SFAM
Festo – SFAM – 2017-09c English
23
Set analogue filter [AnA.F]
7. Select the value for the filter time constants (15 ms, 30 ms, 60 ms, 125 ms, 250 ms, 500 ms or
999 ms) with the A/B pushbuttons.
8. Press the EDIT button to confirm the set value.
[dIG.F] and the currently selected value flash. The digital filter can be set.
Set smoothing for the digital filter [diGF]
Note
A high filter time constant and high smoothing can result in a switching time of several
seconds.
9. Select the value for cushioning (d1 to d6 or d.OFF) with the A/B pushbuttons.
10.Press the EDIT button to confirm the set value.
[ConS] is displayed and the currently selected value flashes.
The unit for the air consumption (m
3
, scf or l) can be set.
Set the physical unit for the air consumption [ConS]
11.Select the desired setting (m
3
, scf or l) with the A/B pushbuttons.
12.Press the Edit button to confirm the selection.
The currently set value [PnP] or [nPn] for the switching element output flashes. The switching
element output can be set.
Set switching output characteristic [PnP] or [nPn]
13.Select the desired setting (PNP or NPN) with the A/B pushbuttons.
14.Press the Edit button to confirm the selection.
[Lock] flashes. The current setting is then displayed.
Setting the security code
Note
Keep the security code where it can be found. If the security code has been forgotten see, the
è
Chapter 6 Resetting SFAM to factory setting.
15.Use the A/B pushbuttons to select between an inactive security code (OFF) or a maximum 4-digit
security code.
16.Press the Edit button to confirm the selection.
The SFAM is in RUN mode.