8.2.2
Error code
Note
There are, of course, also errors in which the diagnostics no longer work. See the
chapter on fault clearance to eliminate them.
Dia
gnostic
level
Error
code
Description
Remedy
Er34
Evacuation time exceeded in 2 of 5
cycles
Check for leakage
Er36
Air supply time exceeded in 2 of 5
cycles
Check for leakage
Lengthen air supply time
Check throttle setting
Er33
Solenoid valve does not switch or does
not switch correctly.
Plunger does not move; current
through solenoid coil is too low; short
circuit in solenoid coil
Press mechanical manual override
several times.
Check supply voltage.
If there is no improvement, the device
is defective.
Send device to Festo.
Er35
The set threshold for evacuation time
is exceeded by a factor of two in 2 of 5
cycles.
Check for leakage
Er37
The set threshold for air supply time is
exceeded by a factor of two in 2 of 5
cycles.
Check for leakage
Lengthen air supply time
Check throttle setting
Er38
Switching frequency of the air saving
function lies above the limit value of
1 Hz
Check for leakage
Er39
Specified vacuum value is not reached
within 10 s
Check for leakage
Check compressed air supply
Switch-back threshold fallen below
(active air saving function and
threshold value comparator)
Set trigger levels logically
Check settings for Out A
Check compressed air supply
Upper trigger level exceeded or lower
trigger level fallen below (window
comparator)
Set trigger levels logically
Check settings for Out A
Check compressed air supply
Summary of Contents for OVEM
Page 52: ...OVEM 52 Festo OVEM 1407c Deutsch Fig 23 SHOW Modus ...
Page 53: ...OVEM Festo OVEM 1407c Deutsch 53 Fig 24 EDIT Modus ...
Page 54: ...OVEM 54 Festo OVEM 1407c Deutsch Fig 25 TEACH Modus ...
Page 106: ...OVEM 106 Festo OVEM 1407c English Fig 23 SHOW mode ...
Page 107: ...OVEM Festo OVEM 1407c English 107 Fig 24 EDIT mode ...
Page 108: ...OVEM 108 Festo OVEM 1407c English Fig 25 TEACH mode ...