8.2.2

Error code

Note

There are, of course, also errors in which the diagnostics no longer work. See the

chapter on fault clearance to eliminate them.

Dia­

gnostic

level

Error

code

Description

Remedy

1

1)

Er34

Evacuation time exceeded in 2 of 5 

cycles

Check for leakage

Er36

Air supply time exceeded in 2 of 5 

cycles

Check for leakage

Lengthen air supply time

Check throttle setting

2

2)

Er33

Solenoid valve does not switch or does

not switch correctly.

Plunger does not move; current

through solenoid coil is too low; short

circuit in solenoid coil

Press mechanical manual override

several times.

Check supply voltage.

If there is no improvement, the device

is defective.

Send device to Festo.

Er35

The set threshold for evacuation time

is exceeded by a factor of two in 2 of 5 

cycles.

Check for leakage

Er37

The set threshold for air supply time is

exceeded by a factor of two in 2 of 5 

cycles.

Check for leakage

Lengthen air supply time

Check throttle setting

2

2)

Er38

Switching frequency of the air saving

function lies above the limit value of

1 Hz

Check for leakage

2

2)

Er39

3)4)

Specified vacuum value is not reached

within 10 s

Check for leakage

Check compressed air supply

Switch-back threshold fallen below

(active air saving function and

threshold value comparator)

Set trigger levels logically

Check settings for Out A

Check compressed air supply

Upper trigger level exceeded or lower

trigger level fallen below (window

comparator)

Set trigger levels logically

Check settings for Out A

Check compressed air supply

Summary of Contents for OVEM

Page 1: ...de Bedienungs anleitung en Operating instructions 8038302 1407c 8038303 Vakuumsaugdüse Vacuum generator OVEM ...

Page 2: ... dieser Bedienungsanleitung durchgeführt werden Installation and commissioning may only be per formed in accordance with these instructions by technicians with appropriate qualifications Warnung Warning Vorsicht Caution Hinweis Note Umwelt Environment Zubehör Accessories Deutsch Vakuumsaugdüse OVEM 3 English Vacuum generator OVEM 57 ...

Page 3: ...eise Luftsparfunktion LS 12 3 4 Schaltpunkte und Hysterese 14 3 5 Diagnose 14 3 6 Messgrößen 15 4 Voraussetzungen für den Produkteinsatz 16 5 Einbau 18 5 1 Mechanisch 18 5 1 1 Direkte Befestigung 18 5 1 2 Befestigung mit Zubehör 18 5 2 Pneumatisch 20 5 3 Elektrisch 20 6 Inbetriebnahme 22 6 1 Symbolik LCD Display 24 6 1 1 Segmentleisten 26 6 2 SHOW Modus 27 6 2 1 Einstellungen für Out A B anzeigen ...

Page 4: ...tgrößen teachen 36 6 4 2 Luftsparfunktion LS teachen 37 6 4 3 Belüftungs und Evakuierungszeiten teachen 38 6 4 4 Sicherheitscode eingeben 39 6 4 5 Probelauf 39 7 Bedienung und Betrieb 39 7 1 Handhilfsbetätigung 39 7 2 Einstellungen und Werte ändern 40 7 3 Auf Werkseinstellung zurücksetzen 40 8 Wartung und Diagnose 40 8 1 Wartung 40 8 2 Diagnose 41 8 2 1 Diagnosemeldekanal di x setzen 42 8 2 2 Fehl...

Page 5: ...hluss 4 Abluftanschluss Schalldämpfer 5 Vakuumanschluss 6 Filterelement zum Wechseln 7 Gehäuse mit Befestigungsbohrungen 8 Schieber zum Wechseln des Filters 9 Filtergehäuse mit Sichtfenster aJ Drosselschraube zur Einstellung der Intensi tät des Abwurfimpulses aA Bedientasten aB EDIT Knopf aC LCD Display aD Stecker für elektrischen Anschluss M12 Fig 1 Bedienteile und Anschlüsse ...

Page 6: ...uumanzeige Spezialanzeige 5 Symbolleiste für Funktionen è Tab 9 6 EDIT Knopf 7 DOWN Taste B Taste 8 UP Taste A Taste 9 Vakuumanzeige aJ Zustandsanzeige Magnetventile Fig 2 Display Hinweis In der Bedienerführung werden die Bedientasten in Abhängigkeit der Verwendung unterschiedlich benannt Bei der Auswahl der Schaltausgänge A Taste B Taste Bei Auswahl der Menüpunkte und Einstellen von Werten UP Tas...

Page 7: ...T Innengewinde BN GN GO Versorgung Vakuumanschluss mit G Innengewinde Abluft anschluss mit offenem Schalldämpfer B GO Versorgung Vakuumanschluss mit NPT Innengewinde Abluft anschluss mit offenem Schalldämpfer BN GO PL Vorbereitet für Versorgungsleiste Vakuum und Abluftan schluss mit QS Verschraubungen B PL Vorbereitet für Versorgungsleiste Vakuum und Abluftan schluss mit QS Verschraubungen Zoll BN...

Page 8: ...seinstellung ausgeliefert Luftsparfunktion bei CE OE aktiv Schaltverhalten des elektrischen Ausgangs Schwellwert Komparator Schaltelementfunktion des elektrischen Ausgangs NO normally open Schließer weitere Werkseinstellungen è Kapitel 12 1 Seite 49 1 Montieren Sie die Vakuumsaugdüse è Kapitel 5 1 Seite 18 2 Schließen Sie die Vakuumsaugdüse pneumatisch an è Kapitel 5 2 Seite 20 3 Schließen Sie die...

Page 9: ...g des Vakuums ist die Grundlage für die Luftsparfunktion der Vakuumsaugdüse è Kapitel 3 3 Seite 12 Werksseitig ist die Luftsparfunktion der Vakuumsaugdüse CE CO aktiviert Die Luftsparfunktion kann ausgeschaltet werden è Kapitel 6 3 4 Seite 34 Die Druckluftversorgung wird durch ein integriertes Magnetventil gesteuert Das Magnetventil ist in zwei verschiedenen Schaltfunktionen NC NO lieferbar Das Va...

Page 10: ...n TEACH Modus gewechselt werden Der TEACH Modus dient zum schnellen Konfigurieren der Daten der Vakuumsaugdüse Die Daten können bei Bedarf über den EDIT Modus geändert werden è Kapitel 6 4 Seite 35 3 2 Schaltausgänge und Schalteingang Das Vakuum wird mit Hilfe eines piezoresistiven Sensorelementes mit nachgeschalteter elektronischer Auswerteeinheit gemessen Das Messergebnis von In A1 wird numerisc...

Page 11: ...uls E tab Dauer Abwurfimpuls Fig 4 Schaltverhalten Schalteingang Code Diagnose Schaltausgang A Schaltausgang B Schalteingang 2P Meldung aus Schaltausgang positiv schaltend Drucksensor Ausgang A Schaltausgang positiv schaltend Drucksensor Aus gang B Schalteingang positiv schaltend Meldung ein Schaltausgang positiv schaltend Diagnosemeldung PI Analogausgang 4 20 mA Vakuum PU Analogausgang 0 10 V Vak...

Page 12: ...iert Die Luftsparfunktion kann ausgeschaltet werden è Kapitel 6 3 4 Seite 34 Ist der gewünschte Schwellwert 1 für das Vakuum erreicht wird die Vakuumerzeugung selbstständig ausgeschaltet Ein Rückschlagventil verhindert den Abbau des Vakuums Durch Leckage z B rauhe Werkstückoberflächen wird das Vakuum trotzdem langsam abgebaut Bei Unterschreitung des einge stellten Schwellwertes 3 wird die Vakuumer...

Page 13: ...et sobald das Vakuum schlechter ist als der Schwellwert 3 Die Schwellwerte sind wie folgt definiert Schwellwert Saugen abschalten 1 Der Schwellwert 1 ist gleich der vom Kunden einstellbaren Einschaltschwelle 2 des Ausgangs Out A è Fig 5 d h der Vakuumerzeuger wird gleichzeitig mit dem Setzen des Ausgangs Out A abgeschaltet Schwellwert Saugen einschalten 3 Der Schwellwert 3 liegt zwischen der Einsc...

Page 14: ...re Systemei genschaften Dazu zählen z B Evakuierungszeiten oder die Funktion der Magnetventile Die Diagnosefunktion ermöglicht dem Bediener das frühzeitige Erkennen von Störungen und das schnelle Auffinden von Fehlern Bei Störungen leuchtet die rote Hintergrundbeleuchtung des Displays Der Anlagenzustand kann über große Entfernungen identifiziert werden Die Diagnosemeldungen werden im Display angez...

Page 15: ...eschaltet wird Zyklus Die Dauer eines Zyklus umfasst den Zeitraum von Beginn der Evakuierung über das Abwerfen bis zum Beginn der erneuten Evakuierung è Fig 6 In Out A 3 4 1 2 2 5 Saugen 1 Zyklus 2 Evakuierungszeit tevac 3 Belüftungszeit tbel 4 Einschaltpunkt Out A 5 Ausschaltpunkt Out A Fig 6 Definition Zyklus Beispiel für Out A Belüftungs und Evakuierungszeiten Die minimale und maximale Belüftun...

Page 16: ...en Sie sicher dass die nachfolgenden Vorgaben stets eingehalten werden Hinweis Das Vakuum wird als Relativdruck gemessen Der angezeigte Druckwert entspricht der tatsächlischen Druckdifferenz zum Umgebungsdruck In Abhängigkeit vom aktuellen absoluten Umgebungsdruck Luftdruck kann der erreichbare angezeigte Druckwert geringer sein als der in den technischen Daten angegebene Wert Vergleichen Sie die ...

Page 17: ...r Class 2 transformer in accordance with UL1310 or UL1585 As an alternative a LV C Limited Voltage Current power source with one of the following properties can be used This device shall be used with a suitable isolating source such that the maximum open circuit vol tage potential available to the product is not more than 24 V DC and the current is limited to a value not exceeding 8 amperes measur...

Page 18: ... Mechanisch 5 1 1 Direkte Befestigung Fig 7 Direkte Befestigung Befestigen Sie die Vakuumsaugdüse mit zwei Schrauben an der vorgesehenen Stelle Größe der Befestigungsschrauben è Tab 5 Anziehdrehmoment max 2 5 Nm Die Verwendung von entsprechenden Unterlegscheiben wird empfohlen oder Befestigen Sie die Vakuumsaugdüse an der Unterseite mit 4 Schrauben M3 Anziehdrehmoment max 0 8 Nm OVEM Größe Befesti...

Page 19: ...ung 3 Sichern Sie mit der Schraube 1 die Vakuumsaugdüse an der Hutschiene Befestigungswinkel Fig 9 Befestigungswinkel Befestigen Sie die Vakuumsaugdüse mit zwei Schrauben an der vorgesehenen Stelle Größe der Befestigungsschrauben è Tab 5 Anziehdrehmoment max 2 5 Nm Die Verwendung von entsprechenden Unterlegscheiben wird empfohlen P Anschlussleiste Die Vakuumsaugdüse kann außerdem auf einer P Ansch...

Page 20: ...inimale Schlauch Innendurchmesser Bei Bedarf können Sie den Schalldämpfer bei OVEM 07 10 14 20 mit einer Schalldämpfererwei terung verlängern è Kapitel 11 Seite 47 5 3 Elektrisch Warnung Verwenden Sie ausschließlich Stromquellen die eine sichere elektrische Trennung der Betriebsspannung nach IEC EN 60204 1 gewährleisten Berücksichtigen Sie zusätzlich die allgemeinen Anforderungen an PELV Stromkrei...

Page 21: ...ng 24 V DC 2 Weiß WH Schaltausgang B Out B 3 Blau BU 0 V 4 Schwarz BK Schaltausgang A Out A 5 Grau GY Schalteingang In Uin 1 Bei Verwendung der Anschlussdose mit Kabel lt Zubehör 2 Anziehdrehmoment max 0 3 Nm Tab 7 Pin Belegung Schaltbilder OVEM 2P OVEM 2N OVEM PU OVEM NU OVEM PI OVEM NI Tab 8 Schaltbilder Vakuumsaugdüse ...

Page 22: ...zu vermeiden Der Grundzustand kann aus anderen Modi erreicht werden durch EDIT Knopf 3 s drücken oder Ablauf einer Überwachungszeit Timeout è Kapitel 13 Seite 51 1 Schalten Sie die Betriebsspannung ein è Die Vakuumsaugdüse befindet sich im RUN Modus 2 Prüfen Sie die Einstellungen der Vakuumsaugdüse Hinweis Eine Übersicht zur Menüstruktur finden Sie in Kapitel 13 Zum Aufbau des Vakuums 1 Beaufschla...

