BLUEHELIX TECH RRT 24 C
18
EN
cod. 3541P250 - Rev. 01 - 07/2018
Position of terminals
fig. 28
Minimum dimensions of fume exhaust terminals
A
Directly under an opening, air inlet, openable window, etc.
300 mm
B
Above an opening, air inlet, openable window, etc.
300 mm
C
Horizontally to an opening, air inlet, openable window, etc.
300 mm
D
Under gutters, drain pipes
75 mm
E
Under cornices or under eaves
200 mm
F
Under balconies or garages
200 mm
G
From a drain pipe or a vertical drain pipe
150 mm
H
From an internal or external corner
100 mm
I
Above ground level, a roof or balcony
300 mm
J
From a surface facing the terminal
600 mm
K
From a terminal facing the terminal
1200 mm
L
From a garage opening (e.g. door, window) with access to the home
1200 mm
M
Vertically from a terminal on the same wall
1500 mm
N
Horizontally from a terminal on the same wall
300 mm
O
From the wall on which the terminal is fitted
N/A
P
From a vertical structure on the roof
150 mm
Q
Above the intersection with the roof
300 mm
NOTES
•
N/A = Not applicable
•
Also, the terminal must be at least 150 mm (fanned draught) from an opening made in the structure of the building to
house a fitted element such as a window frame.
•
Positions of flue terminals: if the flue is installed at a low level the potential effect of the plume must be considered.
Special plume management kits are available by request.
•
The plume must not be directed towards:
-
A frequented approach
-
A window or door
-
An adjacent property
P
D, E
Q
Q
l
B
C
A
G
F
L
J
H
H
K
N
N
M
M
Q