Translation of the original instructions with assembly instructions AF 172 G2, Filtration Group GmbH, 09.12.17, Mat. No. 70355433, Version 05
8
Transport and storage
Transport
•
Always transport horizontally in the original packaging
•
Avoid vibrations
Storage
•
Always store horizontally in the original packaging
•
Always store in a dry, frost-free room
Seaworthy packaging is specified in the
contract documentation as an option.
9
Assembly instructions
DANGER!
Explosion hazard!
Risk of injury to persons or damage to
property.
•
This FG automatic filter is only allowed to
be installed and operated in the category
specified in the contract documentation
(offer/order confirmation).
•
If no category is specified: Do not operate
the FG automatic filter in a hazardous
area!
•
The owner is responsible for zoning.
•
The owner of the plant is solely
responsible for implementing the
appropriate explosion protection
measures!
•
If in doubt, please consult the responsible
authorities.
DANGER!
Explosion hazard!
Risk of injury to persons or damage to
property.
•
The system is only allowed to be installed,
accepted and tested by a suitably qualified
person (99/98/EC).
WARNING!
If the system is installed by unauthorised persons
Risk of injury
All warranty claims are rendered invalid
•
The system must be installed by a suitably trained
person!
9.1
Installation
DANGER!
Explosion hazard!
Risk of injury to persons or damage to
property.
•
Check the conductivity between all
components!
•
Note the maximum permissible resistance:
R < 10
Ω
.
•
Make sure that earthing is provided by the
customer.
It must be possible to remove the filter insert
in order to carry out maintenance work.
•
Prepare a suitable seat on which to mount the filter (e.g.
supports, see data sheet).
•
Be sure to allow the required clearance for dismantling
and discharging (see data sheet).
•
Lift up the automatic filter by the eyebolts using suitable
hoisting gear and remove it from the packaging.
DANGER!
If the filter topples over
Risk of injury to persons or damage to
property.
•
Secure the filter seat firmly in position.
•
Screw the automatic filter to the prepared seat.
•
Remove the caps from the connections.
•
Connect the pipes.
Pressure relief
•
Design measures must be incorporated to prevent
inadmissible excess pressure on the dirty side.
•
Install a pressure relief device if necessary.
9.2
Installing the pipes and selecting the pump
•
Check the pump characteristic.
•
Make sure that the pump suction opening is positioned
well below the liquid level.
•
Ensure a minimum inlet pressure of 1.0 bar.
9.3
Backflushing
The maximum permissible static pressure for the AF 112 G2
is a pressure rating of PN 16.
The normal operating pressure for backflush filters with
internal pressure cleaning is between 1 and 4 bar. Suitable
devices, such as throttles, pressure reducing valves or
locks, must be installed to ensure reliable operation at
higher pressures. At high operating pressures the backflush
volume increases.