Page 23: ...ch Abschalten bei CN oder Einschalten bei ON der Eingangs spannung è Der Vakuumanschluss 5 wird belüftet Das Werkstück löst sich vom Sauggreifer OVEM CE OE Durch Abschalten bei CE oder Einschalten bei OE der Eingangsspannung wird das zweite Magnetventil geschaltet und ein Abwurfimpuls erzeugt è Der Vakuumanschluss 5 wird belüftet Das Werkstück löst sich vom Sauggreifer Hinweis Wird während des Abw...

Page 24: ...ng X X SP Schaltpunkt switching point X X SP min Unterer Schaltpunkt switching point minimal X X SP max Oberer Schaltpunkt switching point maximal X X SP max Diagnose Grenzwert Evakuierungszeit X X SP max Diagnose Grenzwert Belüftungszeit X X HY Hysterese X X NO Schaltcharakteristik Schließer normally open X X NC Schaltcharakteristik Öffner normally closed X X min max Extremwerte Minimaler maximal...

Page 25: ...deren Modi è Tab 10 X Spezialmenü SPEC ist aktiv 1 X In A1 digitale An zeige Druckmesswert steuert Schaltausgang Out B X X di1 digitale An zeige Diagnosemeldekanal 1 steuert Schaltausgang Out B X X di2 digitale An zeige Diagnosemeldekanal 2 steuert Schaltausgang Out B X X Er X digitale An zeige Fehlermeldung Fehlernummer è Kapitel 8 2 Seite 41 X ON OFF Diagnosekanal gesetzt nicht gesetzt kein Abwu...

Page 26: ...è Fig 23 EDIT Modus aktiv Markierte Segmente blinken TEACH Modus aktiv Schaltpunkt Evakuierungszeit max Schaltpunkt Belüftungszeit max Markierte Segmente leuchten und Option blinkt EDIT Modus aktiv ON Luftsparfunktion aktiv OFF Luftsparfunktion inaktiv Markierte Segmente leuchten und Lock blinkt EDIT Modus aktiv Spezialmenü SPEC ist geöffnet auf der LCD Anzeige wird der Sicherheitscode angezeigt S...

Page 27: ...ungszeit min msec Evakuierungszeit max msec Belüftungszeit min msec Belüftungszeit max msec 6 2 1 Einstellungen für Out A B anzeigen Die Vakuumsaugdüse muss sich im RUN Modus befinden Drücken Sie die A Taste Schaltausgang Out A oder B Taste Schaltausgang Out B è Der SHOW Modus des entsprechenden Schaltausgangs ist aktiv Hinweis Liegen Fehler vor werden nach Drücken der A oder B Taste zuerst entspr...

Page 28: ... A Taste bis die Einstellung min ausgewählt ist è min blinkt Der Minimalwert von In A1 wird angezeigt Symbolik bei Anzeige von Extremwerten è Tab 10 2 Drücken Sie kurz den EDIT Knopf è Der Minimalwert wird gelöscht 3 Drücken Sie die UP Taste A Taste è max blinkt Der Maximalwert von In A wird angezeigt 4 Drücken Sie kurz den EDIT Knopf è Der Maximalwert wird gelöscht 5 Drücken Sie die UP Taste A Ta...

Page 29: ...t die UP Taste und DOWN Taste gleichzeitig è Die zulässige Belüftungszeit wird angezeigt Die Segmente msec SP max _ blinken 3 Drücken Sie erneut die UP Taste und DOWN Taste gleichzeitig è Mit jeder weiteren Betätigung der Tasten werden nacheinander die Extremwerte min und max für Evakuierungszeit und dann für die Belüftungszeit angezeigt Möchten Sie den aktuell angezeigte Extremwert löschen dann d...

Page 30: ...viert ist Out A ein normaler Schaltausgang 6 3 1 EDIT Modus starten Warnung Abhängig von der Funktionalität der Maschine Anlage kann die Manipulation von Si gnalzuständen schwere Personen oder Sachschäden verursachen Berücksichtigen Sie dass das Ändern des Schaltverhaltens der Schaltausgänge im EDIT Modus sofort wirksam wird Mit den Bedientasten können verschiedene Einstellungen ausgewählt werden ...

Page 31: ... maximale Evakuierungs und Belüftungszeiten einstellen Fig 13 Einstellmöglichkeiten im EDIT Modus Menüstruktur EDIT Modus è Fig 24 1 Drücken Sie den EDIT Knopf è Der EDIT Modus ist aktiv und Out A blinkt oder bei aktiver Sicherheitssperre blinkt Lock 2 Drücken Sie die UP DOWN Tasten bis der gewählte Sicherheitscode eingestellt ist 3 Drücken Sie den EDIT Knopf è Out A blinkt Sicherheitscode wiedera...

Page 32: ...iguriert werden kann è Kapitel 8 2 Seite 41 Nachfolgend wird der Ablauf anhand des Schaltausgangs Out B beschrieben Die Vakuumsaugdüse befindet sich im EDIT Modus und Out A blinkt Um Out B einzustellen gehen Sie wie folgt vor 1 Drücken Sie die B Taste DOWN Taste è Out B blinkt 2 Drücken Sie den EDIT Knopf um die Auswahl zu bestätigen è In A1 wird angezeigt 3 Drücken Sie den EDIT Knopf um die Auswa...

Page 33: ...e Hysterese HY mit den UP DOWN Tasten ein 10 Drücken Sie den EDIT Knopf um den eingestellten Wert zu bestätigen è NO oder NC blinkt 11 Wählen Sie die Schaltcharakteristik NO NC mit den UP DOWN Tasten aus 12 Drücken Sie den EDIT Knopf um die Auswahl zu bestätigen è Die Vakuumsaugdüse befindet sich im RUN Modus 6 3 3 Dauer Abwurfimpuls einstellen elektrische Handhilfsbetätigung FORC L L L L Fig 15 A...

Page 34: ... für Magnetventil Abwurfimpuls 6 Drücken Sie den EDIT Knopf um das Untermenü zu beenden è Die Vakuumsaugdüse befindet sich im RUN Modus 6 3 4 SPEC Luftsparfunktion Option LS Option Sicherheitscode Evakuierungs und Belüftungszeiten einstellen L L L L Fig 16 Spezialmenü SPEC Menüstruktur EDIT Modus è Fig 24 Die Vakuumsaugdüse befindet sich im EDIT Modus und Out A blinkt 1 Drücken Sie A Taste bis das...

Page 35: ... ist deaktiviert 10 Drücken Sie den EDIT Knopf um den eingestellten Wert zu bestätigen è Die Vakuumsaugdüse befindet sich im RUN Modus 6 4 TEACH Modus Im TEACH Modus kann die Schaltgröße Schaltpunkt oder Schaltfenster mit und ohne Luftsparfunktion sowie die Belüftungs und Evakuierungszeiten geteacht werden Hinweis Stellen Sie vor dem Teachen sicher dass im EDIT Modus die gewünschte Schaltfunktion ...

Page 36: ...fen die Rei henfolge ist frei wählbar 3 Drücken Sie zuerst die A Taste UP Taste und dann zusätzlich den EDIT Knopf è A und TeachIn blinken und der Messwert wird als Teach Punkt TP1 für Out A übernommen oder bei aktiver Sicherheitssperre blinkt Lock è Kapitel 6 4 4 Seite 39 4 Wiederholen Sie die Punkte 2 und 3 für den zweiten Teach Punkt TP2 è Der zweite Teach Punkt TP2 wird übernommen und der neue...

Page 37: ...etriebsspannung ein è Die Vakuumsaugdüse befindet sich im RUN Modus 2 Stellen Sie ein erstes Vakuum TP1 ein z B Objekt gegriffen oder Objekt nicht gegriffen die Reihenfolge ist frei wählbar 3 Drücken Sie zuerst die A Taste UP Taste und dann zusätzlich den EDIT Knopf è LS wird deaktiviert A und TeachIn blinken und der Messwert wird als Teach Punkt TP1 für Out A übernommen oder bei aktiver Sicherhei...

Page 38: ...akuieren und abwerfen è Kapitel 3 6 Seite 15 Hinweis Es wird ein Mittelwert über die Zyklen gebildet Für sinnvolle Ergebnisse sollten ausrei chend Zyklen durchlaufen werden Je mehr Zyklen durchlaufen werden um so besser ist der Wert Die geteachten Werte Evakuierungszeit und Belüftungzeit werden mit einer Funktionsreserve von 100 beaufschlagt und abgespeichert 3 Drücken Sie die A und B Taste Z C gl...

Page 39: ...nge der Vakuumsaugdüse wie gewünscht schalten 7 Bedienung und Betrieb 7 1 Handhilfsbetätigung Mechanisch Fig 20 Bedienung Handhilfsbetätigung Im nicht angesteuerten oder stromlosen Zustand kann mit der Handhilfsbetätigung das Magnetventil manuell geschaltet werden Die Handhilfsbetätigung ist tastend automatische Rückstellung ausge führt Drücken Sie den Stößel der Handhilfsbetätigung mit einem stum...

Page 40: ...n Um die Vakuumsaugdüse auf Werkseinstellung zurückzusetzen gehen Sie wie folgt vor 1 Schalten Sie die Betriebsspannung aus 2 Drücken Sie alle drei Einstellelemente gleichzeitig UP Taste DOWN Taste EDIT Knopf und halten sie gedrückt 3 Schalten Sie die Betriebsspannung wieder ein 8 Wartung und Diagnose 8 1 Wartung Schalten Sie zur äußeren Reinigung folgende Energiequellen ab Betriebsspannung Druckl...

Page 41: ...1 hinein è Der Filter wird durch den Schieber 1 hineingezogen 8 2 Diagnose Es gibt vier Diagnosestufen Um die Diagnosemeldungen anzuzeigen stehen zwei Möglichkeiten zur Verfügung über die logischen Diagnosekanäle di 1 und di 2 des Ausgangs Out B nur bei 2P und 2N über die Anzeige im LCD Display der Vakuumsaugdüse Wenn die Diagnosemeldung am Ausgang Out B gewünscht wird muss der Diagnosekanal di 1 ...

Page 42: ... Aus gänge des Geräts inaktiv Alle Segmente blinken und LCD Anzeige zeigt den aktu ellen Fehler an Alle Segmente blinken bis auf LCD Anzeige Kann nicht er reicht werden da Tasten ge sperrt 1 Rote Hintergrundbeleuchtung des Displays leuchtet Diese Funktion ist für 2P ab Revision 09 Rev09 für alle anderen Typen ab Revision 07 Rev07 verfügbar è Typenschild Tab 12 Diagnosestufen 8 2 1 Diagnosemeldekan...

Page 43: ...en Sie die UP DOWN Tasten bis der gewählte Sicherheitscode eingestellt ist 3 Drücken Sie den EDIT Knopf è Out A blinkt 4 Drücken Sie die B Taste DOWN Taste è Out B blinkt 5 Drücken Sie den EDIT Knopf um die Auswahl zu bestätigen è In A1 wird angezeigt 6 Drücken Sie die B Taste bis der gewünschte Diagnosemeldekanal ausgewählt ist 7 Drücken Sie den EDIT Knopf um die Auswahl zu bestätigen è NO oder N...

Page 44: ... das Gerät defekt Gerät zu Festo senden Er35 Die eingestellte Schwelle der Evakuie rungszeit ist in 2 von 5 Zyklen um das doppelte überschritten Auf Leckage prüfen Er37 Die eingestellte Schwelle der Belüf tungszeit in 2 von 5 Zyklen um das doppelte überschritten Auf Leckage prüfen Belüftungszeit verlängern Drosselstellung überprüfen 22 Er38 Schaltfrequenz der Luftsparfunktion liegt über dem Grenzw...

Page 45: ...im SHOW Modus è Tab 9 2 Alle Segmente blinken Die aktuell kleinste Fehlernummer wird angezeigt 3 Fehlercode ist für 2P ab Revision 09 Rev09 für alle anderen Typen ab Revision 07 Rev07 verfügbar è Typenschild 4 Gilt nur für die Einstellungen des Schaltausgangs Out A 5 Mittlere Reihe der Barcodesegmente blinken Fehleranzeige im SHOW Modus è Tab 9 6 Ausgänge werden selbsttätig zurückgesetzt 0 Signal ...

Page 46: ...oder keine zulässige Betriebsspannung Versorgungsspannung einschalten zulässigen Betriebsspannungsbe reich einhalten Elektrische Anschlüsse vertauscht verpolt Gerät gemäß Anschlussbild ver kabeln Gerät defekt Gerät ersetzen Unvollständige An zeige im Display Display defekt Gerät ersetzen Falsche Druckanzeige Pneumatische Anschlüsse vertauscht Verschlauchung gemäß Abschnitt Einbau pneumatisch ausfü...

Page 47: ...ksetzen Tab 14 Störungsbeseitigung 10 Ausbau 1 Schalten Sie zum Ausbau folgende Energiequellen ab Betriebsspannung Druckluft 2 Trennen Sie die elektrischen und pneumatischen Anschlüsse von der Vakuumsaugdüse 3 Demontieren Sie die Vakuumsaugdüse 11 Zubehör Bezeichnung OVEM 05 OVEM 07 10 OVEM 14 20 Verbindungsleitung M12x1 5 polig 2 5 m NEBU M12G5 K 2 5 LE5 Verbindungsleitung M12x1 5 polig 5 m NEBU ...

Page 48: ...s 80 Bereitschaftsverzögerung ms 500 Schaltausgänge Max Ausgangsstrom mA 100 Spannungsfall V 1 5 Kapazitive Last maximal DC nF 100 Totzeit ms 10 20 35 Schutzfunktionen Induktive Schutzbeschaltung angepasst an MZ MY ME Spulen Kurzschlussfestigkeit ja Überlastfestigkeit ja Verpolungsschutz für alle elektrischen Anschlüsse Isolationsspannung V 50 Stoßspannungsfestigkeit kV 0 8 Schutzart IP65 Schutzkl...

Page 49: ... Das Produkt ist für den Einsatz im Industriebereich vorgesehen Im Wohnbereich müssen evtl Maßnahmen zur Funkentstörung getroffen werden Tab 16 Technische Daten 12 1 Werkseinstellung OVEM H OVEM L Out A SP 0 7 bar 0 4 bar SPmin 0 7 bar 0 4 bar SPmax 0 97 bar 0 67 bar HYS 0 25 bar 0 25 bar 0 1 bar 0 1 bar SPLS 0 7 bar 0 7 bar 0 4 bar 0 4 bar HYSLS 0 25 bar 0 25 bar 0 25 bar 0 25 bar Out B SP 0 5 ba...

Page 50: ...ol OVEM Symbol QO GO CN 2P 2N PU PI NU NI QO GO CE 2P 2N PU PI NU N QS GN CN 2P 2N PU PI NU NI QS GN CE 2P 2N PU PI NU NI QO GO ON 2P 2N PU PI NU NI QO GO OE 2P 2N PU PI NU NI QS GN ON 2P 2N PU PI NU NI QS GN OE 2P 2N PU PI NU NI Tab 18 Schaltsymbole der Funktion ...

Page 51: ...Messwertes hier TP1 Symbol auf dem Display blinkt leuchtet hier Out A Sicherheitscode aktiv Sperrung gegen unbefugte Programmierung Parame trierung Sicherheitscode inaktiv UP Taste A drücken weiterschalten umschalten im Menü UP Taste A oder DOWN Taste B drücken Wert einstellen Taste hier DOWN Taste und EDIT Knopf gleichzeitig drücken EDIT Knopf drücken Verzweigung im Menüsystem Anzeige aktueller F...

Page 52: ...OVEM 52 Festo OVEM 1407c Deutsch Fig 23 SHOW Modus ...

Page 53: ...OVEM Festo OVEM 1407c Deutsch 53 Fig 24 EDIT Modus ...

Page 54: ...OVEM 54 Festo OVEM 1407c Deutsch Fig 25 TEACH Modus ...

Page 55: ...eige 42 Diagnosemeldekanal 42 Fehlercode 44 Display 6 Symbolik 24 E EDIT Modus 10 30 53 Einbau elektrisch 20 mechanisch 18 pneumatisch 20 Einschaltschwelle 13 Einstellen Belüftungszeit 34 Dauer Abwurfimpuls 33 Evakuierungszeit 34 Intensität Abwurfimpuls 23 Luftsparfunktion 34 Schaltausgänge 32 Sicherheitscode 34 Evakuierungszeit 15 anzeigen 29 einstellen 34 löschen 29 teachen 38 Vakuum löschen 28 ...

Page 56: ...1 Schalteingang 10 Schaltpunkte 14 Schlauch Innendurchmesser 20 Schwellwert Saugen abschalten 13 Saugen einschalten 13 Schwellwert Komparator Hysterese 14 Schaltpunkt 14 Symbolik 24 SHOW Modus 10 27 52 Sicherheitscode eingeben 39 einstellen 34 zurücksetzen 40 Spezialmenü Belüftungszeit 34 Evakuierungszeit 34 Luftsparfunktion Option 34 Sicherheitscode 34 Symbolik 25 Stecker Pin Belegung 21 Störungs...

Page 57: ...ode of operation of the air saving function LS 66 3 4 Switching points and hysteresis 68 3 5 Diagnostics 68 3 6 Measured variables 69 4 Requirements for product use 70 5 Installation 72 5 1 Mechanical 72 5 1 1 Direct mounting 72 5 1 2 Mounting with accessories 72 5 2 Pneumatic 74 5 3 Electrical 74 6 Commissioning 76 6 1 Symbolic LCD display 78 6 1 1 Segment bars 80 6 2 SHOW mode 81 6 2 1 Display s...

Page 58: ...ching variables 90 6 4 2 Teach air saving function LS 91 6 4 3 Teach pressurisation and evacuation times 92 6 4 4 Enter the security code 93 6 4 5 Test run 93 7 Operation 93 7 1 Manual override 93 7 2 Changing settings and values 94 7 3 Reset to factory setting 94 8 Maintenance and diagnostics 94 8 1 Maintenance 94 8 2 Diagnostics 95 8 2 1 Set diagnostic message channel di x 96 8 2 2 Error code 98...

Page 59: ...rt 4 Exhaust port silencer 5 Vacuum port 6 Replaceable filter element 7 Housing with mounting holes 8 Slide for changing the filter 9 Filter housing with inspection window aJ Flow control screw for adjusting the intensity of the ejector pulse aA Operating buttons aB EDIT button aC LCD display aD Plug connector for electrical connection M12 Fig 1 Control sections and connections ...

