PAGE / 14
Doc. P/N 8.8128.00.3
Rev. 3 / July, 2020
NOTE: Torque values for Atlas sizes 14” and larger were determined by considering ASME PCC-1 and ASME Section VIII
Devision 1 Mandatory Appendix II guidelines. Torque values in Appendix A are based on a nut factor K = 0.2.
Adjustments to the torque should be considered if the installation utilizes bolting/lubrication with a nut factor other
than K = 0.2. The following expression may be used for correction:
Equation 1: T
2
= (T
1
/K
1
) * K
2
where T
1
and K
1
are the Fike default torque and nut factor values.