RECLAIMER DAMPER (HR-2100B HEAT
RECLAIMER OPTION)
The reclaimer damper, used on C-2100B dryers
equipped with the HR-2100B series heat reclaimer,
must be adjusted to balance the reclaimed air from the
heat zone reclaiming duct to the fan inlet vacuum
plenum. The damper should be adjusted by opening
the rear reclaimer door and checking for a slight vacu-
um in the duct. If a positive pressure is noticed (air
flowing out the door), open the reclaimer damper slight-
ly. If a large vacuum is noticed (air flowing into the
duct), close the reclaimer damper slightly.
NOTE: Making an adjustment change in the fresh-air
louvers may require a slight reclaimer damper adjust-
ment.
HEAT RECLAIMER DOORS
The HR-2100B reclaimer is equipped with hinged
cleanout doors every two feet along the length of the
reclaimer duct. These doors can be opened for clean-
ing the dryer and reclaimer duct wall.
The dryer can also be operated with the reclaimer
doors in the OPEN position to allow reclaiming air to
escape when full reclaiming is not desired. In this situ-
ation, the reclaimer damper should be FULLY CLOSED
and the fresh-air louvers readjusted to give the desired
grain cooling required.
C-2100B1 SERIES FULL HEAT DRYERS
FRESH AIR LOUVERS
The fresh air louvers on the C-2100B1 series dryers
should be fully opened during drying operation.
On C-2100B1 series dryers equipped with HR-2100B1
series Heat Reclaimer, the louvers should be approxi-
mately 66% open, creating a slight vacuum in the fan
inlet plenum. This opening should be fine tuned by
watching the pressure on the hinged skirt doors. If the
doors are being blown outward by the dryer exhaust
15
BLOWER
BURNER
MOTOR
GRAIN COLUMNS
FRESH AIR LOUVER
REAR OUTER FLOOR PANEL
TOP VIEW
HEAT ZONE RECLAIMER DUCT
HR-2100B SERIES HEAT RECLAIMER
RECLAIMER DAMPER
HR-2160B OPTIONAL HEAT RECLAIMER
RECLAIMER DAMPER
HR-2130B OR HR-2140B OPTIONAL RECLAIMER
PLENUM DIVIDER
CLEANOUT DOOR
GRAIN COLUMNS
VACUUM GUAGE
ASC
PSC
HINGED RECLAIMER
SIDE PANEL
HR-2100B1 SERIES
OPTION - FH RECLAIMER
21BAIR.DS4
C2100B1 SERIES FH OR
PRESSURE COOL
DRYERS ONLY -
VACUUM PLENUM
SIDE PANEL
PART NO 401-3994-1
C2100B SERIES VACUUM
COOL DRYERS ONLY
BLOWER PLENUM FLOOR PANEL
PART NO 401-3993-3
HINGED CLEANOUT DOOR
HR-2100B OPTION
Fig. 3-3 Heat reclaimer option
Summary of Contents for C-21100B
Page 22: ...20 ...
Page 36: ...34 Fig 6 3 LP vaporizer assembly Fig 6 4 ASC control panel ...
Page 49: ...Fig 8 1 Power circuit 220V 3 PH for C 2130B C 2140B C 2160B only 47 4B0280A TIF ...
Page 50: ...48 Fig 8 2 Power cirucit 220V Part wind start for C 2175B C 21100 models only 4B0280C TIF ...
Page 51: ...49 Fig 8 3 Power circuit 440V 3 PH for all C 2100B models 4B0280B TIF ...
Page 52: ...Fig 8 4 Control circuit all models except part wind start p 1 of 3 50 4B0280D TIF ...
Page 53: ...Fig 8 4 Control circuit all models except part wind start p 2 of 3 51 4B0280E TIF ...
Page 55: ...Fig 8 5 Control circuit part wind start models only p 1 of 3 53 4B0280H TIF ...
Page 56: ...Fig 8 5 Control circuit part wind start models only p 2 of 3 54 4B0280I TIF ...
Page 58: ...Fig 8 6 Safety circuit portion of control circuit all models 56 4B0280G TIF ...
Page 65: ......