www.fanox.com
Installation_Guide_SIAB000B0010AA_Rev. 03 25 / 32
8.2. Self powering
8.2.1. Single phase minimum self-powering checking
Adjust the Sverker current generator with HOLD 0.8xIsmin, and suddenly, inject it to the relay,
as it would happened in real situation when circuit breaker is close, powering network line.
8.2.2. Three phase minimum self-powering checking
Adjust the Sverker current generator with HOLD 0.4xIsmin, and suddenly, inject it to the relay,
as it would happened in real situation when circuit breaker is close, powering network line.
8.2.3. Verification of Leds/Signalling Outputs/LCD in self-powering conditions
Adjust the Sverker current generator with HOLD 0.4xIsmin, and suddenly, inject it to the relay,
as it would happened in real situation when circuit breaker is close, powering network line. The
Led ON and LCD should be switched on: