Get Data Mode
getWSI##
-
Get the Dominant Wavelength, Saturation & Intensity
Transmit
Receive
getwsi##
getwsiall
XXX SSS YYYYY
Where:
##
represents the Fiber Number and is a number in the range 1 – 20.
xxx
represents the dominant wavelength of the LED in nanometers.
SSS
represents the Saturation (whiteness) and is a number in the range 0–100.
YYYYY
represents the intensity of the LED.
Description
This command is used to get the value of the Dominant Wavelength for the LED under the
Fiber number
##
.
This command should be preceded by the
capture C
command to ensure valid LED data is
stored in the memory of the LED Analyser. The
C1-C5
commands are available but are not as
accurate. The data for each LED can only be read out one-at-the-time, in any order.
Alternatively use the
getwsiall
command to read back the LED data for all 20 leds in
one command.
Example:
The PC transmits
getwsi01
to the LED Analyser to instruct it to send the stored dominant
wavelength & Intensity for the LED positioned under Fiber No 1. The LED Analyser will return
a string
xxx yyyyy
to the PC.
getwsi01
513 100 12345