17. Make sure that the DC network is de-energized and that the
Pylontech SC100 Controller is switched off. DC cable type D and
DC cable type E and the DC cable to the EnergyHub in the terminal
blocks as shown above.
18. Connect ESO 1 to an adapter from the ESO distribution. Connect
the CAN communication cable from the Pylontech control module
NOTE
the red twisted Pre Charge cable connected to 3 of 6
adapters. These 3 adapters must be connected to ESO no. 1,3 and
5.
19. Connect ESO 2 to an adapter without a Pre Charge cable. Then
connect ESO 1 and ESO 2 with an Ethernet cable as shown above.
The Ethernet cable is connected in the right input on ESO 1 and in
the left input on ESO 2. Also make sure that the black DIP switches
on the ESO are in the correct position as shown above.
20. Connect the remaining ESOs to the remaining adapters from
the ESO distribution, connect them with Ethernet cables in
numerical order just as with ESO 1 and 2. The picture above
illustrates the connection of ESOs with Ethernet cables seen from
behind.