Chapter 8: Diagnostic and Repair Procedures
8-7
Error Number 27
Containers are passing the inspection station, but the encoder is
not sending pulses: at least 5 consecutive inspection triggers
occurred without sensor transition.
To correct this error:
•
Check the voltage at P6-2. The signal voltage should be
between 0-12 volts.
•
Check TB4-2 and LED 3 with dip switch S2-7 open.
Error Number 33
This error occurs when the number of consecutively rejected
smashed containers exceeds the limit set in the Consecutive Down
Can Reject Alarm function.
Error Number 34
Two or more consecutive inspection triggers have occurred with
no Down Can sensor transition.
Check LED 5 on the Control Card (ON indicates high-level). Also
check the signal on TB1-14. Blocking the sensor should give 17 - 22
volts on TB1-14. When the sensor is not blocked, the voltage
should be less than 1 volt. If the voltage is not in this range, replace
the sensor.
Error Number 46
The number of containers in the Consecutive External Reject
Alarm was exceeded.
This is a high priority error condition and will cause the Warning
Beacon to flash if Beacon Status is set to HIGH PRIORITY ONLY.
Error Number 47
The Encoder Resolution is to low. Replace the encoder with an
encoder that has higher resolution.