QuickServer Start-up Guide

 

Page 17 of 30

 

There are 3 DIP switches available on the QuickServer. 

A – Address DIP Switch 

B – Baud rate DIP Switch 

S – Secondary DIP Switch 

The following sections describe how to set up the DIP switches in the configuration file.   To configure the use of 
the DIP switches, buffers need to be declared in the “Data Arrays” section which will enable them. 

To configure DIP switches A0-A7 to adjust the Device Id, BACnet MAC address, or both, the dynamic parameters 
field needs to be added to the configuration file. 

To configure DIP switches B0-B3 to adjust the baud rate, the dynamic parameters field needs to be added to the 
configuration file. 

Dynamic_Parameters 
Function 

, Data_Array_Name  , Data_Array_Offset  , Descriptor_Name 

Baud_Rate  , DA_BAUD 

, 0 

, P1 

Appendix A.1.2. Configure DIP switches B0 – B3 

Dynamic_Parameters 

 

, Descriptor_Name 
, Node_Name_A 
, Title_A 

 

, Low_Limit 
, 1 
, 1 

 

, High_Limit 
, 4194303 
, 254 

Function 
Change_Node_ID 
Change_System_MAC_Addr 

, Data_Array_Name 
, DA_A 
, DA_A 

, Data_Array_Offset 
, 0 
, 0 

Appendix A.1.1. Configure DIP switches A0-A7 

Data_Arrays 
Data_Array_Name     , Data_Format         , Data_Array_Length       , Data_Array_Function     , Scan_Interval 
DA_A                             , UINT16                   , 1                                        , Dip_Switches_A              , 2s 
DA_B                             , BAUD                      , 1                                        , Dip_Switches_B              , 2s 
DA_S                             , UINT16                   , 1                                        , Dip_Switches_S               , 2s 

Appendix A.1. QuickServer DIP Switch configuration 

Appendix A Useful Features

 

 
 

ProSoft Technology, Inc. is a provider of FieldServer QuickServers. For Technical Support call 

+1 661.716.5100

 

 

 

Summary of Contents for PS-QS-1010-0780

Page 1: ...QuickServer Start up Guide PS QS 1010 1011 PS QS 1510 1511 APPLICABILITY EFFECTIVITY Effective for all systems manufactured after August 2012 Kernel Version 6 04 Document Revision 11 ...

Page 2: ...3 Use the FieldServer Web GUI to Connect to the QuickServer 14 5 3 1 Using the Discovery Tool to Allocate the IP address 14 5 4 Set IP Address of the QuickServer 15 6 Configuring the QuickServer 16 6 1 6 2 6 3 6 4 Retrieve the Sample Configuration File 16 Change the Configuration File to Meet the Application 16 Load the Updated Configuration file 17 Test and Commission the QuickServer 18 Appendix ...

Page 3: ...ED s 25 Appendix D 1 1 LED Functions 25 Appendix D 2 PS QS 1011 1510 XXXX LED s 26 Appendix D 3 QuickServer FS QS 101X DCC 27 Appendix D 4 Compliance with UL Regulations 27 Appendix D 5 Address DIP Switch Settings 28 Appendix D 6 Baud DIP Switch Settings 30 ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 4: ...ment for details The BTL Mark on the ProtoNode RER is a symbol that indicates to a consumer that a product has passed a series of rigorous tests conducted by an independent laboratory which verifies that the product correctly implements the BACnet features claimed in the listing The mark is a symbol of a high quality BACnet product For more information about the BACnet Testing Laboratory go to htt...

Page 5: ...mount These can be snapped off if not required DIN Rail Mounting Bracket included in the Accessory Kit or ordered separately Din Rail Tab R1 Port R2 Port 3 1 1 Dimension Drawing PS QS 1010 1510 XXXX 3 1 Dimensions 3 MOUNTING ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 6: ...erver Start up Guide Page 6 of 30 LonWorks Port R2 Port 3 1 2 Dimension Drawing PS QS 1011 1511 XXXX ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 7: ...z Power Rating 2 5 Watts Current draw 12V 150 mA Input Voltage 9 30VDC or 12 24VAC Input Power Frequency 50 60 Hz Power Rating 2 5 Watts Current draw 12V 279 mA Approvals TUV approved to UL 916 Standard RoHS Compliant FCC Part 15 Compliant DNP compliant OPC self tested to conformance CE Mark BTL Mark TUV approved to UL 916 Standard RoHS Compliant FCC Part 15 Compliant DNP compliant OPC self tested...

