RHM250P
Series
Parameter
Minimum
Typical
Maximum
Units
Notes & Conditions
Output voltage
12
48
VDC
See Model & Ratings table
Total regulation
%
±10% AC line change at nominal load and ±40%
load change at 60% load nominal line.
Output 1: ±5% 12
-
19V models. ±3% 24V model.
±2% 30
-
48V models.
Output 2: ±5% all models
Minimum load
0
%
Ripple & Noise
Output 1: 12V model 120mVp
-
p. 15V model 150mVp
-
p.
19V model 190mVp
-
p. 24V model 240mVp
-
p.
30
-
48V models 300mVp
-
p.
Output 2: all models 50mVp
-
p
mV(Vp
-
p)
All models measured with 0.1uF and 0.47uF
capacitor and 20 MHz bandwidth.
Hold up time
16
ms
Overload protection
105
130
%
Trip and restart. Automatic recovery
Short circuit protection
Trip and restart. Automatic recovery
Overvoltage protection
112
132
%
Trip and restart. Automatic recovery
Output
Parameter
Minimum
Typical
Maximum
Units
Notes & Conditions
Efficiency
90
92
%
Isolation: Input to Output
4000
VAC
2 x MOPP (BF rated)
Input to Ground
1500
VAC
Isolation resistance
50
M
Ω
Power density
11.4
W/In
3
MTBF
200
KHrs
As per MIL
-
HDBK
-
217F, 25°C GB
Weight
350
g
General
Parameter
Minimum
Typical
Maximum
Units
Notes & Conditions
Operating temperature
-
40
70
°C
Derate linearly from 100% power at 50°C to 50%
power at 70°C
Storage temperature
-
40
85
°C
Cooling
Convection cooled
Temperature coefficient
±0.04
%/
ᵒC
Humidity
0
95
% RH
Non condensing
Operating altitude
3000
m
Vibration
5
g
10
-
500hz, 10min/cycle in each axis x,y and z
Environmental
Parameter
Minimum
Typical
Maximum
Units
Notes & Conditions
Input voltage
90
264
VAC
Input frequency
47
63
Hz
Power factor
0.9
EN61000
-
3
-
2 class A compliant
Input current (rms)
3
A
Low line. At 100VAC
1.5
High line. At 240VAC
Inrush current
75
A
100VAC cold start at 25°C
150
240VAC cold start at 25°C
No load input power
0.3
W
Earth leakage current
0.3
mA
240VAC 60Hz
Input