background image

1.

The air inlet SHALL be located at least 12" from a wall or
other obstruction for unrestricted air flow.

2.

The air outlet SHALL be located so as to direct discharged
air away from the building. (Avoid low overhanging roofs to
avoid recirculation of condenser discharge air on vertical
discharge models.)

3.

Mount the unit on a sturdy base approximately 4" to 6"
above the ground. A concrete slab is recommended. If
concrete blocks are used, be sure to use well-tamped
gravel-fill beneath the blocks to prevent settling. If timbers
are used, use at least 6" x 6" timbers plus gravel-fill to
prevent settling.

4.

A concrete slab should not be in contact with the building
foundation to prevent possible sound or vibration
transmission.

5.

Locate the outdoor unit as close as possible to the indoor
unit. A shorter line set run will reduce refrigerant pressure
drop for increased system performance and reduce system
refrigerant charge for greater reliability.

6.

If practical, unit should be located on the south side of the
structure away from northerly winds to minimize the effects
of blowing snowdrifts and freezing rain. A wind screen or
wind block can also be used. In areas known for snow
accumulation, the unit should be elevated at least 18" above
the ground.

7.

Placement of the unit should be in a well-drained area, or the
unit MUST be supported high enough so run-off will not
enter the unit.

8.

Avoid installations under roof overhangs without guttering.
Water draining from the roof onto the unit could produce
excessive noise and may cause ice to build up on the coil or
fan during cold weather.

9.

Do not locate where heat, lint or exhaust fumes will be
discharged on the unit (as from dryer vent). Rooftop
installation is acceptable in areas of low snow
accumulations, provided the roof will support the unit and
provisions are made for water drainage and the noise or
vibration through the structure.

1.

Refer to the instructions supplied with the evaporator coil.

2.

When installing the evaporator, refer to page 8 for
condenser evaporator match-up. The evaporator should be
installed in an insulated plenum of proper size to
accommodate the coil, whether it be of the “A” coil or “H” coil
type design. Be sure no air can bypass the coil as this can
seriously hamper unit operation.

3.

Install condensate drain as shown below. Use drain
connection size or larger.

4.

Emergency drain facilities SHALL be installed on any
application where water damage may occur due to overflow,
leaking or sweating of condensate drain pan.

DO NOT OPERATE WITHOUT TRAP.  UNIT MUST BE LEVEL OR SLIGHTLY INCLINED TOWARD DRAIN.

5

INSTALLATION

CODES:

The installer SHALL comply with all local, state, and federal codes and/or regulations pertaining to this type of equipment and its

installation. Such codes and/or regulations should take precedence over any recommendations contained herein in lieu of local codes.
Installations SHALL be made in accordance with the National Electrical Code, local codes and recommendations made by the National Board
of Fire Underwriters.

HEAT PUMP

EVAPORATOR & CONDENSATE DRAIN

Summary of Contents for CH1018BBD

Page 1: ...Installation Operation and Maintenance MODEL CH10 CH12 SERIES 1 5 THRU 5 TON Split System High Efficiency Heat Pump REV 1 20 04 23 23 0419N 001...

Page 2: ...iving your unit Look for any punctures or openings and if it appears damage has occurred it should be noted on the freight bill before signing The delivering carrier should be contacted immediately to...

Page 3: ...te the unit in the heating mode at outdoor temperatures above 70 F HEATING OPERATION Turn the heat cool switch to the heat position and set the desired temperature on the thermostat temperature dial A...

Page 4: ...umulated away from the coil Do not wash the outdoor coil if the temperature is approaching or below freezing as this will encourage ice build up 3 Since the heat pump unit is located outdoors it is ex...

Page 5: ...hout guttering Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather 9 Do not locate where heat lint or exhaust...

Page 6: ...oint and braze with silphos rod containing at least 10 silver DO NOT USE SOFT SOLDER Replace the valve core after brazing 2 Leak check all braze joints at approximately 80 psi pressure purge and evacu...

Page 7: ...nstall a line service disconnect switch within sight of the condensing unit The line voltage service wiring for the condensing unit should include a fused disconnect switch 3 Use correct wire size and...

Page 8: ...TXV kits must be purchased as an accessory kit and are required to complete system installation 10 FT 15 FT 25 FT CH1018B A24B1 E3009A16 600 12 5 16 5 8 5 16 5 8 3 8 3 4 CH1024B A24B1 E3009A16 800 20...

Page 9: ...n systems that cool with fixed restrictor SUCTION PRESSURE is 65 PSI which equals 38 F 3 3 C on the R 22 scale of the low side gauge SUCTION LINE temperature taken at the unit is 70 F 21 1 C 70 F 21 1...

Page 10: ...with frost free outdoor coil When the outdoor temperature is below 40 F manually defrost the unit before reading 18 16 14 12 10 60 70 80 90 100 110 OUTDOOR TEMPERATURE F COOLING MODE 26 24 22 20 18 1...

Page 11: ...as shown in Figure 2 4 Attach the bulb securely with the copper strap provided 5 Insulate the bulb thoroughly with a suitable insulation material such as cork tape Figure 2 The indoor piston may requ...

Page 12: ...to accumulate jumper the two test pins marked test together If the coil temperature is above 28 F jumper the DFT defrost thermostat terminals to simulate a closed thermostat Defrost should begin after...

Reviews: