62
VAIE 4000 Compact Systems
System manual
EN
VAIE
4000
D) Rack configuration
In the CONFIGURATION menu, browse through the items and select ‘
set>RACK CONFIG
’.
From here it is possible to configure all the basic settings of the system.
D1) >> System
Emergency units
Configuration of the keys for FMD 2000 range emergency units
D2) >> Microphone units
On the ‘
Microphone units
’ screen page, use the sub-menus to set the configuration
of the microphone units connected to the ‘UNITS’ RJ45 socket of the VAIE.
Select ‘Emergency units’ for FMD 2000 range models or ‘Broadcast units’ for MBT
1106 models.
It is possible to connect up to
two
remote emergency units: click on ‘
Change
’ to set the unit type:
1 key unit = single zone unit (FMD 2001)
12 key unit = 12-zone unit (FMD 2012)
Then, press ‘
Edit Key
’ to configure each key (see
Microphone units
on page 34).
The item ‘Rack amplifiers’ automatically shows the number of amplifiers present in
the system.
Spare amplifier:
Press ‘
Change
’ to activet/deactivate the spare amplifier function
(VAIE4102 and VAIE4252 models only).
Battery capacity:
Press ‘
Change
’ to select a value: 12 or 18 Ah. Please see page
34 for details.
Energy save (enabled/disabled)
For enabling/disabling the function allowing the batteries to go into the energy
saving mode in the absence of the mains power supply.
N.B. In order to comply with the regulations, the “Energy save” function
should always be enabled.
Emergency password (enabled/disabled)
For enabling/disabling the password request for the activation of the Emergency
status; the password is the same as for accessing the OPERATOR level. If the
password is disabled, the EMERGENCY button must be pressed twice consecutively.
Microphone units
Escape
Emergency units
Currently model is emergency units
Broadcast units