Central Station Communications
54
Document #51073 Rev.A 1/19/99 P/N 51073:A
Where:
SSS or SSSS
= Subscriber ID
FA
= Fire Alarm (1st digit)
FA2
= Fire Alarm (2nd digit)
Z
= Channel/Input Number
RFA
= Fire Alarm Restore (1st digit)
RFA2
= Fire Alarm Restore (2nd digit)
TZ
= Zone Trouble (1st digit)
TZ2
= Zone Trouble (2nd digit)
RTZ
= Zone Trouble Restore (1st digit)
RTZ2
= Zone Trouble Restore (2nd digit)
TS
= System Trouble (1st digit)
TS2
= System Trouble (2nd digit)
RTS
= System Trouble Restore (1st digit)
RTS2
= System Trouble Restore (2nd digit)
P
= AC Loss (1st digit)
P2
= AC Loss (2nd digit)
RP
= AC Loss Restore (1st digit)
RP2
= AC Loss Restore (2nd digit)
V
= Fire Supervisory Condition (1st digit)
V2
= Fire Supervisory Condition (2nd digit)
RV
= Fire Supervisory Condition Restore (1st digit)
RV2
= Fire Supervisory Condition Restore (2nd digit)
X
= Test Report (1st digit)
X2
= Test Report (2nd digit)
Y
= Trouble corresponding to the following:
1 = Not Used
2 = Not Used
3 = Not Used
4 = Telco Primary Line Fault
5 = Telco Secondary Line Fault
6 = Not Used
7 = Not Used
8 = Not Used
9 = Not Used
A = Communication Failure Primary Number
B = Communication Failure Secondary Number
C = Not Used
D = Not Used
E = Not Used
F = System Off Normal
UD
= Upload/Download (1st digit)
UD2
= Upload/Download (2nd digit)
Note that for Expanded Reporting, the digital communicator automatically adds the digit corresponding to the
Channel/Input number, and the second digit corresponding to any system trouble condition. Only the first digit
shown in Table 3-3 and Table 3-6 is programmable.
TABLE 4-2:
Format Selection Address Explanation
Summary of Contents for Fire-Watch 411UDAC
Page 18: ...Mounting 18 Document 51073 Rev A 1 19 99 P N 51073 A FIGURE 2 3 411UDAC Backbox 411ACABB CDR ...
Page 80: ...80 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 82: ...82 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 83: ...Document 51073 Rev A 1 19 99 P N 51073 A 83 Notes ...