Parameter

 

Minimum

 

Typical

 

Maximum

 

Units

 

Notes & Conditions

 

Output voltage

 

12

 

 

48

 

VDC

 

See Model & Ratings table

 

Total regulation

 

 

±10% AC line change at nominal load and ±40% 
load change at 60% load nominal line. 

 

Output 1: ±5% 12

-

19V models. ±3% 24V model.                            

±2% 30

-

48V models.                                                  

Output 2: ±5% all models

 

Minimum load

 

0

 

 

 

%

 

 

Ripple & Noise 

 

Output 1: 12V model 120mVp

-

p. 15V model 150mVp

-

p.             

19V model 190mVp

-

p. 24V model 240mVp

-

p.               

30

-

48V models 300mVp

-

p.                                                  

Output 2: all models 50mVp

-

p

 

mV(Vp

-

p)

 

All models measured with 0.1uF and 0.47uF      
capacitor and 20 MHz bandwidth.

 

Hold up time

 

 

16

 

 

ms

 

 

Overload protection

 

105

 

 

130

 

%

 

Trip and restart. Automatic recovery

 

Short circuit protection

 

 

 

 

 

Trip and restart. Automatic recovery

 

Overvoltage protection

 

112

 

 

132

 

%

 

Trip and restart. Automatic recovery

 

Output

 

Parameter

 

Minimum

 

Typical

 

Maximum

 

Units

 

Notes & Conditions

 

Efficiency

 

90

 

 

92

 

%

 

 

Isolation: Input to Output

 

4000

 

 

 

VAC

 

2 x MOPP (BF rated)

 

               Input to Ground

 

1500

 

 

 

VAC

 

 

Isolation resistance

 

 

50

 

 

M

 

 

Power density

 

 

11.4

 

 

W/In

3

 

 

MTBF

 

200

 

 

 

KHrs

 

As per MIL

-

HDBK

-

217F, 25°C GB

 

Weight

 

 

350

 

 

g

 

 

General

 

Parameter

 

Minimum

 

Typical

 

Maximum

 

Units

 

Notes & Conditions

 

Operating temperature

 

-

40

 

 

70

 

°C

 

Derate linearly from 100% power at 50°C  to 50% 
power at 70°C 

 

Storage temperature

 

-

40

 

 

85

 

°C

 

 

Cooling

 

 

 

 

 

Convection cooled

 

Temperature coefficient

 

 

 

±0.04

 

%/

ᵒC

 

 

Humidity

 

0

 

 

95

 

% RH

 

Non condensing

 

Operating altitude

 

 

 

3000

 

m

 

 

Vibration

 

 

 

5

 

g

 

10

-

500hz, 10min/cycle in each axis x,y and z

 

Environmental

 

Parameter

 

Minimum

 

Typical

 

Maximum

 

Units

 

Notes & Conditions

 

Input voltage

 

90

 

 

264

 

VAC

 

 

Input frequency

 

47

 

 

63

 

Hz

 

 

Power factor

 

0.9

 

 

 

 

EN61000

-

3

-

2 class A compliant

 

Input current (rms) 

 

 

 

3

 

A  

 

Low line. At 100VAC

 

 

 

1.5

 

High line. At 240VAC

 

Inrush current 

 

 

 

75

 

 

100VAC cold start at 25°C

 

 

 

150

 

240VAC cold start at 25°C

 

No load input power

 

 

 

0.3

 

W

 

 

Earth leakage current

 

 

 

0.3

 

mA

 

240VAC 60Hz

 

Input

 

Summary of Contents for RHM250P Series

Page 1: ...1 2006 A1 2013 ES60601 1 2005 R2012 CSA C22 2 No 60601 1 14 EN60601 1 2006 A1 2013 Key specifications RHM250P Series Notes Power dense 250W in 3 x 5 Remote on off and 5V stand by Latest medical approvals IEC 60601 1 3 1 and IEC 60601 1 2 4th Ed Earth leakage 300uA BF rated EN55011 Level B conducted radiated 40 to 70 C Operation 5 Year warranty Dimensions 3 x 5 x 1 46 76 2 x 127 x 37mm 250 Watts Th...

Page 2: ...inimum Typical Maximum Units Notes Conditions Efficiency 90 92 Isolation Input to Output 4000 VAC 2 x MOPP BF rated Input to Ground 1500 VAC Isolation resistance 50 MΩ Power density 11 4 W In3 MTBF 200 KHrs As per MIL HDBK 217F 25 C GB Weight 350 g General Parameter Minimum Typical Maximum Units Notes Conditions Operating temperature 40 70 C Derate linearly from 100 power at 50 C to 50 power at 70...

Page 3: ...d 240V 50Hz Surges EN61000 4 5 Installation Class 3 A 2KV 100V and 240V 50Hz 1KV L N Conducted EN61000 4 6 3 6Vrms A 80 AM 1KHz Magnetic Fields EN61000 4 8 30A m A 50 60Hz 1 min Voltage Dips EN61000 4 11 100 for 0 5 cycles 60 5 cycles 30 for 25 30 cycles interrupt 250 300 cycles and 1 sec performance criteria A A B EMC Immunity Safety standard Notes Conditions UL ES 60601 1 2005 R2012 CSA C22 2 No...

Page 4: ...ith JST VHR 5N P4 Pin Connections Pin Function 1 COM 2 Output 2 3 ON OFF 1 All dimensions shown in millimetres inches 4 Standby power output connector mates with JST housing XHP 3 and JST SXH series crimp terminals Input Pin Connections P1 Pin Function 1 Ground 2 Neutral 3 Line Output Pin Connections Pin Function P2 Vout P3 Return 3 DC output M3 screws torque to 3 lb in 30 CNm max ...

Page 5: ...mon component to avoid placing wiring near is the PFC inductor in power factor corrected power supplies 3 Apply additional filtering before the PSU input ensure consideration of which frequencies there are issues with before selecting a filter 4 When using an open frame PSU mount the supply on a metal plate and connect EMI mounting points 5 In multi circuit systems decouple the circuits locally 6 ...

Reviews: