Rev.23
60/311
Synchronism function (25) associated to recloser function (79)
If the parameter “Hold permission” of 79 function is prohibited any external condition will be considered
and 79 function will work normally without considering synchronism.
If “Hold permission” of 79 function is enable and it is associated with “ Permission of closure” of 25
function, could be occur:
1. If permissions LLLB, DLLB, LLDB y DLDB of 25 function are all prohibited, after tripping because of
a fault, circuit breaker never will be reclosed because
“Permission of closure” bit of 25 function will
never be activated. After time adjusted in hold time, 79 function will go to LOCKOUT status.
2. If permissions LLLB, DLLB, LLDB y DLDB of 25 function are all enable, it will be distinguished the
following cases:
a) If line, bar or both of them are dead, the circuit breaker will be always reclosed, because
“Permission of closure” only depends on corresponding permission adjustment, and it is not
necessary synchronism to get the circuit breaker reclose. .
b) If both, line and bar, are alive it will be necessary to get the reclose of the circuit breaker, not
only LLLB permission to be enable either to check synchronism. If LLLB permission is enable
but synchronism conditions do not verify the reclose will not occur and vice versa.
Summary of Contents for SIL B
Page 1: ...EN_FANOXTD_MANU_SIL_Feeder_SILB_R023 Docx USER S MANUAL SIL B Feeder Relay...
Page 8: ...www fanox com Rev 23 8 311 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 23 9 311 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 23 10 311...
Page 11: ...www fanox com Rev 23 11 311 2 3 Cut out pattern CUT OUT PATTERN...
Page 12: ...www fanox com Rev 23 12 311 2 4 Connection diagrams Analog connections...
Page 13: ...www fanox com Rev 23 13 311...
Page 14: ...www fanox com Rev 23 14 311 Digital connections Outputs and Trip circuit supervision...
Page 15: ...www fanox com Rev 23 15 311 2 5 Terminals IEC 61850 or DNP3 0 protocols...
Page 17: ...www fanox com Rev 23 17 311 IEC 60870 5 103 protocol...
Page 25: ...www fanox com Rev 23 25 311 3 3 Functional diagram...
Page 28: ...www fanox com Rev 23 28 311 3 5 1 SIL B 1 CHARGE CURVE 3 5 2 SIL B 5 CHARGE CURVE...
Page 91: ...www fanox com Rev 23 91 311...
Page 140: ...www fanox com Rev 23 140 311...
Page 194: ...www fanox com Rev 23 194 311 Polarization V 35 0 V C Operating Angle 180 C Halfcone Angle 3 C...
Page 307: ...www fanox com Rev 23 307 311 50BF init Fault init 79 Closure permission 52 closure permission...
Page 310: ...www fanox com Rev 23 310 311 NOTES...
Page 311: ...www fanox com Rev 23 311 311...