background image

Because each installation is different in terms of airflow, refrigerant
line length, and configuration, the factory charge may not be correct
for the application. To assure the best performance from the system,
the refrigerant charge should be checked and adjusted if needed on
each installation.

1.

10 SEER systems (Fixed Piston-Type Metering Devices)
For systems with piston-type fixed metering devices, the
SUPERHEAT method is recommended. Read instructions
below and follow chart on page 10.

2.

12 SEER systems (Expansion Valve-Type Metering
Devices)
All 12 SEER units MUST be equipped with an indoor coil
expansion valve with internal check-valve. For systems with
expansion valve metering devices, the SUBCOOLING
method is recommended. Read instructions below and
follow charts on page 10.

9

FIELD CHARGING PROCEDURES

The superheat method is highly recommended for field charging or
checking the existing refrigerant charge in a system. Because each
installation is different in terms of indoor air flow, refrigerant line
length, duct variations, etc., the factory charge may not be correct
for every application. To assure the best performance from the heat
pump, the refrigerant charge should be checked and adjusted when
needed on each installation.

For proper superheat readings, a standard low side refrigerant
gauge and an accurate thermometer are needed. A mercury or stem
type thermometer is not adequate for suction line temperatures. We
recommend electronic thermocouple thermometers (available at
most refrigeration wholesalers); however, an accurate remote bulb
thermometer can be used. When measuring the line temperature,
be sure the thermometer is well insulated to assure accurate
measurements. The chart on page 10 gives superheat values at
various outdoor temperatures. Allow at least 5 minutes running time
between charge adjustment for the unit to stabilize.

Chart on page 10 is based on 360 to 400 CFM/ton indoor airflow and
50% relative humidity. Use on systems that cool with fixed restrictor.
SUCTION PRESSURE is 65 PSI which equals 38°F / 3.3°C on the 
R-22 scale of the low side gauge.
SUCTION LINE temperature taken at the unit is 70°F / 21.1°C.  
70°F / 21.1°C minus 38°F / 3.3°C equals 32°F / 17.8°C superheat.

OUTDOOR TEMPERATURE is 90°F / 32.2°C, indoor temperature is
80°F / 26.7°C.
INTERSECTION of the indoor temperatures and outdoor
temperature lines occurs on the 12°F / 6.7°C superheat line.
ADD CHARGE to obtain 12°F / 6.7°C superheat.

INSTRUCTIONS

1.

Measure suction pressure and determine evaporator
refrigerant temperature on R-22 scale of low side gauge.

2.

Measure suction line temperature on suction line at the
outdoor unit.

3.

Measure outdoor and indoor temperature.

4.

Determine from the table what the superheat should be
considering the indoor and outdoor ambient temperatures. 
(Example indicates 12°F / 6.7°C superheat.)

5.

Adjust charge if needed. Be sure unit is running at stabilized
condition.

NOTE:

If operating superheat is more than 5°F / 2.8°C above the

chart value, add refrigerant. If below the chart value, remove
refrigerant. If below the limit line, remove refrigerant. When
removing refrigerant always be certain to use standard reclaim
procedures.

The subcooling charging method is to be used on units which have
Thermostatic Expansion Valves (TXV) as the expansion device. 
For proper subcooling readings, a standard high side gauge is
required for pressure readings.

Use the chart on page 10 to determine the required subcooling value.

INSTRUCTIONS

1.

Measure the outdoor air temperature. (T1)

2.

Measure the liquid line pressure at the outdoor unit and
determine condenser refrigerant temperature by the scale
on the high side pressure gauge. (T2)

3.

Measure the liquid line temperature on the liquid line at the
outdoor unit. (T3)

4.

Subtract T3 from T2. (T2 – T3) This is the subcooling value.
Compare this value and the outdoor temperature (T1) to the
charts on page 10. If the value is below the line, add
refrigerant. If the value is above the line, remove refrigerant
charge.

NOTE:

When removing refrigerant, always use standard reclaim

procedures.

SUPERHEAT CHARGING 

(for units with pistons)

SUBCOOLING CHARGING 

(for units with TXVs)

Summary of Contents for CH1018BBD

Page 1: ...Installation Operation and Maintenance MODEL CH10 CH12 SERIES 1 5 THRU 5 TON Split System High Efficiency Heat Pump REV 1 20 04 23 23 0419N 001...

Page 2: ...iving your unit Look for any punctures or openings and if it appears damage has occurred it should be noted on the freight bill before signing The delivering carrier should be contacted immediately to...

Page 3: ...te the unit in the heating mode at outdoor temperatures above 70 F HEATING OPERATION Turn the heat cool switch to the heat position and set the desired temperature on the thermostat temperature dial A...

Page 4: ...umulated away from the coil Do not wash the outdoor coil if the temperature is approaching or below freezing as this will encourage ice build up 3 Since the heat pump unit is located outdoors it is ex...

Page 5: ...hout guttering Water draining from the roof onto the unit could produce excessive noise and may cause ice to build up on the coil or fan during cold weather 9 Do not locate where heat lint or exhaust...

Page 6: ...oint and braze with silphos rod containing at least 10 silver DO NOT USE SOFT SOLDER Replace the valve core after brazing 2 Leak check all braze joints at approximately 80 psi pressure purge and evacu...

Page 7: ...nstall a line service disconnect switch within sight of the condensing unit The line voltage service wiring for the condensing unit should include a fused disconnect switch 3 Use correct wire size and...

Page 8: ...TXV kits must be purchased as an accessory kit and are required to complete system installation 10 FT 15 FT 25 FT CH1018B A24B1 E3009A16 600 12 5 16 5 8 5 16 5 8 3 8 3 4 CH1024B A24B1 E3009A16 800 20...

Page 9: ...n systems that cool with fixed restrictor SUCTION PRESSURE is 65 PSI which equals 38 F 3 3 C on the R 22 scale of the low side gauge SUCTION LINE temperature taken at the unit is 70 F 21 1 C 70 F 21 1...

Page 10: ...with frost free outdoor coil When the outdoor temperature is below 40 F manually defrost the unit before reading 18 16 14 12 10 60 70 80 90 100 110 OUTDOOR TEMPERATURE F COOLING MODE 26 24 22 20 18 1...

Page 11: ...as shown in Figure 2 4 Attach the bulb securely with the copper strap provided 5 Insulate the bulb thoroughly with a suitable insulation material such as cork tape Figure 2 The indoor piston may requ...

Page 12: ...to accumulate jumper the two test pins marked test together If the coil temperature is above 28 F jumper the DFT defrost thermostat terminals to simulate a closed thermostat Defrost should begin after...

Reviews: