background image

FEMA ELECTRÓNICA . Series K . K40-CR

11

1.12 Configuration menu (cont.)

Trigger level

Trigger level (from 

0 to 31). Each 

level is approx. 

0.128 Vdc.

Excitation 

 

voltage

Antirrebound

Antirrebound filter 

 

(0 to 1000 mSec.)

Alarms

Alarm 1

Alarm mode

Deactivated

Normal

Repeat

Setpoint

Type of alarm

els, value ‘

on_h’

 activates the reset on high signal value, and value 

on_0’

 activates reset on low signal. Front reset activates always by 

state.

• ‘

Trigger level

’ (‘

trIG

’) - select the signal voltage level at which the 

instrument will consider that the signal has reached the activation 

level. Selectable from 0 to 31 levels, where each level is approx.

imately 0.128 Vdc. Trigger level is the same for channels ‘start’ and 

‘stop’. Reset channel has a fixed trigger to 2,5 Vdc. The three leds to 

the left of the value reflect the state (‘0’ or ‘1’) of control channels 

‘Start’, ‘Stop’ and ‘Reset’.
• ‘

Excitation voltage

’ (‘

V.EXc

’) - power provided by the instrument 

to  power-up  the  sensors  (if  needed)  used  to  control  the  signals 

‘start’, ‘stop’ and / or ‘reset’, or to be used as an active signal (‘1’) for 

special connections. Select the for the excitation voltage at 5 Vdc, 

9 Vdc, 15 Vdc or 18 Vdc. Select ‘

no

’ to disable the excitation voltage.

•  ‘

Antirrebound  filter

’  (‘

rbnd

’)  -    Vlue  between  0 mSeconds  and 

1000 mSeconds. when a signal is received, detection of additional 

signals is inhibited for the time defined in this parameter. Recom

-

mended  value  for  a  mechanical  contact  sensor  is  100 mSeconds. 

Applies to  ‘start’, ‘stop’ and ‘reset’ signals.

The ‘

Alarms

’ (‘

ALr

’) menu configures the independent activation of 

up to 3 relay outputs (or transistor or SSR control), installed with the 

R1 (or T1 or SSr) optional modules 

(see section 2.1)

For outputs up 

to 4 and 6 relays, see special modules R2, R4 and R6 at section 

2.6

The alarm states are indicated in the front display with leds marked 

as ‘1’, ‘2’ and ‘3’.To configure an alarm, enter into the alarm menu 

(‘

ALr1

’, ‘

ALr2

’ or ‘

ALr3

’) and configure the following parameters :

•  parameter  ‘

Alarm mode

’  (‘

Mode

’)  allows  to  disable  the  alarm 

(‘

oFF

’) or to select between two working modes : 

•in  ‘

normal

’  mode  (‘

norM

‘)  the  alarm  has  a  setpoint  con

-

figured, that activates when the display reading reaches the 

setpoint value. It can be configured as a ‘maximum alarm’ or 

‘minimum alarm’. Provides configuration for independent ac

-

tivation and deactivation delays, flash control and action se

-

lection on activation.
• in ‘

repeat

’ mode (‘

rEPt

’) the alarm activates each time that 

the  chronometer  reaches  a  multiple  of  the  setpoint.  Alarm 

remains  active  during  the  time  indicated  at  parameter  ‘

de-

activation delay

’ (‘

dEL.1

’). Other parameters on the ‘

Alarm

’ 

menu have no effect in this mode. This mode is not functional 

in viewing modes with tenths of second or cents of second.

Application  :  chronometer  in  ‘mm.ss’  mode  with  a’repeat’ 

alarm  and  setpoint  1  at  ‘15.00’.  Alarm  activates  ar  ‘15.00’, 

‘30.00’, ‘45.00’, etc. 

• at ‘

Alarm type

’ (‘

TypE

’) select the alarm to act as a maximum type 

alarm (‘

MAX

’) or a minimum type alarm (‘

MIn

’). The maximum type 

alarm (or minimum type alarm) activates when the display value is 

higher (or lower) than the setpoint value.
• at ‘

Setpoint

’ (‘

SEt

’) enter the value for the alarm activation point

.

