5.4 Psuedo Points In FireClass
FireClass Fire detection system FireClass Panels
28
Service and Maintenance Doc.
version1
Field
Description
Address
Pseudo Point 43
Label
Walktest Sounders
Use
Sounders are walktested
using standard point
commands as directed from
the User Interface.
This point is set and cleared
surrounding that walktest to
place a record into the panel
log.
Table 23: Psuedo Point 43-Details
Field
Description
Address
Pseudo Point 44
Label
Inhibit Sound LED
Use
The system monitors the
isolate status of sounder
devices.
If all sounders are isolated this
point is set, once one sounder
is available the point is
cleared.
The activation of this point
inhibits the activation of the
sounder LED.
The goal is not to indicate on
the front panel that sounders
are active, when the system
knows they are all isolated.
Table 24: Psuedo Point 44-Details
Field
Description
Address
Pseudo Point 45
Label
Commissioning
Use
The system monitors the
commissioning states. If any
are active this point is raised.
Table 25: Psuedo Point 45-Details
Field
Description
Address
Pseudo Point 46
Label
Download Required
Use
In network configurations all
panels broadcast issue
details relating to their core
functionality. If this differs
between panels then the
network will not operate as
intended and full upload may
not be possible
Table 26: Psuedo Point 46-Details
Field
Description
Address
Pseudo Point 47
Label
Test Equipment
Use
This point is activated when
FireClass Checker is
connected to the panel.
Table 27: Psuedo Point 47-Details
Field
Description
Address
Pseudo Point 48
Label
Walktest Outputs
Use
This point is activated when
an output test is started from
the panel user interface.
Table 28: Psuedo Point 48-Details
Field
Description
Address
Pseudo Point 54
Label
Force Day Mode
Use
If the panel was in day mode
and a panel restart is
performed. This point is
activated to return to panel to
day mode.
Table 29: Psuedo Point 54-Details
Field
Description
Address
Pseudo Point 56
Label
Isolation For Test
Use
This point is activated if the
menu option to isolate non-
LED outputs is selected.
Table 30: Psuedo Point 56-Details