SILB with one RS485 port for ModBus and one RJ45 port for IEC61850 or
DNP3.0
The device features 1 exterior RS485 connections through three terminals (+, - y GND) located
on the back of the unit. The protocol used is Modbus RTU
These ports can be used for the continuous monitoring of the device from a remote PC or SCADA
system. Up to 32 units can be connected to one bus, each with its own modbus address. Speed
and direction are configurable.
In order to minimize communications errors due to noise, a shielded twisted conductor cable is
the recommended physical medium. In order to make the connection, connect all + terminals on
one side and all
– terminals on the other side.
If a 3 strand cable is used for communication, the ground terminals (GND) should be connected
to the earth cable.
If a 2 strand cable is used for communication, the ground terminals (GND) should be connected
to the cable shielding. The shielding should be connected to GND at only one point, so as to
avoid circular currents.
Resistance loads must be used at both ends if a very long cable is used. The best solution for
avoiding signal reflection is the addition of resistance loads at both ends of the cable. The value
of these resistance loads should be the same as the impedance of the cable.
RS485 are insulated from the auxiliary voltage, but there is no insulation between the two ends
of rs485 terminals. In highly aggressive environments fiber optics can be used, with the
corresponding converters.
Connection diagram of an RS485 bus:
Besides, there is another rear communication RJ45 port using IEC61850 or DNP3.0.
Summary of Contents for SIL B
Page 1: ...EN_FANOXTD_MANU_SIL_Feeder_SILB_R023 Docx USER S MANUAL SIL B Feeder Relay...
Page 8: ...www fanox com Rev 23 8 311 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view...
Page 9: ...www fanox com Rev 23 9 311 2 2 Equipment dimensions...
Page 10: ...www fanox com Rev 23 10 311...
Page 11: ...www fanox com Rev 23 11 311 2 3 Cut out pattern CUT OUT PATTERN...
Page 12: ...www fanox com Rev 23 12 311 2 4 Connection diagrams Analog connections...
Page 13: ...www fanox com Rev 23 13 311...
Page 14: ...www fanox com Rev 23 14 311 Digital connections Outputs and Trip circuit supervision...
Page 15: ...www fanox com Rev 23 15 311 2 5 Terminals IEC 61850 or DNP3 0 protocols...
Page 17: ...www fanox com Rev 23 17 311 IEC 60870 5 103 protocol...
Page 25: ...www fanox com Rev 23 25 311 3 3 Functional diagram...
Page 28: ...www fanox com Rev 23 28 311 3 5 1 SIL B 1 CHARGE CURVE 3 5 2 SIL B 5 CHARGE CURVE...
Page 91: ...www fanox com Rev 23 91 311...
Page 140: ...www fanox com Rev 23 140 311...
Page 194: ...www fanox com Rev 23 194 311 Polarization V 35 0 V C Operating Angle 180 C Halfcone Angle 3 C...
Page 307: ...www fanox com Rev 23 307 311 50BF init Fault init 79 Closure permission 52 closure permission...
Page 310: ...www fanox com Rev 23 310 311 NOTES...
Page 311: ...www fanox com Rev 23 311 311...