 

This parameter is eligible for configuration through the ‘

Fast access

’ 

menu 

(see section 1.12.5).

1.12.4 

Alarms

Summary of Contents for K40-CR

Page 1: ...4 digit display Fast access to alarm setpoints special modes for counting exceeded time and totalized counting times on power up function configurable led brightness Universal AC and DC power Up to 3...

Page 2: ...nt time has passed see section 1 12 4 The on_alarm parameter allows to associated a predefined function to the activation of the alarm Available functions are stop counting activate the reset set read...

Page 3: ...1 12 9 Function Password 13 1 12 10 Factory reset 13 1 12 11 Firmware version 13 1 12 12 Brightness 13 1 12 13 Access to optional modules 13 1 13 Full configuration menu 14 1 14 Factory configuration...

Page 4: ...nnection for correct operation nor for com pliance with the security regu lations 8 9 0 Fuse To comply with security regulation 61010 1 add to the power line a protection fuse acting as disconnection...

Page 5: ...ation menu a B function automatically activates the alternative connections mode The reset function can be activated from three independent and con figurable sources Front reset associated to the fron...

Page 6: ...e 18Vdc 15Vdc 9 Vdc 5Vdc maximum current 70 mA protection yes current limited to 70 mA Display refresj 12 refresh second retention memory yes recovers counting value in case of power loss Power power...

Page 7: ...a ENTER key It selects and accesses the menu option currently dis played At menus with numerical value entries it validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access...

Page 8: ...nstrument The On Power Up on Pu menu configures functions to apply at start up It applies only to instrument restart after power loss It does not apply to instrument restart due to change in configura...

Page 9: ...n to add 1 each time alarm 1 activates on alarm 2 o AL2 select on to add 1 each time alarm 2 activates on alarm 3 o AL3 select on to add 1 each time alarm 3 activates on reset o rSt select on to add 1...

Page 10: ...inimum value if the actual value is smaller It replaces the maximum value if the actu al value is larger Minimum and maximum values are visible through front key UP 5 see section 1 12 5 Application a...

Page 11: ...e independent activation of up to 3 relay outputs or transistor or SSR control installed with the R1 or T1 or SSr optional modules see section 2 1 For outputs up to 4 and 6 relays see special modules...

Page 12: ...top to stop the counting set the Alarm flash AL FL parameter to on to activate the flash of the display when alarm is active To manually deactivate the flash mode press any of the front keys or change...

Page 13: ...Password PASS menu select a 4 digit code to block access to the configuration menu Instrument configuration will not be ac cessible to non authorized personnel To activate the Password se lect on and...

Page 14: ...s access to the configuration parameters of the channel B function Fn b previously selected If no function has been selected menu entry indicates Fn b n Following is an explanation for menus Fn b 1 to...

Page 15: ...delay Inverted relay Locked alarm Disabled Normal Repeat Stop Alarm flash Controls Activation for Start and Stop Pulls for reset Pulls for Start and Stop Activation for reset Pull down No pull Pull u...

Page 16: ...et activates by edges EdGE Function on channel B no Controls Pulls for start and stop pull up P uP Activation for start and stop by falling edge on_0 Pulls for reset pull up P uP Activation for reset...

Page 17: ...ment is variable and the operator requires that the setting of each drying time to be easily accessible and modifiable The modification of other configuration parameters must be locked During the proc...

Page 18: ...ualified personnel only To open the housing use a flat screwdriver to free the fixation clips if possible in the following order D C B and A Remove the front cover Let the inside of the instrument sli...

Page 19: ...nd regulations 1 20 Warranty This instrument is warranted against all manufacturing defects for a period of 24 MONTHS from the shipment date This warranty does not apply in case of misuse accident or...

Page 20: ...ntinuous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt...

Page 21: ...special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_man...

Page 22: ...Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manu...

Page 23: ...programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrument front keypad through menu entries Opt 1 Opt 2 or Opt 3 depending on the posit...

Page 24: ...without front key pad To configure the instrument remove the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument...

Page 25: ...lder 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel me...

Page 26: ...FEMA ELECTR NICA Series K K40 CR 26 Notes...

Page 27: ...FEMA ELECTR NICA Series K K40 CR 27 Notes...

Page 28: ......

Reviews: