Document #51073 Rev. A 1/19/99 P/N 51073:A
23
Input Channels
FIGURE 2-7:
Notifier AFP-200 Connection to 411UDAC
411UDAC
411UDAC Relay 2 Output (DACT Trouble)
Note: The MMX-2 monitor module input,
which is being used to monitor the
411UDAC Relay Output programmed for
DACT Trouble (requires optional 411RK
Relay Kit), must be programmed as
'DACT Trouble' at the Notifier AFP-200.
The 411UDAC must be programmed as a
Slave Communicator (programming
address 64 set to ‘2’)
Notifier AFP-200
Channel 2/Zone 2
Channel 1/Zone 1
Channel 3/Zone 3
2.2K EOL Channel 4
2.2K EOL
4.7K EOL
MMX-2 Monitor Circuit Input
SLC Loop
UL listed
2.2K EOL
P/N 27070
AFP-200
Trouble
Relay
AFP-200
Alarm Relay
AFP-200
Supervisory Relay
Program the 411UDAC as follows:
Channel 1 - Normally Open Contact Device (alarm)
Channel 2 - Host Panel Trouble
Channel 3 - Supervisory
A
F
P
2411A
.CDR