Document #50066 Rev. D2 12/03/02 P/N 50066:D2
41
Programming Options
Programmable Relay #1 (53)
Programmable Relay #1 may be programmed to activate on alarm, trouble, supervisory, communication failure or
any combination of the four conditions. The default (factory) setting for this address is '1' for activation on alarm
only. Valid entries for address 53 are '0' through 'F' as listed below:
0 = Disable
1 = Alarm
2 = Supervisory
3 = Alarm or Supervisory
4 = Trouble
5 = Alarm or Trouble
6 = Supervisory or Trouble
7 = Alarm or Supervisory or Trouble
8 = Communication Failure
9 = Alarm or Communication Failure
A = Supervisory or Communication Failure
B = Alarm or Supervisory or Communication Failure
C = Trouble or Communication Failure
D = Alarm or Trouble or Communication Failure
E = Supervisory or Trouble or Communication Failure
F = Alarm or Supervisory or Trouble or Communication Failure
Programmable Relay #2 (54)
Programmable Relay #2 is programmed in address 54. The default (factory) setting for this address is '4' for activa-
tion on trouble only. Valid entries for address 54 are '0' through 'F' as listed above.
Future Use (55)
Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at '0' causes the control panel to operate as a
fire panel only
. Selecting '1' will cause the panel to
operate as a
slave communicator only
. Selecting '2' will cause the panel to operate as a
fire panel/communicator
.
Zones 1-5 Function Selection (57-61)
The five zones on the control panel may be programmed as shown below. Program entries alter zone function and
transmittal priority.
TABLE 3-5:
Program Entry
Function
0
Operates 2-wire smoke detectors
1
Pull station
2
Normally open contact device
3
Supervisory
4
Supervisory autoresettable. Self-restore function, is not latched by the control panel
5
Waterflow silenceable. Silencing of silenceable Notification Appliance Circuits
allowed. Affects zone 3 only.
6
Waterflow nonsilenceable. Silencing of silenceable Notification Appliance Circuits
not allowed. Must clear waterflow alarm condition and press reset key. Affects zone 3
only
Summary of Contents for MS-5024
Page 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 7: ......
Page 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 54: ......
Page 56: ......
Page 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Page 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...