Fedders CH1018BBD Installation, Operation And Maintenance Manual Download Page 11

A. Factory-Installed Expansion Valves

The sensing bulb must be installed to the vapor line
during the field installation. Skip to step 3 below for factory-
installed expansion valves.

B. Field-Installed Expansion Valves

1. Disassemble the flow rater body and remove the 

piston from the distributor. Be sure to save the 
O-ring in the tail piece.

2. Install the expansion valve between the tail piece 

and the distributor as shown in Figure 2. Be sure to install 
the O-rings as shown in Figure 2.

3. The bulb and capillary tubing should be routed outside of 

the coils’ casing, making sure the capillary tube will not be 
directly against sharp casing edges. The bulb should be 
installed after the vapor and liquid line is soldered and 
leak checked to prevent subjecting the bulb to excessive 
heat. To assure accurate sensing and the best 
performance, the bulb should be placed on the upper half 
of the vapor line at the two or ten o’clock position and at 
least 6" from the coil manifold as shown in Figure 2.

4. Attach the bulb securely with the copper strap provided.

5. Insulate the bulb thoroughly with a suitable insulation 

material such as cork tape.

Figure 2

The indoor piston may require changing to match the outdoor unit.
The correct indoor piston is shipped with each outdoor unit. Each
coil has a marker strip, marked with the size of the factory-installed
piston located on the coil liquid line. Compare this piston marking
with the chart on page 8. If they are different, change the piston to
the correct size as shown in Figure 1.
The piston is located in the distributor fitting on the liquid line.
To change the piston, remove stub tube nut (left-hand thread) and
separate the liquid line from the distributor, then the piston. Install
the correct piston with the rounded end toward the distributor.
Reinstall the O-ring and stub nut (do not nick or handle the O-ring).

NOTE:

ON PRECHARGED COIL, THE REFRIGERANT WILL

HAVE TO BE REMOVED PRIOR TO CHANGING THE PISTON.

Figure 1

11

FIXED PISTON TYPE RESTRICTORS

EXPANSION VALVES

REFRIGERANT METERING DEVICES

NOTE: 

The indoor expansion device size and type are located on the outdoor unit’s series and rating plate.

Summary of Contents for CH1018BBD

Page 1: ...Installation Operation and Maintenance MODEL CH10 CH12 SERIES 1 5 THRU 5 TON Split System High Efficiency Heat Pump REV 1 20 04 23 23 0419N 001...

Page 2: ...iving your unit Look for any punctures or openings and if it appears damage has occurred it should be noted on the freight bill before signing The delivering carrier should be contacted immediately to...

Page 3: ...te the unit in the heating mode at outdoor temperatures above 70 F HEATING OPERATION Turn the heat cool switch to the heat position and set the desired temperature on the thermostat temperature dial A...

Page 4: ...umulated away from the coil Do not wash the outdoor coil if the temperature is approaching or below freezing as this will encourage ice build up 3 Since the heat pump unit is located outdoors it is ex...

Page 5: ...hout guttering Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather 9 Do not locate where heat lint or exhaust...

Page 6: ...oint and braze with silphos rod containing at least 10 silver DO NOT USE SOFT SOLDER Replace the valve core after brazing 2 Leak check all braze joints at approximately 80 psi pressure purge and evacu...

Page 7: ...nstall a line service disconnect switch within sight of the condensing unit The line voltage service wiring for the condensing unit should include a fused disconnect switch 3 Use correct wire size and...

Page 8: ...TXV kits must be purchased as an accessory kit and are required to complete system installation 10 FT 15 FT 25 FT CH1018B A24B1 E3009A16 600 12 5 16 5 8 5 16 5 8 3 8 3 4 CH1024B A24B1 E3009A16 800 20...

Page 9: ...n systems that cool with fixed restrictor SUCTION PRESSURE is 65 PSI which equals 38 F 3 3 C on the R 22 scale of the low side gauge SUCTION LINE temperature taken at the unit is 70 F 21 1 C 70 F 21 1...

Page 10: ...with frost free outdoor coil When the outdoor temperature is below 40 F manually defrost the unit before reading 18 16 14 12 10 60 70 80 90 100 110 OUTDOOR TEMPERATURE F COOLING MODE 26 24 22 20 18 1...

Page 11: ...as shown in Figure 2 4 Attach the bulb securely with the copper strap provided 5 Insulate the bulb thoroughly with a suitable insulation material such as cork tape Figure 2 The indoor piston may requ...

Page 12: ...to accumulate jumper the two test pins marked test together If the coil temperature is above 28 F jumper the DFT defrost thermostat terminals to simulate a closed thermostat Defrost should begin after...

Reviews: