BLUEHELIX TECH RRT 24 C
27
EN
cod. 3541P250 - Rev. 01 - 07/2018
P34
Pump operation
0-3 = Operation strategy
2
P35
Modulating pump min. speed
30-100%
30%
P36
Modulating pump start speed
90-100%
90%
P37
Modulating pump max. speed
90-100%
100%
P38
Pump deactivation temperature during Post-Circu-
lation (b01=1)
0-100°C
50°C
Pump deactivation temperature during Post-Circu-
lation (b01=2)
0-100°C
55°C
Pump deactivation temperature during Post-Circu-
lation (b01=3)
0-100°C
55°C
Pump deactivation temperature during Post-Circu-
lation (b01=4)
0-100°C
55°C
P39
Pump activation hysteresis temperature during
Post-Circulation (b01=1)
0-100°C
10°C
Pump activation hysteresis temperature during
Post-Circulation (b01=2)
0-100°C
25°C
Pump activation hysteresis temperature during
Post-Circulation (b01=3)
0-100°C
25°C
Pump activation hysteresis temperature during
Post-Circulation (b01=4)
0-100°C
25°C
P40
Heating user max. setpoint
20-90°C
80°C
P41
Max. output in heating
0-100%
80%
P42
Burner shutdown in DHW (b01=1)
0=Fixed, 1=Linked to setpoint, 2=Solar
0=Fixed
Legionella protection (b01=2)
0-7=Days of activation (1 = Once every 24 hours /
7= Once every 168 hours)
0=No protection
Burner shutdown in DHW (b01=3)
0=Fixed, 1=Linked to setpoint, 2=Solar
0=Fixed
Legionella protection (b01=4)
0-7=Activation days
0=No protection
P43
Comfort activation temperature (b01=1)
0-50°C
40°C
Hot water tank hysteresis (b01=2)
0-60°C
2°C
Comfort activation temperature (b01=3)
0-80°C
40°C
Hot water tank hysteresis (b01=4)
0-60°C
2°C
P44
Not used (b01=1)
Do not modify
0
Primary setpoint (b01=2)
70-85°C (Primary circuit temperature adjustment in
DHW)
80°C
Comfort deactivation hysteresis (b01=3)
0-20°C
20°C
Primary setpoint (b01=4)
70-85°C (Primary circuit temperature adjustment in
DHW)
80°C
P45
DHW standby time (b01=1)
30-255seconds
120seconds
DHW standby time (b01=2)
30-255seconds
120seconds
DHW standby time (b01=3)
30-255seconds
120seconds
DHW standby time (b01=4)
30-255seconds
120seconds
P46
DHW user max. setpoint (b01=1)
40-70°C
55°C
DHW user max. setpoint (b01=2)
40-70°C
65°C
DHW user max. setpoint (b01=3)
40-70°C
55°C
DHW user max. setpoint (b01=4)
40-70°C
65°C
P47
DHW pump Post-Circulation (b01=1)
0-255seconds
3seconds
DHW pump Post-Circulation (b01=2)
0-255seconds
30seconds
DHW pump Post-Circulation (b01=3)
0-255seconds
30seconds
DHW pump Post-Circulation (b01=4)
0-255seconds
30seconds
P48
Max. output in DHW
0-100%
100%
P49
Comfort1 standby time (b01=1)
0-100minutes
20minutes
Not implemented (b01=2)
--
--
Not implemented (b01=3)
--
--
Not implemented (b01=4)
--
--
Contents Description
Range
Default