Page 8: ... radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his expense Modifications not expressly approved by FieldServer could void the u...

Page 9: ...ion the QuickServer LonWorks port insert a small screwdriver in the commissioning hole on the face of the QuickServer s enclosure to access the Service Pin See the instructions on the QuickServer as to which way to toggle the screwdriver during commissioning 4 2 QuickServer LonWorks PS QS 1011 1511 XXXX GND 4 1 2 RS 485 Connection R1 Port Only on Non LonWorks QuickServers B A SG 4 1 1 RS 485 Conne...

Page 10: ...n example The S0 S3 DIP switch selection is read directly into a Data Array This Data_Array value can be used for customized configuration selection operations such as 4 4 3 DIP Switches S0 S3 ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 11: ...software Connect an Ethernet cable between the PC and QuickServer or connect the QuickServer and the PC to the Hub switch using a straight cat5 cable The Default IP Address of the QuickServer is 192 168 2 X Subnet Mask is 255 255 255 0 If the PC and the QuickServer are on different IP Networks assign a Static IP Address to the PC on the 192 168 2 X network 5 2 Connect the PC to the QuickServer ove...

Page 12: ...ort utility utility php Use the Discovery tool to find the QuickServer and launch the Web GUI from the Discovery tool 5 3 1 Using the Discovery Tool to Allocate the IP address 5 3 Use the FieldServer Web GUI to Connect to the QuickServer ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 13: ...eldServer is connected to a router the IP Gateway of the FieldServer should be set to the IP address of the router that it is connected to Click Update IP Settings then click on the System Restart to restart the Gateway and activate the new IP address Note that the QuickServer will need to be pointed to the new IP address on the Web Browser before the GUI will be accessible again Unplug Ethernet c...

Page 14: ...le of the drivers ordered In the main menu of the PS GUI screen go to Setup File Transfer Retrieve Click on config csv and open or save the file Refer to the FieldServer Configuration Manual in conjunction with the Driver supplements for information on configuring the QuickServer See www prosoft technology com Support for specific details details 6 2 Change the Configuration File to Meet the Appli...

Page 15: ...nce download is complete click the System Restart Button or simply cycle power to the QuickServer to put the new file into operation Note that it is possible to do multiple downloads to the QuickServer before resetting it 6 3 Load the Updated Configuration file ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 16: ... GUI click on View Connections to see the number of messages on each For troubleshooting assistance refer to Appendix B or contact ProSoft technology Technical Support at www prosoft technology com Support 6 4 Test and Commission the QuickServer ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 ...

Page 17: ...eters field needs to be added to the configuration file Dynamic_Parameters Function Data_Array_Name Data_Array_Offset Descriptor_Name Baud_Rate DA_BAUD 0 P1 Appendix A 1 2 Configure DIP switches B0 B3 Dynamic_Parameters Descriptor_Name Node_Name_A Title_A Low_Limit 1 1 High_Limit 4194303 254 Function Change_Node_ID Change_System_MAC_Addr Data_Array_Name DA_A DA_A Data_Array_Offset 0 0 Appendix A 1...

Page 18: ...thod load_csv DA_LOAD_CSV 2 csvfilenames On_Change Config_Table Config_Table_Name Table_String Table_Index_Value csvfilenames profile1 csv 1 Profile config 1 csvfilenames profile2 csv 2 Profile config 2 csvfilenames profile3 csv 3 Profile config 3 csvfilenames profile4 csv 4 Profile config 4 Data_Arrays Data_Array_Name Data_Format Data_Array_Length Data_Array_Function Scan_Interval DA_LOAD_CSV UIN...

Page 19: ...mation Before contacting Technical support to report an issue go to Start Programs FieldServer utilities Tools and run the FST_Diag program Take a log See ENote0058 in the folder called Library on the USB Flash Drive Send this log together with a detailed description of the problem to support fieldserver com for evaluation Note that while all necessary documentation is shipped with the FieldServer...

Page 20: ...anty also will not apply to interconnecting cables or wires consumables or to any damage resulting from battery leakage In all cases FieldServer Technology s responsibility and liability under this warranty shall be limited to the cost of the equipment The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provision and compliance with such instructi...

Page 21: ...on the FieldServer If this occurs immediately report the related system error shown in the error screen of the FS GUI interface to FieldServer Technologies for evaluation RX On normal operation of PS QS 1010 the RX LED will flash when a message is received on the field port of the QuickServer TX On normal operation of PS QS 1010 the TX LED will flash when a message is sent on the field port of the...

Page 22: ...ieldServer Technologies for evaluation COMM ERR LED2 The COMM ERR LED will flash once on power up and flash once 15 seconds after power up A error go to the error screen of the RUI interface Config ERR LED3 The Config ERR LED will flash once on power up and flash once 15 seconds after power up A Error Screen in the Remote User Interface for a description of the configuration error Node Offline LED...

Page 23: ...Cnet MS TP 0367 Modbus RTU BACnet IP 0104 Modbus RTU JCI Metasys N2 0038 Modbus RTU LonWorks 0085 Modbus TCP BACnet IP 0237 Modbus TCP LonWorks 0154 Modbus TCP BACnet MS TP 0419 Modbus TCP JCI Metasys N2 0117 SNMP BACnet IP 0333 SNMP LonWorks 0337 SNMP JCI Metasys N2 0150 Add BACnet MS TP LonWorks 0345 Appendix D 3 QuickServer PS QS 101X DCC Light Description LON TX LED On normal operation of PS Q...

Page 24: ...2 Off Off On On Off Off Off Off 13 On Off On On Off Off Off Off 14 Off On On On Off Off Off Off 15 On On On On Off Off Off Off 16 Off Off Off Off On Off Off Off 17 On Off Off Off On Off Off Off 18 Off On Off Off On Off Off Off 19 On On Off Off On Off Off Off 20 Off Off On Off On Off Off Off 21 On Off On Off On Off Off Off 22 Off On On Off On Off Off Off 23 On On On Off On Off Off Off 24 Off Off Of...

Page 25: ...Off 58 Off On Off On On On Off Off 59 On On Off On On On Off Off 60 Off Off On On On On Off Off 61 On Off On On On On Off Off 62 Off On On On On On Off Off 63 On On On On On On Off Off 64 Off Off Off Off Off Off On Off 65 On Off Off Off Off Off On Off 66 Off On Off Off Off Off On Off 67 On On Off Off Off Off On Off 68 Off Off On Off Off Off On Off 69 On Off On Off Off Off On Off 70 Off On On Off O...

Page 26: ...On Off 103 On On On Off Off On On Off 104 Off Off Off On Off On On Off 105 On Off Off On Off On On Off 106 Off On Off On Off On On Off 107 On On Off On Off On On Off 108 Off Off On On Off On On Off 109 On Off On On Off On On Off 110 Off On On On Off On On Off 111 On On On On Off On On Off 112 Off Off Off Off On On On Off 113 On Off Off Off On On On Off 114 Off On Off Off On On On Off 115 On On Off...

Page 27: ...On Off Off On 148 Off Off On Off On Off Off On 149 On Off On Off On Off Off On 150 Off On On Off On Off Off On 151 On On On Off On Off Off On 152 Off Off Off On On Off Off On 153 On Off Off On On Off Off On 154 Off On Off On On Off Off On 155 On On Off On On Off Off On 156 Off Off On On On Off Off On 157 On Off On On On Off Off On 158 Off On On On On Off Off On 159 On On On On On Off Off On 160 Of...

Page 28: ...93 On Off Off Off Off Off On On 194 Off On Off Off Off Off On On 195 On On Off Off Off Off On On 196 Off Off On Off Off Off On On 197 On Off On Off Off Off On On 198 Off On On Off Off Off On On 199 On On On Off Off Off On On 200 Off Off Off On Off Off On On 201 On Off Off On Off Off On On 202 Off On Off On Off Off On On 203 On On Off On Off Off On On 204 Off Off On On Off Off On On 205 On Off On O...

Page 29: ...n 234 Off On Off On Off On On On 235 On On Off On Off On On On 236 Off Off On On Off On On On 237 On Off On On Off On On On 238 Off On On On Off On On On 239 On On On On Off On On On 240 Off Off Off Off On On On On 241 On Off Off Off On On On On 242 Off On Off Off On On On On 243 On On Off Off On On On On 244 Off Off On Off On On On On 245 On Off On Off On On On On 246 Off On On Off On On On On 24...

Page 30: ...200 Off Off On Off 2400 On Off On Off 4800 Off On On Off 9600 On On On Off 19200 Off Off Off On 20833 On Off Off On 28800 Off On Off On 38400 On On Off On 57600 Off Off On On 76800 On Off On On 115200 Off On On On Appendix D 6 Baud DIP Switch Settings ProSoft Technology Inc is a provider of FieldServer QuickServers For Technical Support call 1 661 716 5100 Page 30 of 30 ...

Reviews: