Document #51073 Rev. A 1/19/99 P/N 51073:A
37
Program Mode
4+2 Standard and 4+2 Express Formats Primary Central Station Event Codes
If ‘1, A or C’ is entered for address 20, the following data is automatically programmed for the Primary Central
Station phone number event codes. Enter '00' for the Setting to disable the report to the Central Station.
TABLE 3-2:
4+2 Standard and 4+2 Express Formats - Primary
Address
Description
Setting
145 - 146
Primary # Input Channel 1 Active Event Code
11
147 - 148
Primary # Input Channel 2 Active Event Code
12
149 - 150
Primary # Input Channel 3 Active Event Code
13
151 - 152
Primary # Input Channel 4 Active Event Code
14
153 - 154
Primary # Input Channel 1 Fault Event Code
F1
155 - 156
Primary # Input Channel 2 Fault Event Code
F2
157 - 158
Primary # Input Channel 3 Fault Event Code
F3
159 - 160
Primary # Input Channel 4 Fault Event Code
F4
161 - 162
Primary # AC Fault Event Code
92
163 - 164
Primary # Earth Fault Event Code
61
165 - 166
Primary # Low Battery Fault Event Code
62
167 - 168
Primary # No Battery Fault Event Code
63
169 - 170
Primary # Phone Line 1 Voltage Fault Event Code
64
171 - 172
Primary # Phone Line 2 Voltage Fault Event Code
65
173 - 174
Primary # NAC Fault Event Code
66
175 - 176
Primary # Phone Number 1 Communication Fault Event Code
6A
177 - 178
Primary # Phone Number 2 Communication Fault Event Code
6B
179 - 180
Primary # System Off Normal Fault Event Code
6F
181 - 182
Primary # Input Channel 1 Active Restore Code
E1
183 - 184
Primary # Input Channel 2 Active Restore Code
E2
185 - 186
Primary # Input Channel 3 Active Restore Code
E3
187 - 188
Primary # Input Channel 4 Active Restore Code
E4
189 - 190
Primary # Input Channel 1 Fault Restore Code
D1
191 - 192
Primary # Input Channel 2 Fault Restore Code
D2
193 - 194
Primary # Input Channel 3 Fault Restore Code
D3
195 - 196
Primary # Input Channel 4 Fault Restore Code
D4
197 - 198
Primary # AC Voltage Fault Restore Code
93
199 - 200
Primary # Earth Fault Restore Code
A1
201 - 202
Primary # Low Battery Fault Restore Code
A2
203 - 204
Primary # No Battery Fault Restore Code
A3
205 - 206
Primary # Phone Line 1 Voltage Fault Restore Code
A4
207 - 208
Primary # Phone Line 2 Voltage Fault Restore Code
A5
209 - 210
Primary # NAC Fault Restore Code
A6
211 - 212
Primary # Phone Number 1 Communication Fault Restore Code
AA
213 - 214
Primary # Phone Number 2 Communication Fault Restore Code
AB
215 - 216
Primary # System Off Normal Restore Code
AF
217 - 218
Primary # System Test Message
99
219 - 220
Primary # System Abnormal Test Message
91
221 - 222
Primary # Upload/Download Request Code
71
223 - 224
Primary # Upload Successful Code
72
225 - 226
Primary # Download Successful Code
73
227 - 228
Primary # Upload/Download Failed Code
74
Summary of Contents for Fire-Watch 411UDAC
Page 18: ...Mounting 18 Document 51073 Rev A 1 19 99 P N 51073 A FIGURE 2 3 411UDAC Backbox 411ACABB CDR ...
Page 80: ...80 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 82: ...82 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 83: ...Document 51073 Rev A 1 19 99 P N 51073 A 83 Notes ...