Page 60: ...vacuum display special display 5 Toolbar for functions è Tab 9 6 EDIT button 7 DOWN button B button 8 UP button A button 9 Vacuum display aJ Status indicator solenoid valve Fig 2 Display Note The operating buttons are designated differently in the user guidance depending on use With the selection of the switching outputs A button B button With the selection of menu items and setting values UP butt...

Page 61: ...read B GN All ports with NPT female thread BN GN GO Supply vacuum port with female G threads exhaust port with open silencer B GO Supply vacuum port with female NPT threads exhaust port with open pneumatic silencer BN GO PL Prepared for supply strip vacuum port and exhaust port with QS fittings B PL Prepared for supply strip vacuum port and exhaust port with QS fittings in inch sizes BN PL PO Prep...

Page 62: ...s shipped with the following factory settings Air saving function with CE OE active Switching characteristics of the electrical output threshold value comparator Switching element function of the electrical output NO normally open Additional factory settings è chapter 12 1 page 103 1 Mount the vacuum suction nozzle è chapter 5 1 page 72 2 Connect the vacuum suction nozzle pneumatically è chapter 5...

Page 63: ...m suction nozzle s air saving function è chapter 3 3 page 66 The air saving function of the vacuum suction nozzle CE CO is activated in the factory The air saving function can be switched off è chapter 6 3 4 page 88 The compressed air supply is controlled by an integrated solenoid valve The solenoid valve can be supplied with two different switching functions NC and NO The vacuum is generated as s...

Page 64: ... the RUN mode The TEACH mode is used for fast configuration of the vacuum suction nozzle s data The data can be revised if needed via the EDIT mode è chapter 6 4 page 89 3 2 Switching outputs and switching input The vacuum is monitored with the aid of a piezo resistive sensor element with following electronic eval uation unit The measurement result of In A1 is now shown numerically and graphically...

Page 65: ...pulse Fig 4 Switching characteristics of switching input Code Diagnostics Switching output A Switching output B Switching input 2P Message off Switching output Positive switching Pressure sensor out put A Switching output Positive switching Pressure sensor out put B Switching input Positive switching Message on Switching output Positive switching Diagnostic message PI Analogue output 4 20 mA Vacuu...

Page 66: ...ing function is activated in the factory The air saving function can be switched off è chapter 6 3 4 page 88 If the desired threshold value 1 is reached for the vacuum vacuum generation is automatically switched off A non return valve prevents the reduction of the vacuum Nonetheless leakage e g due to rough workpiece surfaces will slowly reduce the vacuum If the pressure drops below the set thresh...

Page 67: ...ain when the vacuum is worse than threshold 3 The threshold values are defined as follows Threshold value Switch off suction 1 The threshold value 1 is equal to the customer adjustable switch on threshold 2 of the output Out A è Fig 5 that is the vacuum generator is switched off simultaneously with the setting of the output Out A Threshold value Switch on suction 3 The threshold value 3 lies betwe...

Page 68: ...onitors additional system characteristics as well These include evacuation times or the function of the solenoid valves for ex ample The diagnostic function permits the user to detect malfunctions early and locate errors quickly In case of malfunctions the red background illumination of the display lights up The system status can be identified over large distances The diagnostic messages are shown...

Page 69: ...on nozzle is switched off Cycle The duration of a cycle covers the time from the start of evacuation through ejection to the start of the new evacuation è Fig 6 In Out A 3 4 1 2 2 5 Suction 1 Cycle 2 Evacuation time tevac 3 Air supply time tair 4 Switch on point Out A 5 Switch off point Out A Fig 6 Definition of cycle example for Out A Pressurisation and evacuation times The minimum and maximum pr...

Page 70: ...re that the following specifications are always observed Note The vacuum is measured as relative pressure The displayed pressure value is the actual pressure difference to ambient pressure The attainable displayed pressure value may be lower than the value indicated in the specifications depending on the current abso lute ambient pressure air pressure Compare the limit values specified in these op...

Page 71: ... 2 power source or Class 2 transformer in accordance with UL1310 or UL1585 As an alternative a LV C Limited Voltage Current power source with one of the following properties can be used This device shall be used with a suitable isolating source such that the maximum open circuit voltage potential available to the product is not more than 24 V DC and the current is limited to a value not exceeding ...

Page 72: ...e exhaust can flow without hindrance 5 1 Mechanical 5 1 1 Direct mounting Fig 7 Direct mounting Mount the vacuum suction nozzle at the intended position with two screws size of the mounting screws è Tab 5 assembly torque max 2 5 Nm We recommend the use of corresponding washers or Mount the vacuum suction nozzle on the bottom with 4 screws size M3 with max mounting torque 0 8 Nm OVEM Size of mounti...

Page 73: ...ion of the arrow 3 Secure the vacuum suction nozzle to the H rail with screw 1 Mounting bracket Fig 9 Mounting bracket Mount the vacuum suction nozzle at the intended position with two screws size of the mounting screws è Tab 5 assembly torque max 2 5 Nm We recommend the use of corresponding washers Common supply manifold The vacuum suction nozzle can also be mounted on a common supply manifold wi...

Page 74: ...m hose internal diameters If required you can extend the pneumatic silencer for OVEM 07 10 14 20 with a sound absorber extension è chapter 11 page 101 5 3 Electrical Warning Use only power sources which guarantee reliable electrical isolation of the operating voltage in accordance with IEC EN 60204 1 Also observe the general requirements for PELV power circuits in accordance with IEC EN 60204 1 No...

Page 75: ...H Switching output B Out B 3 Blue BU 0 V 4 Black BK Switching output A Out A 5 Grey GY Switching input In Uin 2 With usage of the plug socket with cable as specified in Accessories 3 Max tightening torque 0 3 Nm Tab 7 Pin allocation Circuit diagrams OVEM 2P OVEM 2N OVEM PU OVEM NU OVEM PI OVEM NI Tab 8 Circuit diagrams for vacuum suction nozzle ...

Page 76: ...a blunt object The basic status can be reached from other modes by pressing EDIT button 3 s or expiration of a monitoring time timeout è chapter 13 page 105 1 Switch on the operating voltage è The vacuum suction nozzle is in the RUN mode 2 Check the settings of the vacuum suction nozzle Note An overview of the menu structure can be found in chapter 13 Building up the vacuum 1 Pressurize the vacuum...

Page 77: ...tching the input voltage off in the case of CN or on in the case of ON è The vacuum port 5 is pressurized The workpiece detaches itself from the suction gripper OVEM CE OE Switching the input voltage off for CE or on for OE switches the second solenoid valve and gen erates an ejector pulse è The vacuum port 5 is pressurized The workpiece detaches itself from the suction gripper Note Switching the ...

Page 78: ...witching point X X SP min Lower switching point switching point minimum X X SP max Upper switching point switching point maximum X X SP max Diagnostics evacuation time limit value X X SP max Diagnostics air supply time limit value X X HY Hysteresis X X NO Switching characteristic of normally open contact X X NC Switching characteristic of normally closed contact X X min max Extreme values minimum ...

Page 79: ...e in other modes è Tab 10 X Special menu SPEC is active 1 X In A1 digital display Pressure measurement value controls switching output Out B X X di1 digital display Diagnostic message channel 1 controls switch ing output Out B X X di2 digital display Diagnostic message channel 2 controls switch ing output Out B X X Er X digital display Error message error number è chapter 8 2 page 95 X ON OFF Diag...

Page 80: ...ked segments flash TEACH mode active Switching point max evacuation time Switching point max air supply time Marked segments light up and Option flashes EDIT mode active ON Air saving function active OFF Air saving function inactive Marked segments light up and Lock flashes EDIT mode active Special menu SPEC is open the security code is shown on the LCD display Segment at the bottom right is lit R...

Page 81: ...ply time msec Evacuation time min msec Evacuation time max msec Air supply time min msec Air supply time max msec 6 2 1 Display settings for Out A B The vacuum suction nozzle must be in the RUN mode Press the A button switching output Out A or the B button switching output Out B è The SHOW mode of the corresponding switching output is active Note If there are errors pressing the A or B button firs...

Page 82: ...P key A button until the setting min is selected è min flashes The minimum value of In A1 is displayed Symbols during display of extreme values è Tab 10 2 Briefly press the EDIT button è The minimum value is deleted 3 Press the UP key A button è max flashes The maximum value of In A is displayed 4 Briefly press the EDIT button è The maximum value is deleted 5 Press the UP key A button è The vacuum...

Page 83: ...ey and DOWN key again simultaneously è The permitted air supply time is displayed The segments msec SP max _ flash 3 Press the UP key and DOWN key again simultaneously è Each additional time the buttons are actuated the extreme values min und max for evacu ation time and then for air supply time will be shown one after the other If you wish to delete the currently displayed extreme value briefly p...

Page 84: ...vated Out A is a normal switching output 6 3 1 Start EDIT mode Warning Depending on the functions of the machine system the manipulation of signal statuses can cause serious injury to people and material damage Note that if the switching characteristics of the switching outputs is modified in the EDIT mode the new status will be effective immediately Various settings can be selected with the opera...

Page 85: ...LS option security code maximum evacuation and air supply times Fig 13 Setting options in the EDIT mode menu structure EDIT mode è Fig 24 1 Press the EDIT button è The EDIT mode is active and Out A flashes or if there is an active security lock Lock flashes 2 Press the UP DOWN keys until the chosen security code is set 3 Press the EDIT button è Out A flashes Store the security code where it can be...

Page 86: ...B can also be configured as a diagnostic output è chapter 8 2 page 95 In the following the process is described using the switching output Out B The vacuum suction nozzle is in the EDIT mode and Out A is flashing To set Out B proceed as follows 1 Press the B button DOWN key è Out B flashes 2 Press the EDIT button to confirm the selection è In A1 is displayed 3 Press the EDIT button to confirm the ...

Page 87: ...with the UP DOWN keys 10 Press the EDIT button to confirm the set value è NO or NC flashes 11 Select the switching characteristic NO NC by pressing the UP DOWN keys 12 Press the EDIT button to confirm the selection è The vacuum suction nozzle is in the RUN mode 6 3 3 Set duration of ejector pulse electrical manual override FORC L L L L Fig 15 Set ejector pulse length menu structure EDIT mode è Fig...

Page 88: ...jector pulse solenoid valve 6 Press the EDIT button to exit the submenu è The vacuum suction nozzle is in the RUN mode 6 3 4 SPEC Set air saving function option LS option security code evacuation and air supply times L L L L Fig 16 Special menu SPEC menu structure EDIT mode è Fig 24 The vacuum suction nozzle is in the EDIT mode and Out A is flashing 1 Press the A button until the menu SPEC is sele...

Page 89: ...IT button to confirm the set value è The vacuum suction nozzle is in the RUN mode 6 4 TEACH mode In the TEACH mode the switching variable switching point or switching window with and without air saving function as well as the air supply and evacuation times can be taught Note Before teaching make sure that the desired switching function window or threshold comparator and the desired hysteresis are...

Page 90: ...or object not gripped the sequence is freely select able 3 First press the A button UP key and then also the Edit button è A und TeachIn flash and the measurement value is taken over as a teach point TP1 for Out A or Lock flashes if security blocking is active è chapter 6 4 4 page 93 4 Repeat points 2 and 3 for the second teach point TP2 è The second teach point TP2 is taken over and the new switc...

Page 91: ...Switch on the operating voltage è The vacuum suction nozzle is in the RUN mode 2 Set an initial vacuum TP1 e g object gripped or object not gripped the sequence is freely select able 3 First press the A button UP key and then also the Edit button è LS is deactivated A und TeachIn flash and the measurement value is taken over as a teach point TP1 for Out A or Lock flashes if security blocking is ac...

Page 92: ... cycle i e evacuate and eject è chapter 3 6 page 69 Note A mean value is created across the cycles A sufficient number of cycles should be run so that the results will be meaningful The more cycles are run the better is the value The taught values evacuation time and air supply time are applied with a function re serve of 100 and stored 3 Press the A and B button Z C simultaneously and then also t...

Page 93: ...on nozzle s switching output switches as desired 7 Operation 7 1 Manual override Mechanical Fig 20 Operating the manual override The manual override can be used to switch the solenoid valve manually when it is not being actuated or not supplied with power The manual override is non detenting automatic reset Press down the plunger of the manual override with a blunt pin The solenoid valve is brough...

Page 94: ...ozzle to factory setting proceed as follows 1 Switch off the operating voltage 2 Press all three setting elements UP button DOWN button EDIT button simultaneously and keep them depressed 3 Switch the operating voltage back on 8 Maintenance and diagnostics 8 1 Maintenance Switch off the following energy sources before cleaning the exterior of the device operating voltage compressed air If necessary...

Page 95: ...lled in by the slide 1 8 2 Diagnostics There are four diagnostic levels There are two options for displaying the diagnostic messages via the logical diagnostic channels di 1 and di 2 of the output Out B only for 2P and 2N via the indicator in the LCD display of the vacuum suction nozzle If the diagnostic message is desired at the output Out B the diagnostic channel di 1 or di 2 must be set configu...

Page 96: ...able outputs of the device are inactive All segments are flashing and LCD display shows the cur rent error All segments are flashing ex cept for LCD dis play Cannot be achieved since keys are blocked 1 Red background illumination of the display is lit This function is available for 2P from Revision 09 Rev09 for all other types from Revision 07 Rev07 è rating plate Tab 12 Diagnostic levels 8 2 1 Se...

Page 97: ...ock flashes 2 Press the UP DOWN keys until the chosen security code is set 3 Press the EDIT button è Out A flashes 4 Press the B button DOWN key è Out B flashes 5 Press the EDIT button to confirm the selection è In A1 is displayed 6 Press the B button until the desired diagnostic channel is selected 7 Press the EDIT button to confirm the selection è NO or NC flashes 8 Select the switching characte...

Page 98: ... the device is defective Send device to Festo Er35 The set threshold for evacuation time is exceeded by a factor of two in 2 of 5 cycles Check for leakage Er37 The set threshold for air supply time is exceeded by a factor of two in 2 of 5 cycles Check for leakage Lengthen air supply time Check throttle setting 22 Er38 Switching frequency of the air saving function lies above the limit value of 1 H...

Page 99: ...OW mode è Tab 9 2 All segments are flashing The currently smallest error number is shown 3 Error code is available for 2P from Revision 09 Rev09 for all other types from Revision 07 Rev07 è rating plate 4 Applies only for the settings of the switching output Out A 5 Middle row of the barcode segments is blinking error display in the SHOW mode è Tab 9 6 Outputs are reset automatically logic 0 Tab 1...

Page 100: ...Supply voltage not applied or permitted operating voltage not present Switch on supply voltage maintain permitted operating voltage range Electrical connections swapped incorrect polarity Wire in accordance with the circuit diagram Device defective Replace the device Incomplete display Display defective Replace the device Incorrect pressure display Pneumatic connections swapped Connect tubing in a...

Page 101: ...t hysteresis Tab 14 Fault clearance 10 Disassembly 1 Switch off the following sources of energy before disassembly operating voltage compressed air 2 Disconnect the electrical and pneumatic connections to the vacuum suction nozzle 3 Remove the vacuum suction nozzle 11 Accessories Designation OVEM 05 OVEM 07 10 OVEM 14 20 Connecting cable M12x1 5 pin 2 5 m NEBU M12G5 K 2 5 LE5 Connecting cable M12x...

Page 102: ...s 500 Switching outputs Max output current mA 100 Voltage drop V 1 5 Maximum capacitive load DC nF 100 Dead time ms 10 20 35 Protective functions Inductive protective circuit Adapted to MZ MY ME coils Protection against short circuit Yes Overload protection Yes Protection against incorrect polarity For all electrical connections Insulation voltage V 50 Surge resistance kV 0 8 Degree of protection ...

Page 103: ...9 1 The product is intended for use in industrial environments Measures for interference suppression may need to be implemented in residential areas Tab 16 Technical data 12 1 Factory setting OVEM H OVEM L Out A SP 0 7 bar 0 4 bar SPmin 0 7 bar 0 4 bar SPmax 0 97 bar 0 67 bar HYS 0 25 bar 0 25 bar 0 1 bar 0 1 bar SPLS 0 7 bar 0 7 bar 0 4 bar 0 4 bar HYSLS 0 25 bar 0 25 bar 0 25 bar 0 25 bar Out B ...

Page 104: ... OVEM Symbol QO GO CN 2P 2N PU PI NU NI QO GO CE 2P 2N PU PI NU N QS GN CN 2P 2N PU PI NU NI QS GN CE 2P 2N PU PI NU NI QO GO ON 2P 2N PU PI NU NI QO GO OE 2P 2N PU PI NU NI QS GN ON 2P 2N PU PI NU NI QS GN OE 2P 2N PU PI NU NI Tab 18 Circuit symbols for the function ...

Page 105: ...the measured value here TP1 Symbol on the display flashes illuminated here Out A Security code active block to prevent unauthorised programming parameterisa tion Security code inactive Press the UP key A continue reverse in the menu Press the UP key A or the DOWN key B set value Press key here DOWN key and EDIT button simultaneously Press the EDIT button Branching in the menu system Display of cur...

Page 106: ...OVEM 106 Festo OVEM 1407c English Fig 23 SHOW mode ...

Page 107: ...OVEM Festo OVEM 1407c English 107 Fig 24 EDIT mode ...

Page 108: ...OVEM 108 Festo OVEM 1407c English Fig 25 TEACH mode ...

Page 109: ... 96 Symbols 78 Display 60 Symbols 78 E EDIT mode 64 84 107 Ejector pulse Adjusting intensity 77 Set duration 87 Symbols 78 Error code 98 Evacuation time 69 Delete 83 Display 83 Setting 88 Teach 92 Vacuum Delete 82 Extreme values Air supply time 69 Delete 83 Display 83 Evacuation time 69 Delete 83 Display 83 Vacuum 69 Display 82 F Factory setting 103 Reset 94 Fault clearance 98 100 Features 61 H H ...

Page 110: ...ty code 88 Switching outputs 86 SHOW mode 64 81 106 Special menu Air supply time 88 Air saving function option 88 Evacuation time 88 Security code 88 Symbols 79 Switch back threshold 67 Switch on threshold 67 Switching input 64 Switching output 64 Display settings 81 Setting 86 Symbols 78 Teach 90 Switching points 68 Symbols Display 78 Segment bars 80 T TEACH mode 64 89 108 Teaching Air supply tim...

Page 111: ...tereintragung vorbehalten Reproduction distribution or sale of this document or communica tion of its contents to others without express authorization is prohibited Offenders will be liable for damages All rights re served in the event that a patent utility model or design patent is registered Copyright Festo AG Co KG Postfach 73726 Esslingen Deutschland Phone 49 711 347 0 Fax 49 711 347 2144 e ma...

Reviews: