Document #51073 Rev. A 1/19/99 P/N 51073:A
77
Ademco Contact ID Format Event Code Description
EVENT
MESSAGE
Sounder/Relay Disables - 520
520 Sounder/Relay disable
DISABLE - Sounder/Relay - #
521 Bell 1 disable
DISABLE - Bell/Siren - #1
522 Bell 2 disable
DISABLE - Bell/Siren - #2
523 Alarm relay disable
DISABLE - Alarm Relay
524 Trouble relay disable
DISABLE - Trouble Relay
525 Reversing relay disable
DISABLE - Reversing Relay
526 Bell 3 disable
DISABLE - Bell/Siren - #3
527 Bell 4 disable
DISABLE - Bell/Siren - #4
System Peripheral Disables - 530 and 540
Communication Disables - 550 and 560
551 Dialer disabled
DISABLE - Dialer Disable
552 Radio transmitter disabled
DISABLE - Radio Disable
Bypasses - 570
570 Zone bypass
BYPASS - Zone Bypass - #
571 Fire bypass
BYPASS - Fire Bypass - #
572 24-Hour zone bypass
BYPASS - 24-Hour Bypass - #
573 Burglar bypass
BYPASS - Burg. Bypass - #
574 Group bypass
BYPASS - Group Bypass - #
Test Misc. - 600
601 Manual trigger test
TEST - Manually Triggered
Restore not applicable
602 Periodic test report
TEST - Periodic
Restore not applicable
603 Periodic RF transmission
TEST - Periodic Radio
Restore not applicable
604 Fire test
TEST - Fire Test
Restore not used
605 Status report to follow
STATUS - Status Follows
Restore not applicable
606 Listen-in to follow
LISTEN - Listen-in Active
Restore not applicable
607 Walk test mode
TEST - Walk Test Mode
608 System abnormal test
TEST - System Abnormal Test
Summary of Contents for Fire-Watch 411UDAC
Page 18: ...Mounting 18 Document 51073 Rev A 1 19 99 P N 51073 A FIGURE 2 3 411UDAC Backbox 411ACABB CDR ...
Page 80: ...80 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 82: ...82 Document 51073 Rev A 1 19 99 P N 51073 A Notes ...
Page 83: ...Document 51073 Rev A 1 19 99 P N 51073 A 83 Notes ...