutes when installed as a category B system.
Dorgard X
2
will fail-to-safe when Battery level falls to 0%.