DEVICE PROGRAMMING UNIT USER’S MANUAL
| CHAPTER 2
14
PROGRAMMING
The 1000/1500 device address address range is
01 to 60. If the data entered is out of range, the
following screen will flash for 3 seconds:
INCORRECT ENTRY!!!
If the smoke detector was not programmed
correctly, the display will show a screen similar to
the following:
8810
LOOP=1 ADDRESS=41
PROGRAMMING FAILED
<EXIT RE-DO>
Press EXIT to return to the Main Menu. Press RE-DO
to reprogram the detector.
When the detector is removed from the socket, the
8720 will return to the top programming screen and
will increment the address.
8800, 8801, 8802, 8804, 8805 and 8806
Interface modules or manual stations must be pro-
grammed using cable P/N 555-133891 that is stored in
the cable compartment in the bottom of the 8720.
Before starting to program one of these devices, open
the cable compartment and insert the programming plug
in one end of the cable into the red and black banana
jacks in the cable compartment of the unit. (Refer to
Figure 2, pages 10-11.) Then follow the procedure below:
•
With the 8720 displaying the Main Menu, press the
PROGRAM button. The 8720 will prompt the user to
insert or connect a device or detector.
The 8720 is not equipped with polarity reversal for MPC-1000
and MPC-1500 system devices. If the display searches for a
device for longer than two seconds, reverse the polarity of the
programming cable.
firealarmresources.com
Summary of Contents for 8720
Page 2: ...firealarmresources com...
Page 4: ...DEVICE PROGRAMMING UNIT USERS MANUAL CONTENTS ii TABLE OF CONTENTS firealarmresources com...
Page 22: ...DEVICE PROGRAMMING UNIT USER S MANUAL CHAPTER 2 18 PROGRAMMING firealarmresources com...
Page 35: ...firealarmresources com...
Page 36: ...P N 315 033260FA 3 8 Fernwood Road Florham Park New Jersey 07932 firealarmresources com...