background image

The heat pump system is a highly efficient way to heat and cool your
home. During the summer months, the system transfers heat and
humidity from your home to the outside. During the winter months,
the heat pump will transfer heat from the outside to inside your
home without drying the inside air.

Please take the time to read the operation instructions below to
familiarize yourself with your new heat pump system.

The heating and cooling functions are controlled by a wall
thermostat. The type of thermostat will vary depending on customer
preference, but generally most heat pump thermostats will be 
one-stage cool, two-stage heat type. The following instructions will
help you understand the operation of the thermostat and how to use
it for maximum efficiency.

FAN OPERATION:

The thermostat has a fan switch for

continuous or intermittent operation. This is identified as fan ON and
AUTOMATIC. In the AUTOMATIC position the indoor fan will run
only when the compressor is running whether in heating or cooling
mode. When the compressor turns off, the indoor fan will also turn
off. In the ON position, the fan will run constantly. This position will
keep the temperature throughout the home more even and will
generally improve indoor air quality by continuously drawing the air
through the air filter, especially if the filter is of the high-efficiency
type. If this position proves drafty in the winter months, your
contractor can, in most cases, wire the indoor fan to operate
continuously on a lower fan speed, and the correct higher fan speed
when the compressor is running. This arrangement will also be more
economical to operate than the continuous high speed operation.

Turn the thermostat heat/cool switch to the cool position. Set the
desired temperature on your thermostat dial. Do not operate the
cooling unit for extended periods at indoor temperatures over 85°F.
The unit indoor design temperature range is between 70°F and 80°F
in the cooling mode.

Turn the thermostat heat/cool switch to the heat position. Set the
desired temperature on your thermostat dial. Do not operate the
heating unit at indoor temperatures over 80°F. The unit indoor
design temperature range is between 65°F and 80°F in the heating
mode.

Never operate the unit in the cooling mode at outdoor temperatures
below 60°F without a low ambient control. Never operate the unit in
the heating mode at outdoor temperatures above 70°F.

HEATING OPERATION:

Turn the heat/cool switch to the

heat position and set the desired temperature on the thermostat
temperature dial.

AUXILIARY HEAT:

Most heat pump installations include

electric resistance heat for auxiliary heat (when the outdoor
temperature is too low for the heat pump to provide enough heat)
and for emergency heat (the outdoor unit is not working). On a
properly-sized installation the heat pump will supply all the heat you
will need during cool weather. As the temperature drops, the heat
output from the heat pump will be reduced. The auxiliary heat
installed in your system will come on as needed to make up for this
reduction of heat output.

The need for auxiliary heat is detected by your thermostat. If the
thermostat senses a temperature fall of more than 2°F below the set
point, the auxiliary heat will turn on.  For this reason, setting the
thermostat to the desired temperature and not changing the
temperature during the day can be more economical than varying
the thermostat setting.

If you intend to set the temperature back at night, you should
consider that, when the temperature is turned back up to the normal
setting, the system will be operating during the coldest time of the
day (early morning hours) and may require auxiliary heat if the
increase in temperature is above 2°F.

EMERGENCY HEAT:

This switch will turn the outdoor unit

off and use the electric auxiliary heat only to provide heat. If outdoor
unit should malfunction, turn the emergency heat switch to the ON
position and contact your service person.

Your heat pump has a control system designed to defrost the
outdoor coil by warming it up to keep it clear of ice and operating
efficiently. When the temperature drops below 40°F, the control
system will sense that conditions are right for the formation of ice.
After a time period of 60 to 90 minutes, the heat pump will go into
the defrost mode. At this time, the outdoor coil may be heavily iced
or no ice may be visible, depending on the outdoor humidity. When
the unit starts the defrost mode, the outdoor fan will turn off and
you may hear a hissing noise that disappears as defrost continues.
As the outdoor coil warms, you may notice steam coming off the
coil. When the coil reaches a predetermined temperature (usually
within 7 minutes), the defrost cycle will end. You may hear a hiss
as the unit switches back to the normal heating mode.

3

OPERATION INSTRUCTIONS

THERMOSTAT

COOLING OPERATION

DEFROST OPERATION

HEATING OPERATION

Summary of Contents for CH1018BBD

Page 1: ...Installation Operation and Maintenance MODEL CH10 CH12 SERIES 1 5 THRU 5 TON Split System High Efficiency Heat Pump REV 1 20 04 23 23 0419N 001...

Page 2: ...iving your unit Look for any punctures or openings and if it appears damage has occurred it should be noted on the freight bill before signing The delivering carrier should be contacted immediately to...

Page 3: ...te the unit in the heating mode at outdoor temperatures above 70 F HEATING OPERATION Turn the heat cool switch to the heat position and set the desired temperature on the thermostat temperature dial A...

Page 4: ...umulated away from the coil Do not wash the outdoor coil if the temperature is approaching or below freezing as this will encourage ice build up 3 Since the heat pump unit is located outdoors it is ex...

Page 5: ...hout guttering Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather 9 Do not locate where heat lint or exhaust...

Page 6: ...oint and braze with silphos rod containing at least 10 silver DO NOT USE SOFT SOLDER Replace the valve core after brazing 2 Leak check all braze joints at approximately 80 psi pressure purge and evacu...

Page 7: ...nstall a line service disconnect switch within sight of the condensing unit The line voltage service wiring for the condensing unit should include a fused disconnect switch 3 Use correct wire size and...

Page 8: ...TXV kits must be purchased as an accessory kit and are required to complete system installation 10 FT 15 FT 25 FT CH1018B A24B1 E3009A16 600 12 5 16 5 8 5 16 5 8 3 8 3 4 CH1024B A24B1 E3009A16 800 20...

Page 9: ...n systems that cool with fixed restrictor SUCTION PRESSURE is 65 PSI which equals 38 F 3 3 C on the R 22 scale of the low side gauge SUCTION LINE temperature taken at the unit is 70 F 21 1 C 70 F 21 1...

Page 10: ...with frost free outdoor coil When the outdoor temperature is below 40 F manually defrost the unit before reading 18 16 14 12 10 60 70 80 90 100 110 OUTDOOR TEMPERATURE F COOLING MODE 26 24 22 20 18 1...

Page 11: ...as shown in Figure 2 4 Attach the bulb securely with the copper strap provided 5 Insulate the bulb thoroughly with a suitable insulation material such as cork tape Figure 2 The indoor piston may requ...

Page 12: ...to accumulate jumper the two test pins marked test together If the coil temperature is above 28 F jumper the DFT defrost thermostat terminals to simulate a closed thermostat Defrost should begin after...

Reviews: