Feel Good mr. steam AirButler Installation, Operation & Maintenance Manual Download Page 19

 Flush or Recess 

1
8 " 

CEMENT BOARD

Thin Set

Finished

Wall Surface

Silicone

Silicone

Steam Outlet Face

VAPOR BARRIER

Cement Board

Thin Set

Finished 

Wall Surface

Silicone

Silicone

STEP 1. 

Confirm proper stud spacing: The studs 

must have a minimum spacing of 14-1/8” and a 
maximum spacing 19". If the stud spacing is outside 
the required range then shim or otherwise reposition 
the studs as required.   

  Installing the steam head between 

incorrectly spaced studs may result in damage to the 
steam head and result in a leak within the wall cavity 
and cause property damage.   

STEP 2.

 Locate the steam head 6-12” above the 

finished floor. Locate the steam head where a steam 
bather can not come into contact with direct steam 
emissions.  See page 6 for information on the steam 
emission zone.   

  Steam is hot. Locate the steam head 

where a steam bather can not come into contact 
with direct steam emissions.  Failure to follow these 
directions may result in a hazardous condition, 
scalding or personal injury.  

STEP 3. 

Position the steam head between 2 

properly spaced studs. Extend the adjustable 
brackets as required so the steam head fits snugly 
between two studs. Use a level to ensure the steam 
head is level (see Fig. 3).  Tighten the eight bracket 
adjustment screws (supplied).  

Linear Steam Head

®

®

NOTE:

 Drawings are for illustrative purposes only.

 

Consult with qualified designer, architect or contractor for steam room construction.

Installer Section 

Model 104480

Figure 3

Figure 4

Steam Head Installation

Stud

Stud

Steam Head Face

Steam Outlet

Level

Copper Tubing 

or Brass Pipe 

(Not Supplied)

14 

1

/

8

 - 19”

Linear SteamHead 
shown without the 

optional faceplate 

or diverter.

Vapor Barrier

Steam Outlet Face

Bracket  

Adjustment Screws 

STEP 4. 

If the optional decorative faceplate is used,  

see the installation instructions for the optional faceplate  
on page 5. If the optional decorative faceplate is not used,  
position the steam head so that the steam head face will be flush 
with the finished wall face (see Fig. 4).  

STEP 5.

 With the stem head properly positioned, with or without a 

decorative faceplate, provide eight screws as required to securely 
mount the steam head brackets to the studs. 

 Failure to position the steam head face as instructed may 

result in improper steam head alignment, or a leak within the wall cavity 
and cause problems associated with leaks, moisture and property 
damage from leaks.  

STEP 6.

 Plumb rigid copper tubing or brass pipe from the steam 

generator to the steam head. Use a ¾” NPT fitting appropriate for the 
steam piping used. Plumbing must not form traps or valleys. Thread 
sealant must be used as required to ensure a leak free joint between 
the piping and steam head.  

STEP 7. 

Before continuing or closing the wall, test the installation, 

piping and steam head for leaks, traps, position, steam emission zone 
and for general proper installation.  

  Failure to test the steam head installation may result in 

leaks, and cause problems associated with leaks, moisture and property 
damage from leaks.

18

Summary of Contents for mr. steam AirButler

Page 1: ...Good Inc Rev 5 2022 Table of Contents AirTempo Wireless Control AromaSteam SteamHead Linear Steamhead SteamLinx Mobile App MS Super AutoFlush MX Autoflush Condensation Pan PUR100474 PUR100421 PUR10393...

Page 2: ...Installation Operation Maintenance Manual AirTempo Wireless Touch Control with Steamhead mr steam Feel Good Inc PUR100474 Rev 5 22...

Page 3: ...A occurs when the internal temperature of the body reaches a level several degrees above the normal body temperature of 98 6 F The symptoms of hyperthermia include an increase in the internal temperat...

Page 4: ...stalled inside or outside the steam room as a matter of personal preference If the control is installed outside the steam room a Remote Temperature Probe part number MSTS must be installed inside the...

Page 5: ...on glass a peel and stick film is provided on pages 20 21 and may be used as a mask for a clean look from behind the glass Steam Generator 3 ft Cable Standard optional 30 or 60 cable available Wirele...

Page 6: ...i i i iV i i i i i i i V d The probe has an integral 30 cable Insure that the probe and or steam generator are located accordingly i v V L i L i 2 Drill a 5 16 inch diameter hole in the wall Do not o...

Page 7: ...E For Illustrative Purposes Only Drawings Not to Scale 1 AirTempo Operating Instructions The AirTempo features programmable temperature control programmable time duration AromaSteam ON OFF ChromaSteam...

Page 8: ...the TEMP key for 10 seconds The temperature units will toggle to Fahrenheit F or Celsius C USING AIRTEMPO AS A REMOTE TheAirTempocanberemovedfromits holder andusedas aremote control towarmupthesteamsh...

Page 9: ...ed by a number This is the software revision CO indicates the AirTempo control has lost communication with the steam generator Ensure all connections are secure between the steam generator and the tra...

Page 10: ...unications However there is no guarantee that interference will not occur in a particular installation If this equip ment does cause harmful interference to radio or television reception which can be...

Page 11: ...l Flush Mount specify finish 104215XX Surface Bezel Surface Mount AirTempo Surface specify finish 104220 AirTempo Control Cable 3ft All 104117 30 30 ft Control Cable Optional 103990 60 60 ft Control C...

Page 12: ...in place Template For Flush Mount Kit Installation www mrsteam com Products information and specifications are subject to change without notice For more information call Sales Support at 1 800 76 STEA...

Page 13: ...Installation Operation Maintenance Manual AromaSteam SteamHead mr steam Feel Good Inc PUR100421 Rev 5 22...

Page 14: ...tant flooring install Acrylic Shield Part Number MS 103938 3 To prevent door seals from deteriorating do not locate the steam head where direct steam emission would contact door seals STEP 2 Install s...

Page 15: ...Installation Operation Maintenance Manual mr steam Feel Good Inc Linear Steam Head Residential Model 104480 IMPORTANT Leave this material with the homeowner PUR103936 Rev 5 22...

Page 16: ...esistant flooring install Acrylic Shield Part Number MS 103938 3 To prevent door seals from deteriorating do not locate the steam head where direct steam emission would contact door seals STEP 2 Insta...

Page 17: ...e linear steam head read and follow the Installation and Operation Manual s provided with all system components generator controls accessories etc If the installation and operation manuals are not ava...

Page 18: ...tlet Figure 2 3 4 NPT Steam Inlet 9 1 4 1 1 16 2 1 4 5 8 2 1 8 P104481 Linear Steam Head 104483 Faceplate 104484 Diverter 104482 AromaTray Bracket Adjustment Screws Adjustable Brackets Linear SteamHea...

Page 19: ...om construction Installer Section Model 104480 Figure 3 Figure 4 Steam Head Installation Stud Stud Steam Head Face Steam Outlet Level Copper Tubing or Brass Pipe Not Supplied 14 1 8 19 Linear SteamHea...

Page 20: ...led inside the steam room the control must be located 2 4 5 feet above the floor near the bather seating area 3 The control features an integral temperature sensor Locate the control in a location rep...

Page 21: ...tact with steam presentees a scalding hazard The steam head must be installed in a location to ensure that a steam bather will not be near the steam emission zone The diverter reduces the steam emisso...

Page 22: ...njury Because direct steam is very hot the diverter will be hot during the steam session and will remain hot for a period of time after steam session Never install remove or adjust a diverter when the...

Page 23: ...ing a steam bath session or for a period of time after the steam bath session may result in burns scalding or personal injury Failure to first read the instructions provided with the MrSteam Essential...

Page 24: ...Linear Steam Head using the video Use only these installation instructions for a safe and problem free installation Linear Steam Head NOTE Drawings are for illustrative purposes only Consult with qual...

Page 25: ...72 STEAM 2020 MrSteam and des A Lifetime of Pleasure AirTempo AromaFlo AudioWizard AutoFlush AutoSteam Butler Package ChromaSteam Clean Steam Every Time Club Therapy CT Day Spa Digital 1 Express Steam...

Page 26: ...Installation Operation Maintenance Manual SteamLinx mr steam Feel Good Inc PUR100518 Rev 5 22...

Page 27: ...ZS Pg QOZZW U AbSO 1cab S AS dWQS Wb QO PS R e Z ORSR T abSO Q ZZ R OeW Ua T aQVS ObWQ c aSa Zg OQYOUS 1 bS ba AbSO W f eWbV 7 bSU OZ 1OPZS AbSO W f 0 O R 3bVS Sb 1OPZS eS Ac Zg O R 1OPZS 7 ab cQbW a...

Page 28: ...bVS W bS Sb BVS W RWQOb ZWUVb AbSO W f eWZZ b PS WZZc W ObSR 0ZcS C Wba O S Q SQbSR Q SQbZg C Wba O S cb T O US b OW SR Bc P SOYS TT 7 ac S AbSO W f Wa Q SQbSR b bVS abSO US S Ob CaS O O S QZW aW WZO...

Page 29: ...Installation Operation Maintenance Manual S Su er Auto lu mr steam Feel Good Inc PUR100200E Rev 5 22...

Page 30: ...llowing each use A time delay allows the water to cool down about two hours before it drains resulting in a safe and gentle operation BOX CONTENTS AutoFlush System Valve with Cord Installation Instruc...

Page 31: ...ded can be added 3 Open Drain Valve handle must be aligned with brass nipple 4 Connect the AutoFlush System cord connector to the three pin connector as shown Do not drain into a steam enclosure or an...

Page 32: ...Installation Operation Maintenance Manual X Auto lu mr steam Feel Good Inc PUR100532 Rev 5 22...

Page 33: ...ollowing each use A time delay allows the water to cool down about two hours before it drains resulting in a safe and gentle operation BOX CONTENTS AutoFlush System Valve with Cord Installation Instru...

Page 34: ...toFlush System valve will open and may discharge boiling water SWEAT FITTINGS When using sweat fittings use only tin base solder with a melting point below 600 degrees F Do not overheat Ends of water...

Page 35: ...Installation Operation Maintenance Manual Conden ation Pan mr steam Feel Good Inc TS0012 Rev 5 22...

Page 36: ...in accordance with applicable national and local codes Check local plumbing code for receptor trap and vent requirements Condensation pans drain by gravity The condensation pan is equipped with an int...

Page 37: ...1 Express Steam Feel GoodInc FromBathroomto Spa iButler iGenie iSizing iSteam MakingWellness a Way of Life Music Therapy Spa Package Steam on Demand Steam Home iTempo iTempo Plus SmartSizing SteamSta...

Reviews: