Programming Reference Sheet
66
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Appendix B
Programming Reference Sheet
❐
00
❐
01
❐
02
❐
03
❐
04
❐
05
❐
06
❐
07
❐
08
❐
09
❐
10
❐
11
❐
12
❐
13
❐
14
❐
15
Addresses 00 to 15 store the Primary Central Station Phone Number.
Enter 'F' to represent the end of the number.
❐
16
Primary Central Station Communication Format:
Enter '0 - D'.
❐
17
❐
18
❐
19
❐
20
Primary Central Station Account Code:
Valid entries are '0 - F'.
❐
21
❐
22
❐
23
❐
24
Primary Central Station 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❐
25
Primary Number Test Time Interval.
Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
❐
26
❐
27
❐
28
❐
29
❐
30
❐
31
❐
32
❐
33
❐
34
❐
35
❐
36
❐
37
❐
38
❐
39
❐
40
❐
41
Addresses 26 to 41 store the Secondary Central Station Phone Number.
Enter 'F' to represent the end of the number.
❐
42
Secondary Central Station Communication Format:
Enter '0 - D'.
❐
43
❐
44
❐
45
❐
46
Secondary Central Station Account Code:
Valid entries are '0 - F'.
❐
47
❐
48
❐
49
❐
50
Secondary Central Station 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❐
51
Secondary Number Test Time Interval.
Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
❐
52
Alarm Verification.
Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
❐
53
Programmable Relay 1:
Enter '0' to Disable; '1' for Alarm; '2' for Supervisory; '3' for Alarm or Supervisory;
'4' for Trouble; '5' for Alarm or Trouble; '6' for Supervisory or Trouble; '7' for Alarm or Supervisory or Trouble; '8'
for Communication Failure; '9' for Alarm or Communication Failure; 'A' for Supervisory or Communication Fail-
ure; 'B' for Alarm or Supervisory or Communication Failure; 'C' for Trouble or Communication Failure; 'D' for
Alarm or Trouble or Communication Failure; 'E' for Supervisory or Trouble or Communication Failure; 'F' for
Alarm or Supervisory or Trouble or Communication Failure.
❐
54
Programmable Relay 1:
Enter '0' to Disable; '1' for Alarm; '2' for Supervisory; '3' for Alarm or Supervisory;
'4' for Trouble; '5' for Alarm or Trouble; '6' for Supervisory or Trouble; '7' for Alarm or Supervisory or Trouble; '8'
for Communication Failure; '9' for Alarm or Communication Failure; 'A' for Supervisory or Communication Fail-
ure; 'B' for Alarm or Supervisory or Communication Failure; 'C' for Trouble or Communication Failure; 'D' for
Alarm or Trouble or Communication Failure; 'E' for Supervisory or Trouble or Communication Failure; 'F' for
Alarm or Supervisory or Trouble or Communication Failure.
❐
55
Future use.
❐
56
Slave Communicator/Fire Panel Selection.
Enter '0' for fire panel only; '1' for slave communicator only; '2'
for fire panel/communicator operation.
❐
57
Zone 1 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
58
Zone 2 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
59
Zone 3 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6'
for waterflow (nonsilenceable).
...To enter Programming Mode, press the
MODE
key, the code
7764
and then the
[ENTER/STORE]
key...
Summary of Contents for MS-5024
Page 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 7: ......
Page 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 54: ......
Page 56: ......
Page 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Page 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...