Fire-Lite Alarms MS-5024 Product Description Download Page 61

                  Document #50066    Rev.  D2    12/03/02     P/N 50066:D2

61

Slave Communicator Configuration

CHAPTER 6

Slave Communicator Configuration

The MS-5024 may be used as a slave communicator to a host or master FACP (fire alarm control panel).  All wiring 
between the master and the slave communicator is supervised.  4.7K ohm End-of-Line resistors should be connected.

In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host 
FACP.  The inputs have the following functions in the slave configuration:

• Zone 1/Channel 1 is used for general alarm

• Zone 2/Channel 2 is used for general trouble

• Zone 3/Channel 3 may be programmed to match the FACP relay function used as an input

• Zone 4/Channel 4 is used for supervisory

• Zone 5/Channel 5 may be programmed to match the FACP relay function used as an input

The factory settings for Zone 2/Channel 2 alarm and restoral are altered as follows:

If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, the report code for Zone 2 Alarm Code 
(address 83, 199) is 'F', Zone 2 Restoral Code (address 111, 227) is 'E'

If 1, A or C is entered for address 16 or 42, the report code for Zone 2 Alarm Code (addresses 84-85, 200-
201) is 'FF', Zone 2 Restoral Code (addresses 140-141, 256-257) is 'EF.'

The factory settings for Zone 4/Channel 4 alarm and restoral are altered as follows:

If 0, 2, 3, 4, 5, 6, 7, 8, 9, B or D is entered for address 16 or 42, report code for Zone 4/Channel 4 Alarm 
Code (address 85, 201) is '8', Zone 4 Restoral Code (address 113, 229) is 'E.' 

If 1, A or C is entered for addresses 16 or 42, the report code for Zone 4 Alarm Code (addresses 88-89, 204-
205) is 84, Zone 4 Restoral Code (addresses 144-145, 260-261) is 'E4.'

Location 56 must be programmed to a '1' to enable the control panel as a slave communicator.  

Be certain to connect the slave communicator’s primary AC power to the same branch circuit as the host FACP.

Note that Alarm Presignal and Alarm Verification do not function in Slave Communicator Mode.

Summary of Contents for MS-5024

Page 1: ...Fire Control Communicator MS 5024 MS 5024E PN 50066 D2 ECN 02 606 D Document 50066 12 03 02 Rev ...

Page 2: ...xplosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least o...

Page 3: ... anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former and ...

Page 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...

Page 5: ...B 17F 16 1 7 Specifications 16 1 8 Telephone Requirements and Warnings 17 1 8 1 Telephone Circuitry 17 1 8 2 Digital Communicator 17 1 8 3 Telephone Company Rights and Warnings 17 1 8 4 For Canadian Applications 18 CHAPTER 2 Installation 19 2 1 Mounting Options 19 2 2 Backbox Mounting 19 FIGURE 2 1 Cabinet Dimensions and Knockout Locations 20 FIGURE 2 2 Backbox and Battery Box 21 2 3 Operating Pow...

Page 6: ... 4 2 Standard and 4 2 Express Format Primary 35 TABLE 3 3 3 1 4 1 Express 4 1 Standard and Expanded 4 2 Expanded Secondary 37 TABLE 3 4 4 2 Standard and 4 2 Express Format Primary 39 FIGURE 3 2 Verification Timing Diagram 40 TABLE 3 5 41 CHAPTER 4 Operating Instructions 46 4 1 Switches 46 4 1 1 Reset 46 4 1 2 Silence 46 4 1 3 Mode 47 4 1 4 1st Event 47 4 1 5 Down Arrow 47 4 1 6 Up Arrow 47 4 1 7 E...

Page 7: ......

Page 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...

Page 9: ...e Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired CAN ULC S524M Standard for Installation of Fire Alarm Systems Other ...

Page 10: ...ocument 50066 Rev D2 12 03 02 P N 50066 D2 Note When dressing wires maintain a minimum of 0 25 distance between conductors to power limited and nonpower limited circuits TB1 Secondary Transformer Connector ...

Page 11: ...e features as the MS 5024 but allows connection to 220 240 VAC input Note that unless otherwise specified the term MS 5024 shall be used in this manual to refer to both the MS 5024 and MS 5024E Fire Control Communicators 1 1 Product Features Selectable as Fire Panel Fire Panel Communicator or Slave Communicator Programmable Zone ID 2 wire smoke Pull station Normally open contact Supervisory Superv...

