Battery Calculations
64
Document #50066 Rev.D2 12/03/02 P/N 50066:D2
Main Power Supply
The MS-5024 provides filtered power for operating the fire alarm control panel, operating external devices and oper-
ating the standby battery. The power for operating external devices is limited. Use Table A-2 (standby or nonalarm)
and Table A-3 on page 65 (alarm) to determine if external loading is within the capabilities of the power supply.
Concerning 4-wire smoke detectors: be sure to power detectors from TB4, Terminals 3 & 4.
Note that all external devices are connected to TB4 only.
Notes:
1.
Refer to the Device Compatibility Document for 2-wire smoke detector standby current
2.
Must use compatible listed Power Supervision Relay
TABLE A-2:
Regulated Load in Standby
Device Type
# of Devices
Current
(amps)
Total Current
(amps)
Main Circuit Board
1
X
0.123
=
0.123
ADM-24
(1 maximum)
X
0.006
=
RZA-5F
(1 maximum)
X
0
=
0
CAC-5F
(1 maximum)
X
0
=
0
NACA-2F
(1 maximum)
X
0
=
0
2-wire Detector Heads
[ ]
X
[ ]
1
=
4-wire Detector Heads
[ ]
X
[ ]
1
=
Power Supervision Relays
2
[ ]
X
0.025
=
Additional Current Draw
from TB4 (nonalarm)
X
=
Sum Column for Standby Load
=
amps
Summary of Contents for MS-5024
Page 4: ...4 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 7: ......
Page 8: ...8 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 54: ......
Page 56: ......
Page 74: ...74 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...
Page 77: ...Document 50066 Rev D2 12 03 02 P N 50066 D2 77 Notes ...
Page 78: ...78 Document 50066 Rev D2 12 03 02 P N 50066 D2 Notes ...