SFAM
Festo – SFAM – 2017-09c English
25
For teaching the switching variables:
2. Generate a flow rate (Flow1)
3. First press the A pushbutton and then also the Edit button.
[Out A] and bar graph flash and the measurement value is assumed as the first teach point or [Lock]
flashes if the security lock is active.
Only with active security blocking [Lock] (points 4 and 5):
4. Press the A/B pushbuttons until the chosen security code is set.
5. Press the Edit button.
[Out A] and the bar graph flash and the measurement value is assumed as the first teach point.
6. Generate a second flow rate (Flow 2).
7. First press the A pushbutton and then also the Edit button.
The second teach point is assumed and the switching point (SP) or switching points (SP.Lo and
SP.Hi) become valid.
The SFAM is in RUN mode.
5.7
RECORDER mode
In the RECORDER mode, a manual air consumption measurement can be performed.
Fig. 8
RECORDER mode
1. Press the A and B pushbuttons simultaneously.
The SFAM is in RECORDER mode
The status of the measurement [Run] or [Stop] is displayed.
2. The measurement can be started or stopped by pressing the A pushbutton.
3. By pressing the B pushbutton, you can reset the measurement to zero.
4. Press the A and B pushbuttons simultaneously.
The SFAM is in RUN mode.
Note
If the RECORDER mode is exited during an ongoing measurement [Run], the
measurement will continue in the background.