![Festo MPS PA Operating Instructions Manual Download Page 62](http://html1.mh-extra.com/html/festo/mps-pa/mps-pa_operating-instructions-manual_2283255062.webp)
Maintenance and troubleshooting
Bottling Learning System
62
© Festo Didactic
696690
12.6
Error due to parameterization
The following table shows errors that can be influenced by incorrect setting of parameters or can occur as a
result of incorrect operation.
Location
Error /
Disturbance variable /
Danger potential
What is the effect of the
error, disturbance
variable, or danger?
What causes errors?
How can I detect and
prevent errors?
Parameter error
Pump
Characteristic curve not
linear
In the case of level
control, the I system
cannot be compensated
to zero with the P
controller
System performance
Set offset of the
manipulated variable in
FluidLab-PA
Motors MA31/MA32 of
the conveyor belts
Motor controller QA2
switches off
Tapes do not run
Adjustment values of the
potentiometers on the
motor controller are
adjusted
Visual inspection / data
sheet, motor controller,
setting of values:
increase current
limitation /
Increase speed to 50% /
ramp
Upper tank VE2
The filling level signal in
FluidLab-PA does not
match the scale display
on the tank
Measurement error or
inaccuracy
Adjust filling level sensor
and/or edit setting
parameters for tank
geometry
Settings in FluidLab-PA
EasyPort
Connection to EasyPort
Connection cannot be
established
Set the EasyPort
address, e.g. 2,
at the EasyPort using the
Address buttons
Summary of Contents for MPS PA