Page 12: ...its NACA 2F Class A Converter module for Notification Appliance Cir cuits FIGURE 1 1 DP 5024 B B B B B A A B B B B B 1 2 3 4 1 1 2 2 3 4 TEST CONNECTOR J1 J3 BELLS 1 2 TB5 TB4 TB3 TB2 TB1 NO NC C NO NC C ZONE 1 ZONE 2 ZONE 4 ZONE 5 ZONE 3 PRIMARY SECONDARY KISS OFF LOAD LED 3 PRIMARY ACTIVE LED 1 SECONDARY ACTIVE LED 2 24V NON RESETTABLE 24V RESETTABLE FIGURE 1 2 MS 5024 Control Panel Notification...

Page 13: ...ration with one circuit also configurable for Style D Input circuits may be used as standard fire control panel zones or slave communicator input channels Initiating Device Circuit 1 Style B accepts Normally Open contact devices and 2 wire smoke detectors Initiating Device Circuit 2 Style B accepts Normally Open contact devices and 2 wire smoke detectors Initiating Device Circuit 3 Style B D accep...

Page 14: ...uch Tone programmable to rotary For tone burst or touchtone type formats discern proper Ack and Kissoff tone s the frequency and time duration of the tone s vary with the transmission format The control panel will adjust accordingly Communicate in the following formats 12 Tone Burst Types 20 pps 3 1 4 1 and 4 2 Standard 3 1 Expanded 4 1 Expanded 4 2 Expanded 2 Touchtone Types 4 1 Ademco Express an...

Page 15: ...paper labels permit an easy change of zone information refer to Figure 2 11 on page 28 Note that the RZA 5F Remote Annunciator requires the use of the ADM 24 Annunciator Driver Module Only one ADM 24 RZA 5F combination is allowed per system 1 6 3 CAC 5F The CAC 5F Class A Converter module converts the Style B Class B Initiating Device Circuits to Style D Class A The CAC 5F mounts to terminal block...

Page 16: ...rcuit current 42 mA maximum Maximum loop resistance 100 ohms End of Line Resistor 4 7K watt P N 27072 UL listed Detector loop current sufficient to ensure operation of one alarmed detector zone Standby current 7 26 mA includes ELR and 2 mA maximum detector current Smoke Detector Identifier A Refer to Fire Lite Device Compatibility Document for listed compatible devices Notification Appliance Circu...

Page 17: ...d by the total RENs contact the telephone company to determine the maximum REN for the calling area 1 8 2 Digital Communicator Before connecting the control panel to the public switched telephone network the installation of two RJ31X jacks is necessary The following information is provided if required by the local telephone company Manufacturer Fire Lite Alarms Inc One Fire Lite Place Northford CT...

Page 18: ...tions company The equipment must also be installed using an acceptable method of connection The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier Any repairs or alterations made by the user to this equipme...

Page 19: ... for wiring convenience Select the appropriate knockout s and pull the required conductors into the box Note that there are no knockouts located on the left hinged side of the cabinet All wiring should be in accordance with the National and or Local codes for fire alarm systems 2 2 Backbox Mounting Refer to Figure 2 1 on page 20 and Figure 2 2 on page 21 Make certain there is no power AC or DC app...

Page 20: ... 3 000 7 620 cm 1 250 3 175 cm 10 000 25 400 cm 1 250 3 175 cm 1 25 3 175 cm 1 25 3 175 cm 1 125 2 858 cm 0 875 2 223 cm 14 5 36 83 cm 3 25 8 255 cm 1 75 4 445 cm 3 5 8 89 cm 12 5 31 75 cm 4 125 10 478 cm 6 125 15 558 cm 8 125 20 638 cm 10 125 25 718 cm 1 000 2 540 cm 6 5 16 51 cm 9 500 24 130 cm 7 62 cm 3 0 FIGURE 2 1 Cabinet Dimensions and Knockout Locations Right Side Top Bottom TR 3 R Trim Rin...

Page 21: ...from the MS 5024 cabinet and BB 17F 3 Position the BB 17F near the MS 5024 cabinet and connect with conduit making sure there is at least of clearance between the two cabinets 4 Anchor the BB 17F to the wall RRU FP DFNER FP RRU FP DFNER FP 5LJKW VLGH HSWK FP HSWK FP DWWHU R FP 2SWLRQDO DWWHU R FP 2SWLRQDO 7 RS RWWRP 7 RS 85 DFNER DQG DWWHU R ...

Page 22: ...wer disconnect devices A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection Connect the Earth Ground wire minimum 14 AWG 2 00 mm2 to the grounding stud indicated by the ground symbol label Note that conduit must not be used for an Earth Ground connection since this does not provide reliable protection Secondary Power Source batteri...

Page 23: ... zones 2 wire Smoke Detector factory default Pull Station Normally Open Contact Device Supervisory Supervisory autoresettable Zone 3 may also be programmed as Waterflow silenceable Waterflow nonsilenceable Note A maximum of five waterflow devices may be used on Zone 3 per NFPA 72 Four wire smoke detectors may be connected to any zone Resettable power is provided via TB4 Terminals 3 4 It is allowab...

Page 24: ... a typical circuit connection Refer to the Fire Lite Device Compatibility Document for a listing of compatible notification appliances Note that both NACs may be converted to Style Z Class A by using an NACA 2F Class A Converter module refer to Figure 2 14 on page 30 FIGURE 2 5 Auxiliary Power Connections 1 2 3 4 Nonresettable Power 300 mA 24 VDC filtered nonresettable power can be obtained from T...

Page 25: ...ontacts rated for 2 0 amps 30 VDC resistive Each relay may be programmed for alarm trouble supervisory communications failure or any combina tion of these Refer to Figure 2 7 on page 25 for UL Power limited wiring requirements Note that all relay connections must be power limited or nonpower limited No mixing is permitted FIGURE 2 7 Programmable Relay Terminals Relay 1 Relay 2 Relay Connections Po...

Page 26: ... wiring must enter and exit the cabinet through different knockouts and or conduits A typical wiring diagram for the MS 5024 is shown below B B B B B A A B B B B B 1 2 3 4 1 1 2 2 3 4 TEST CONNECTOR J1 J3 BELLS 1 2 TB5 TB4 TB3 TB2 TB1 NO NC C NO NC C ZONE 1 ZONE 2 ZONE 4 ZONE 5 ZONE 3 PRIMARY SECONDARY KISS OFF LOAD LED 3 PRIMARY ACTIVE LED 1 SECONDARY ACTIVE LED 2 24V NON RESETTABLE 24V RESETTABL...

Page 27: ... possible via double line seizure as well as usage of an RJ31X style interconnection The control panel s digital com municator is built into the main circuit board Connection and wiring of two phone lines is required as shown below Note that it is critical that the digital communicator be located as the first device on the incoming telephone circuit to properly function FIGURE 2 9 Wiring Phone Jac...

Page 28: ...ion of the following Alarm Zone 1 red LED Alarm Zone 2 red LED Alarm Zone 3 red LED Alarm Zone 4 red LED Alarm Zone 5 red LED System Trouble yellow LED The remote annunciator provides individual zone alarm LEDs a system trouble LED a piezo sounder and a remote sounder shut off switch All LEDs and their wiring are supervised for open conditions Any open condition will cause the System Trouble LED t...

Page 29: ...tional Boards FIGURE 2 12 Wiring the RZA 5F ADM 24 ADM 24 RZA 5F Note Make wiring connections with system power off Maximum wire impedance is 100 ohms per wiring connection 24V FIGURE 2 13 Installing Annunciator in Single Gang Box screw 6 32 x 1 00 LG ...

Page 30: ...tes the nonsilenceable waterflow function FIGURE 2 14 NACA 2F Style Z Converter Module Polarized bell Polarized bell Polarized strobe Polarized horn Polarized horn Polarized strobe Note Notification Appliance Circuit polarity is shown in alarm state Style Z Notification Appliance Circuits are supervised and power limited Dummy load any unused circuits with 4 7K ohm ELR P N 71245 across B and B Ins...

Page 31: ...ful entry into Program Mode places the system into trouble A system off normal message is transmitted to the Central Station 3 1 Entering Program Mode To enter Program Mode press the MODE key once the display will go blank The user than has ten seconds to start entering the code 7764 7764 spells PROG on a Touch Tone phone If an incorrect key is entered reenter the proper 4 digit code before pressi...

Page 32: ...ory set to F from 00_F to 15_F Programming is typically done as follows If the phone number to be entered is 484 7161 press the 4 key The display will read 00_4 Press the ENTER STORE key to save the entry to memory and increment to the next address 01_F Enter the remaining numbers in their respective addresses as shown below Valid entries for both the primary and secondary phone numbers are 0 F wi...

Page 33: ...roper selection or consult our factory representatives For any format cho sen the control panel automatically programs all of the event codes See Table 3 1 Table 3 2 Table 3 3 and Table 3 4 CAUTION Default entries for event codes as shown in Table 3 1 through Table 3 4 are programmed into memory each time address 16 is altered Be certain to double check entries after programming the Zone Functions...

Page 34: ...ore Code E 118 Primary Zone 4 Disabled Restore Code E 119 Primary Zone 5 Disabled Restore Code E 120 Primary Drill Restore Code 9 121 Primary AC Fault Restore Code E 122 Primary Zone 1 Fault Restore Code E 123 Primary Zone 2 Fault Restore Code E 124 Primary Zone 3 Fault Restore Code E 125 Primary Zone 4 Fault Restore Code E 126 Primary Zone 5 Fault Restore Code E 127 Primary Earth Fault Restore Co...

Page 35: ...y Communication Trouble Secondary Fault Code FE 134 135 Primary Annunciator Fault Code FC 136 137 Primary System Off Normal Code FF 138 139 Primary Zone 1 Alarm Restore Code E1 140 141 Primary Zone 2 Alarm Restore Code E2 142 143 Primary Zone 3 Alarm Restore Code E3 144 145 Primary Zone 4 Alarm Restore Code E4 146 147 Primary Zone 5 Alarm Restore Code E5 148 149 Primary Zone 1 Disabled Restore Cod...

Page 36: ... sent to the Primary phone number may be sent every 6 8 12 or 24 hours If the message is to be sent every 24 hours leave the factory default entry of 0 If other test report times are needed enter 1 for 12 hours 2 for 8 hours or 3 for 6 hours Secondary Central Station Phone Number 26 41 The sixteen addresses 26 41 are factory set to F from 26_F to 41_F Programming is typically done as follows If th...

Page 37: ...lt our factory representatives For any format cho sen the control panel automatically programs all of the event codes See Table 3 1 Table 3 2 Table 3 3 and Table 3 4 CAUTION Default entries for event codes as shown in Table 3 1 through Table 3 4 are programmed into memory each time address 42 is altered Be certain to double check entries after programming the Zone Functions addresses 57 61 Program...

Page 38: ...e Code E 234 Secondary Zone 4 Disabled Restore Code E 235 Secondary Zone 5 Disabled Restore Code E 236 Secondary Drill Restore Code 9 237 Secondary AC Fault Restore Code E 238 Secondary Zone 1 Fault Restore Code E 239 Secondary Zone 2 Fault Restore Code E 240 Secondary Zone 3 Fault Restore Code E 241 Secondary Zone 4 Fault Restore Code E 242 Secondary Zone 5 Fault Restore Code E 243 Secondary Eart...

Page 39: ...ndary Communication Trouble Secondary Fault Code FE 250 251 Secondary Annunciator Fault Code FC 252 253 Secondary System Off Normal Code FF 254 255 Secondary Zone 1 Alarm Restore Code E1 256 257 Secondary Zone 2 Alarm Restore Code E2 258 259 Secondary Zone 3 Alarm Restore Code E3 260 261 Secondary Zone 4 Alarm Restore Code E4 262 263 Secondary Zone 5 Alarm Restore Code E5 264 265 Secondary Zone 1 ...

Page 40: ...s or 3 for 6 hours Alarm Verification 52 Alarm verification works only on zones programmed as 2 wire smoke detector zones After detecting an alarm the control panel removes power from all zones for 6 seconds resetting all 2 wire smoke detectors Power is reapplied and a 12 second retard period allows detectors to stabilize During the retard reset period of 18 seconds subsequent alarms by the same i...

Page 41: ...mmed in address 54 The default factory setting for this address is 4 for activa tion on trouble only Valid entries for address 54 are 0 through F as listed above Future Use 55 Slave Communicator Fire Panel Selection 56 Leaving address 56 at 0 causes the control panel to operate as a fire panel only Selecting 1 will cause the panel to operate as a slave communicator only Selecting 2 will cause the ...

Page 42: ...ory or supervisory autoresettable will cause the defaulted event codes note in Table 3 1 through Table 3 4 to be automatically changed The defaulted code of 1 is changed to 8 for Formats 3 1 and 4 1 Standard and Expanded 4 2 Expanded and 4 1 Express The defaulted codes of 11 12 13 14 and 15 are changed to 81 82 83 84 and 85 accordingly for Formats 4 2 Standard and 4 2 Express Waterflow Retard Time...

Page 43: ...vents silencing of Notification Appliance Circuit 1 and the on board piezo sounder for one minute after an alarm The factory default setting is 0 for no silence inhibit of Notification Appliance Circuit 1 Autosilence Notification Appliance Circuit 1 71 Notification Appliance Circuit 1 may be autosilenced after a programmed time interval between 5 and 30 minutes Enter 1 for 5 minute autosilence 2 f...

Page 44: ... the Primary Central Station Number Communication Format address 16 and the Secondary Central Sta tion Number Communication Format address 42 automatically program addresses 82 313 with factory default selections Any of the event codes may be changed Consult your Central Station prior to altering the event codes Entering an event code of 0 will cause the communicator to not transmit the report For...

Page 45: ...z The software for the MS 5024E operates the internal clock based upon 50 Hz End Programming Exit Programming Mode by pressing the MODE key followed by the 4 digit code corresponding to an alternate mode of operation then press the ENTER STORE key During Program Mode if no key is pressed within 10 minutes the control panel will revert to Normal Mode ...

Page 46: ...tus LEDs Turn off the Notification Appliance Circuits Reset all zones by temporarily removing power Silence the on board piezo sounder Store reset message in the History file Restore the programmable relays to normal Temporarily remove power from the resettable power output TB4 Terminals 3 4 Upon release of the Reset Switch the display will read rES_ for six seconds Any alarm supervisory or troubl...

Page 47: ...iew other events newer that have occurred and are active not yet cleared 4 1 7 ENTER STORE See individual mode descriptions in other sections of this manual 4 2 Display and LEDs Four 7 segment red LED characters provide visual annunciation of status events and messages A list of messages that may appear on the display in Normal Mode is shown below d__1 Zone 1 Disabled d__2 Zone 2 Disabled d__3 Zon...

Page 48: ...tely Supervisory A yellow LED that blinks to indicate the need for action in connection with the supervision or maintenance of sprinklers extinguishing systems or other protective systems System Silence A yellow LED that turns on to indicate that an alarm or trouble condition exists in the system but both Notification Appliance Circuits if programmed as silenceable and local piezo have been silenc...

Page 49: ...e 1st Event key will stop the scrolling and cause the display of the first alarm that occurred after the panel was last reset cleared of all active events and placed into Normal Mode Operation of the Up and Down arrow keys will display all remaining events in order of their occurrences 4 3 1 Alarm Response The control panel will upon detection of an alarm condition Turn on the alarm LED Activate r...

Page 50: ...he supervisory LED Deactivate the supervisory relay s if programmed Clear the display of the SUP message Communicate a supervisory restoral message to the Central Station Turn off the piezo sounder Turn off the annunciator zone LED and annunciator piezo sounder Note that for any zone programmed for supervisory autoresettable the Reset key does not need to be pressed to clear the zone supervisory c...

Page 51: ... 3472 spells DISA on a Touch Tone phone A flashing lower case d will appear on the far left of the display Press the zone number to be disabled The number will appear on the far right display character Pressing the ENTER STORE key will disable the selected zone Note that the relay if programmed for trouble is activated and the trouble LED will blink The zone disable message will remain on the disp...

Page 52: ...wer is restored the no battery no_b message will appear The battery must be disconnected from the system and either replaced or allowed to restore itself before being reinstalled CAUTION Be certain to clear the no battery condition since the battery will not recharge from this condition and the panel will not clear itself The low battery condition will self clear when the battery recharges provide...

Page 53: ...mat 3 5 7 9 Format 1 A C Format B D Report 3 1 4 1 Standard 4 1 Express 3 1 4 1 Expanded 4 2 Standard 4 2 Express 4 2 Expanded Alarm SSS S A SSS S A AAA A Z SSSS AA2 SSSS AZ Alarm Restore SSS S RA SSS S RA RARARA RA Z SSSS RARA2 SSSS RAZ Zone Trouble Zone Open SSS S TZ SSS S TZ TZTZTZ TZ Z SSSS TZTZ2 SSSS TZZ Zone Trouble Restore SSS S RTZ SSS S RTZ RTZRTZRTZ RTZ Z SSSS RTZRTZ2 SSSS RTZZ System Tr...

Page 54: ......

Page 55: ...phone Line Fault Notification Appliance Circuits Fault Communication Trouble Annunciator Trouble System Off Normal 4 Restoral Reports Zone Alarm Supervisory Zone s Enabled Fire Drill AC Zone Fault Earth Battery Telephone Line Notification Appliance Circuits Communication Annunciator Trouble System Off Normal 5 24 Hour Test Lowest Priority Red LEDs are provided on the control panel circuit board to...

Page 56: ......

Page 57: ...uits for four seconds for the first alarm on a zone Subsequent alarms will sound for one second Troubles cause the Notification Appliance Circuits to remain on Disable the alarm relay s if programmed Display all alarm conditions as they occur Display all zone troubles as they occur Display ground faults as they occur Transmit off normal message to Central Station s Continue to communicate any even...

Page 58: ...t the off normal message to the Central Station s Continue to communicate any events not previously acknowledged at the Central Station prior to entering His tory Mode The Down arrow key moves the History file to show older previous events The Up arrow key moves the History file to show newer most recent events Shown below is the list of messages as they will appear on the display To erase the lis...

Page 59: ...on in this mode 5 3 1 Zones Pressing 01 through 05 followed by the ENTER STORE key displays the zone voltage of the selected zone Listed below are the nominal threshold voltages for each zone Zone Normal w EOL Shorted Open Circuit 1 through 5 23 5V 00 0V 25 4V 5 3 2 AC Line Pressing A followed by the ENTER STORE key displays the AC input voltage as shown below The following lists the AC line volta...

Page 60: ...dialing Once the first digit is pressed the display will move the C or D character one position to the left while placing the digit to be dialed on the farthest right display position Continue to press the phone numbers to be dialed Successive depressions of the ENTER STORE key hangs up and picks up the phone places the phone on or off the hook The secondary phone line may be tested by pressing th...

Page 61: ...larm and restoral are altered as follows If 0 2 3 4 5 6 7 8 9 B or D is entered for address 16 or 42 the report code for Zone 2 Alarm Code address 83 199 is F Zone 2 Restoral Code address 111 227 is E If 1 A or C is entered for address 16 or 42 the report code for Zone 2 Alarm Code addresses 84 85 200 201 is FF Zone 2 Restoral Code addresses 140 141 256 257 is EF The factory settings for Zone 4 Ch...

Page 62: ... 50066 D2 Relays in the master FACP activate various input circuits on the slave communicator Messages event codes pro grammed for a particular input circuit channel will be transmitted to the Central Station upon relay activation FIGURE 6 1 Slave Communicator Connections ...

Page 63: ...an be located in the backbox 2 12 Ampere Hour and 17 Ampere Hour batteries require the BB 17F battery box TABLE A 1 Battery Calculations Standby Load Current amps X Required Standby Time in Hours 24 or 60 Hours __________ Alarm Load Current amps X Required Alarm Time in Hours i e 5 minutes 0 084 __________ Add Standby and Alarm Load for Required Ampere Hour Battery __________ Multiply by the Derat...

Page 64: ...e detectors be sure to power detectors from TB4 Terminals 3 4 Note that all external devices are connected to TB4 only Notes 1 Refer to the Device Compatibility Document for 2 wire smoke detector standby current 2 Must use compatible listed Power Supervision Relay TABLE A 2 Regulated Load in Standby Device Type of Devices Current amps Total Current amps Main Circuit Board 1 X 0 123 0 123 ADM 24 1 ...

Page 65: ...five zones in alarm For one zone in alarm the RZA 5F current draw is 16 mA 5 The current shown represents one zone on the Main Circuit Board in alarm For all five zones in alarm the current draw increases to 0 39 amps 6 Relays may be programmed for alarm trouble supervisory communications failure or any combination of these TABLE A 3 Regulated Load in Alarm Device Type of Devices Current amps Tota...

Page 66: ...ure B for Alarm or Supervisory or Communication Failure C for Trouble or Communication Failure D for Alarm or Trouble or Communication Failure E for Supervisory or Trouble or Communication Failure F for Alarm or Supervisory or Trouble or Communication Failure 54 Programmable Relay 1 Enter 0 to Disable 1 for Alarm 2 for Supervisory 3 for Alarm or Supervisory 4 for Trouble 5 for Alarm or Trouble 6 f...

Page 67: ...ne minute 71 Autosilence NAC 1 Enter 0 for no autosilence 1 for 5 minutes 2 for 10 minutes 3 for 15 minutes 4 for 20 minutes 5 for 25 minutes 6 for 30 minutes 72 Coding NAC 1 Enter 0 for steady 1 for March Time 120 ppm 2 for California 10 seconds On 5 sec onds Off 3 for Temporal second On second Off second On second Off second On 1 second Off 73 Notification Appliance Circuit 2 Selection Enter 0 f...

Page 68: ...162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 ...

Page 69: ... Secondary Central Station Account Code 47 48 49 50 Secondary Central Station 24 Hour Test Time 0000 12 00 midnight 51 Secondary Number Test Time Interval 0 for 24 hours 52 Alarm Verification 0 for no verification 53 Programmable Relay 1 1 for alarm only 54 Programmable Relay 2 4 for trouble only 55 Future use 56 Slave Communicator Fire Panel Selection 0 for fire panel only operation 57 Zone 1 Fun...

Page 70: ... NAC 2 0 for no silence inhibit 75 Autosilence NAC 2 0 for no autosilence 76 Coding NAC 2 0 for steady no coding 77 Trouble Reminder 0 for no trouble reminder 78 Annunciator Printer Supervision 0 for annunciator not present 79 Backup Reporting 0 to report to secondary phone number as backup only 80 Touchtone Rotary Select 0 for touchtone dialing 81 Make Break Ratio 0 for 67 33 ratio 0 0 0 0 0 0 0 ...

Page 71: ...1 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 1 1 1 2 1 3 1 4 1 5 F 1 F 2 F ...

Page 72: ...ections Wire Requirements Circuit Type Circuit Function Wire Type and Limitations Recommended Maximum Distance feet m Wire Gauge InitiatingDevice Circuit power limited Connects to Initiating Devices Untwisted unshielded wire Do not exceed 100 ohms 10 000 3 000 m 8 000 2 400 m 4 875 1 480 m 3 225 980 m 12AWG Belden 9582 14AWG Belden 9580 16AWG Belden 9572 18AWG Belden 9571 0 75 mm2 3 25 mm2 24 VDC ...

Page 73: ... History File Fire protection is off 8768 TROU Activates internal system voltmeter for troubleshooting and diagnosing problems Fire protection is off while voltmeter function is enabled 5267 LAMP Turns on all LEDs on the main PCB for 5 seconds Fire protection is on TABLE D 2 Function Modes Code Activity Notes 3472 DISA Allows disabling of any input zone May only disable one zone at a time Places s...

Page 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...

Page 75: ...on formats 14 communicator 11 controls 13 current 11 D description 11 dial tone 14 dialing 14 digital communicator 14 17 27 display 47 Down Arrow 47 E ENTER STORE 47 event codes programming 44 exit programming 45 export version 11 F Fire Drill 52 fire panel 41 fire panel communicator 11 format communication 33 37 formats communication 14 function modes 73 H history 58 history file 11 I IDC 16 23 s...

Page 76: ...nce inhibit 11 programming 43 size 11 slave communicator 11 41 61 specifications 16 Supervisory 48 Supervisory Condition Response 50 Supervisory Restoral Response 50 switches 46 System Alarm 48 System Silence 48 System Trouble 48 T telephone circuit 13 17 24 telephone circuits wiring 27 test time 36 40 interval 36 40 tone burst 14 touchtone 14 programming 44 transformer 14 Transmittal Priorities 5...

Page 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...

Page 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...

Page 79: ...ransportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that the manufacturer is not an insurer a...

Page 80: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...

Reviews: