67
Programming Reference Sheet
❐
60
Zone 4 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
61
Zone 5 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
62
❐
63
Waterflow Retard Timer.
Enter 0 - 89 additional seconds.
❐
64
AC Loss Reporting Delay.
Enter '0' for 6 hour delay; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10
hours; '5' for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19
hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❐
65
Alarm Presignal.
Enter '0' to disable alarm presignal; '1' to enable.
❐
66
❐
67
❐
68
Alarm Presignal Delay Time.
Enter 0 - 179 additional seconds (default - 120 seconds).
❐
69
Notification Appliance Circuit #1 Selection.
Enter '0' for enabled (silenceable); '1' for enabled
(nonsilenceable); '2' for disabled.
❐
70
Silence Inhibit NAC #1.
Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #1 for one minute.
❐
71
Autosilence NAC #1.
Enter '0' for no autosilence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4'
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❐
72
Coding NAC #1.
Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds On, 5 sec-
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off).
❐
73
Notification Appliance Circuit #2 Selection.
Enter '0' for enabled (silenceable); '1' for enabled
(nonsilenceable); '2' for disabled.
❐
74
Silence Inhibit NAC #2.
Enter '0' for no silence inhibit; '1' to inhibit silencing of NAC #2 for one minute.
❐
75
Autosilence NAC #2.
Enter '0' for no autosilence; '1' for 5 minutes; '2' for 10 minutes; '3' for 15 minutes; '4'
for 20 minutes; '5' for 25 minutes; '6' for 30 minutes.
❐
76
Coding NAC #2.
Enter '0' for steady; '1' for March Time (120 ppm); '2' for California (10 seconds On, 5 sec-
onds Off); '3' for Temporal (½ second On, ½ second Off, ½ second On, ½ second Off, ½ second On, 1½ second Off)
❐
77
Trouble Reminder.
Enter '0' to disable trouble reminder; '1' to enable.
❐
78
Annunciator Supervision.
Enter '0' for annunciator not present; '1' for annunciator present.
❐
79
Backup Reporting.
Enter '0' to report to secondary phone number as backup only; '1' to report to secondary
phone number for all reports/messages.
❐
80
Touchtone/Rotary Select.
Enter '0' for touchtone dialing; '1' for rotary dialing.
❐
81
Make/Break Ratio.
Enter '0' for 67/33 ratio; '1' for 62/38 ratio.
Summary of Contents for MS-5024
Page 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 7: ......
Page 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 54: ......
Page 56: ......
Page 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Page 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...