Troubleshooting and FAQs
19
Why is Dorgard X
2
not releasing to the Fire Alarm?
• Quick Range Test the system. Refer to the System X User Guide
• Have some Dorgard X
2
unit released and not others? If so conduct a Full Range Test (see
the System X User Guide)
• Have the Dorgard X
2
units been Linked to the System X transmitter?
• Has the System X been installed correctly? Does the LCD display ‘
FIRE
’ when the fire
alarm is sounding?
• Check fire alarm sounds for at least 30 seconds
• Check fire door is free to close unhindered
• Check that the Plunger has a minimum of 10mm of down travel before the Ferrule
contacts the floor or Floorplate
• If category B System X is installed, check the fire alarm is louder than 80 decibels where
the System X transmitter is situated. If so adjust the sensitivity of the System X
transmitter (see System X User Guide)
• Has the System X been installed on a staged fire alarm system?. Check installation of the
System X transmitter