BalanCed Flue sItIng

The terminal should be positioned to avoid combustion products entering the building or accumulating in 

stagnant pockets around buildings. The terminal must be protected by a guard if it is less than 2 metres above 

ground level or in a position where any person has access to it (i.e. a balcony). a heat protection shield should be 

fitted if the terminal is less than 850mm from a plastic or painted gutter or less than 450mm from painted eaves. 

Prevailing winds should be taken into account when siting a flue.

always CHeCk For any BuIldIng regulatIons aMendMents wHICH May

Have Been Issued aFter tHe PuBlICatIon oF tHIs Manual

3

3.2 standards & regulatIons - Flue regulatIons

Clearances advised by Bs 5410-1: 2014

regular appliance (open, low level discharge and Balanced) Flue termination Clearance

The basic requirement with regard to flue positioning is that no hazard or nuisance is caused by the flue gases. 

Diagrams 20a and 20b show clearances advised by BS 5410-1: 2014.

Regional requirements where flue clearances differ can be found in the

regional requirements section in OFTeC Book Four.

A

G

E

B

C & D

K

F

F

L

N

O

P

H

J

Boundary

Boundary

F

Q

Q

Q

Q

Q

Q

Q

R

Pressure Jet

Location

Appliance Burner Type

Condensing

    

UK

  A  Directly below an opening, airbrick, opening window etc. 

1000mm

  B  Horizontally to an opening, airbrick, opening window etc. 

1000mm

  C  Below a gutter, eaves or balcony with protection 

1000mm

  D  Below a gutter or a balcony without protection 

1000mm

  E  From vertical sanitary pipe work 

300mm

  F  From an internal or external corner or surface or boundary alongside the terminal 

300mm

  G  Above ground or balcony level 

300mm

  H  From a surface or a boundary facing the terminal 

1200mm

  J 

From a terminal facing the terminal 

2500mm

  K  Vertically from a terminal on the same wall 1500mm
  L  Horizontally from a terminal on the same wall 

750mm

  M  Above the highest point of an intersection with the roof 

600mm

  N  From a vertical structure on the side of the terminal 

750mm

  O  Above a vertical structure less than 750mm from the side of the terminal 

600mm

  P  From a ridge terminal to a vertical structure on the roof 

1500mm

  Q  Above or to the side of any opening on a flat or sloping roof 

600mm

  R  Below any opening on a sloping roof 

2000mm

M

Minimum distances to terminals in millimeters as measured from the top of the chimney

or the outer edge of where flue gases pass through low level discharge openings

Diagram 20a

9

Summary of Contents for Enviromax Popular C26

Page 1: ...This manual must remain with the householder once installation is complete HEATING SOLUTIONS ENVIRONMENT INNOVATION TECHNOLOGY Technical Manual Condensing BoileR...

Page 2: ...mbustion Air Requirements 14 3 5 Liquid Fuel Supply 15 4 SYSTEM Condensing BOILER 4 1 End User Information 16 4 2 Installer Guidelines 19 4 3 Technical Details 21 5 SYSTEMPAC Condensing BOILER 5 1 End...

Page 3: ...ace the critical advantage provided by training and years of experience Firebird domestic condensing boilers are highly efficient and are all ErP A rated Energy related Products They use less fuel and...

Page 4: ...be sought following eye contact or prolonged reddening of the skin The small quantities of adhesives and sealants used in the product are cured They present no known hazards when used in the manner fo...

Page 5: ...ook Four Oil fired appliance system installation requirements Copies of British Standards may be purchased direct from BSI Customer Services 389 Chiswick High Rd London W4 4AL Tel 44 0 345 0869001 Int...

Page 6: ...in an unheated garage should not exceed 3 meters and Should be lagged with water proof insulation to prevent freezing Boiler Sealed Condensate Drain Discharge Pipe 75mm Soak Away Lime Stone Chippings...

Page 7: ...STANDARDS REGULATIONS Condensate Disposal Condensate Trap Fitting 1 Push washer into trap socket and screw trap onto boiler socket 2 Push flexible pipe onto trap socket 3 Final assembly Washer S S tr...

Page 8: ...3 3 1 STANDARDS REGULATIONS Condensate Disposal System No 2 Condensate Pump Indent Order Condensate PUMP kit is available as an optional extra 8...

Page 9: ...B C D K F F L N O P H J Boundary Boundary F Q Q Q Q Q Q Q R Pressure Jet Location Appliance Burner Type Condensing UK A Directly below an opening airbrick opening window etc 1000mm B Horizontally to a...

Page 10: ...or low level flue and low level balanced flue discharge when tested to BS EN 303 1 5 Terminating positions must be at least 1 8m distant from a fuel storage tank unless a wall with at least 30 minutes...

Page 11: ...disperse vapours 3 The effect of the moisture generated must be considered in relation to the possible corrosion of metal parts it might reach and to the possible formation of ice on pathways in freez...

Page 12: ...sing birdguard System 35 clamp plate System 35 clamp plate System 35 flexible liner suitable for condensing applications System 35 adaptor 500mm Adjustable length Boiler adaptor Condensing boiler Cond...

Page 13: ...ax length 6m Overall length must take into account bends where 45 bend 0 5m length and 90 bend 1m length INSTALLATION INSTRUCTIONS SUPPLIED WITH ALL FLUE KITS Elbows 45 90 Adjustable extensions 305 42...

Page 14: ...photocell has stopped a burner 1 Ensure that the gasket door is sealed correctly to the boiler 2 Ensure that the burner collar is in place If you see that the burner collar and surrounding area is ge...

Page 15: ...allow household waste or hot ashes container in vicinity of oil storage tank or boiler flue outlet 15 Flexible Oil Pipe s Two flexible burner Diesel hoses are supplied with the boiler which must be w...

Page 16: ...the event of the control thermostat failing and keeps the boiler safe The safety high limit thermostat will shut the boiler off and will require the limit button to be pushed to restart the boiler It...

Page 17: ...ING The boiler thermostat control and safety system is not designed and must not be relied on to protect plastic pipe from overheating Additional measures must be incorporated into the system pipework...

Page 18: ...e measured in bar equals static head of system measured in bar plus 0 3 Sealed Heating Circuit The system must comply with BS 7074 Part 1 and BS 5449 Part 1 with a maximum water temperature of 80 C A...

Page 19: ...n Mains cold water is supplied through the boiler drain fill valve Heating Circuit This is the heating system including the boiler which is filled from the mains supply via a flex filling loop to a pr...

Page 20: ...to operate the post purge function on the burner when applicable If a permanent live supply is not provided the burner will not operate Mains Burner Limit Lockout WIRING Electrical Supply The boiler a...

Page 21: ...Condensing output range Weight kg Dimensions mm H W D A B C E F G I J K L C26 System Condensing 26kW 148 856 555 618 760 231 165 210 580 648 341 78 62 93 C35 System Condensing 35kW 151 856 555 618 760...

Page 22: ...pocket ACC003PKT ACC003PKT 8 1 Condensate trap ACC000TRP ACC000TRP 9 1 Condensate hose ACC000FLX ACC000FLX 10 1 Heat deflector ACC000HTD ACC000HTD 11 1 Air hose ACC000SSH ACC000SSH 12 1 Control panel...

Page 23: ...mm dia plastic pipe 22 mm dia plastic pipe Circulating Pump 25 60 25 60 Integral Expansion Vessel Normal Capacity 12 litres 12 litres Expansion Vessel Pre charge Pressure 1 bar 1 bar Low Pressure Wate...

Page 24: ...the event of the control thermostat failing and keeps the boiler safe The safety high limit thermostat will shut the boiler off and will require the limit button to be pushed to restart the boiler It...

Page 25: ...IPING The boiler thermostat control and safety system is not designed and must not be relied on to protect plastic pipe from overheating Additional measures must be incorporated into the system pipewo...

Page 26: ...ure measured in bar equals static head of system measured in bar plus 0 3 Sealed Heating Circuit The system must comply with BS 7074 Part 1 and BS 5449 Part 1 with a maximum water temperature of 80 C...

Page 27: ...on Mains cold water is supplied through the boiler drain fill valve Heating Circuit This is the heating system including the boiler which is filled from the mains supply via a flex filling loop to a p...

Page 28: ...otection It is also required to operate the post purge function on the burner when applicable If a permanent live supply is not provided the burner will not operate WIRING Electrical Supply The boiler...

Page 29: ...J A L E F G K B Model Systempac Condensing output range Weight kg Dimensions mm H W D A B E F G I J K L C26 Systempac Condensing 26kW 160 945 597 651 795 242 92 633 44 271 133 121 236 C35 Systempac C...

Page 30: ...at pocket ACC003PKT ACC003PKT 8 1 Condensate trap ACC000TRP ACC000TRP 9 1 Condensate hose ACC000FLX ACC000FLX 10 1 Heat deflector ACC000HTD ACC000HTD 11 1 Pressure vessel ACC012PVL ACC012PVL 12 1 Insp...

Page 31: ...es 24 litres Flue Indoor Boilers Balanced Flue Assembly 125 5 mm dia 125 5 mm dia Max Low Level Flue Length 1 5m 1 5m Max High Level Balanced Flue Length 6m 6m Heating System Sealed Fit in accordance...

Page 32: ...done with the boiler in the condition it is going to be operating at that is if a balanced flue is installed the air hose is fixed on the burner In the case of a Slimline Heatpac ensure that the door...

Page 33: ...lear of all foreign matter Refill the system and again vent at all points as described Examine the complete system for water leaks having pressurised it to 1 2 5 bar Correct any leaks then check opera...

Page 34: ...leaks Draw off any accumulated water and sludge from the tank by opening the drain valve Turn off the diesel supply and remove the filter bowl then wash the element clean with diesel Fit a new element...

Page 35: ...nt qualified engineer using the correct installation and test equipment must carry out installation and commissioning 5 This warranty does not cover special incidental or consequential damages injury...

Page 36: ...Valve Location Condensate Trap where fitted Condensate Trap Piped to Drain Condensate Trap Primed Float and Condensate Trap in Place Check Flue Seals Deflector Plate and Baffles Graphite Door Seal and...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...e the specification of our products at any time and be without obligation to make similar changes in products previously produced MLOBNZEB000 For further information on Firebird products please contac...

Reviews: