Events and Default Event Codes
Note: The character ‘x’ in the following table refers to the input circuit number (1 - 4).
Group Definitions:
Format Group 1
4+2 Ademco Express Standard, DTMF
1400/2300 Hz ACK
3+1 Expanded 1800 Hz Carrier
2300 Hz ACK
3+1 Expanded 1900 Hz Carrier
1400 Hz ACK
4+1 Expanded 1800 Hz Carrier
2300 Hz ACK
4+1 Expanded 1900 Hz Carrier
1400 Hz ACK
4+2 Standard 1800 Hz Carrier
2300 Hz ACK
4+2 Expanded 1800 Hz Carrier
2300 Hz ACK
4+2 Standard 1900 Hz Carrier
1400 Hz ACK
4+2 Expanded 1900 Hz Carrier
1400 Hz ACK
Format Group 2
4+1 Ademco Express Standard, DTMF
1400/2300 Hz ACK
3+1 Standard 1800 Hz Carrier
2300 Hz ACK
3+1 Standard 1900 Hz Carrier
1400 Hz ACK
4+1 Standard 1800 Hz Carrier
2300 Hz ACK
4+1 Standard 1900 Hz Carrier
1400 Hz ACK
Note that although all Expanded Mode formats communicate two digits per event, only the first digit is
programmable. The second digit cannot be changed.
411UDAC Events
Format Group 1
Format Group 2
Ademco Contact ID
Input Circuit Functions
Active
Restore
Active
Restore
Active and
Restore
Sensor #
2-Wire Smoke
1x
Ex
1
E
111
00x
Pull Station
1x
Ex
1
E
115
00x
Contact Closure
1x
Ex
1
E
110
00x
Host Control Panel Trouble
FF
Ex
F
E
373
00x
Latching Supervisory
8x
Ex
8
E
200
00x
Autoresettable Supervisory
8x
Ex
8
E
200
00x
Silenceable Waterflow
1x
Ex
1
E
113
00x
Nonsilenceable Waterflow
1x
Ex
1
E
113
00x
Latching Process Monitor
00
Ex
0
E
000
00x
Autoresettable Process Monitor
00
Ex
0
E
000
00x
Other Events
Active
Restore
Active
Restore
Active and
Restore
Sensor #
Input Circuit Fault
Fx
Dx
F
D
380
00x
AC Fault
92
93
9
9
301
000
Earth Fault
61
A1
6
A
310
000
Low Battery Fault
62
A2
6
A
302
000
No Battery Fault
63
A3
6
A
311
000
Phone Line 1 Fault
64
A4
6
A
351
000
Phone Line 2 Fault
65
A5
6
A
352
000
NAC Fault
66
A6
6
A
321
000
Phone Number 1 Fault
6A
AA
6
A
354
001
Phone Number 2 Fault
6B
AB
6
A
354
002
System Off Normal Fault
6F
AF
6
A
308
000
Special Events
Active
Restore
Active
Restore
Active and
Restore
Sensor #
System Test Message
99
-
9
-
602
000
System Abnormal Test Message
91
-
F
-
608
000
Upload/Download Request
71
-
7
-
411
000
Upload Successful
72
-
7
-
416
000
Download Successful
73
-
7
-
412
000
Upload/Download Failed
74
-
7
-
412
000
Summary of Contents for Fire-Watch 411UDAC
Page 18: ...Mounting 18 Document 51073 Rev A 1 19 99 P N 51073 A FIGURE 2 3 411UDAC Backbox 411ACABB CDR ...
Page 80: ...80 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 82: ...82 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 83: ...Document 51073 Rev A 1 19 99 P N 51073 A 83 Notes ...