BLUEHELIX TECH RRT 24 C
17
EN
cod. 3541P250 - Rev. 01 - 07/2018
Table. 5- Accessories
Connection to collective flues
fig. 27- Examples of connection to collective flues (
= Air /
= Fumes)
Table. 6 - Examples & classification
If the boiler is to be connected
BLUEHELIX TECH RRT 24 C
to a collective flue or to a single flue with natural draught,
the flue or chimney must be expressly designed by professionally qualified technical personnel in conformity with the
current regulations and be suitable for room sealed fan assisted boilers.
Backflow preventer valve
The boiler
BLUEHELIX TECH RRT 24 C
is equipped as standard with a backflow preventer valve (anti-backflow sys-
tem), therefore it can be connected
to a positive
pressure collective flue system, only if using G20 gas.
Losses in m
eq
Air
intake
Fume exhaust
Vertical
Horizontal
Ø 80
PIPE
1 m M/F
1KWMA83W
1.0
1.6
2.0
BEND
45° M/F
1KWMA65W
1.2
1.8
90° M/F
1KWMA01W
1.5
2.0
PIPE SECTION
with test point
1KWMA70W
0.3
0.3
TERMINAL
air, wall
1KWMA85A
2.0
-
fumes, wall with antiwind
1KWMA86A
-
5.0
FLUE
Fume outlet only Ø80
01
1KWMA86U
-
4.0
ATTENTION: CONSIDER THE HIGH PRESSURE LOSSES OF Ø50 and Ø60 ACCESSORIES; USE
THEM ONLY IF NECESSARY AND AT THE LAST FUME EXHAUST SECTION.
Type
Description
C2X
Intake and exhaust in common flue (intake and exhaust in same flue)
C4X
Intake and exhaust in common and separate flues, but undergoing similar pressure zones
C8X
Exhaust in single or common flue and wall air intake
B3X
Intake from installation room by means of concentric duct (that encloses the exhaust) and exhaust in common flue with
natural draught
IMPORTANT- THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION FOR COMBUSTION PURPOSES
C
8X
C
2X
C
4X