1. Alarm Receiver 1
2. Alarm Receiver 2
3. Sequence Receiver 3
4. Sequence Receiver 4
5. Sequence Receiver 5
6. Sequence Receiver 6
7. Test alarm/Routine call receiver
8. Technical alarm receiver
9. Information alarm receiver
Change of time delay for alarm button
The delay time on the alarm button can be set to between 1 and 30 seconds. The default time
is 5 seconds.
From keypad:
< 1-30 >
From phone:
053
< 1–30 > #
Note: The delay programmed is the time until the alarm is activated by the ECII™ Flex. It will
take an additional two seconds before the alarm is called out because of the start-up time and
latency in the PSTN.
Connections to telephone line with automatic dial/
connection.
If the ECII™ Flex is connected to a telephone line with automatic dial or automatic connection;
where the telephone exchange directs the call without the user entering any keys, a pause must
be added to prevent the ECII™ Flex from calling out. One
– symbol represents a pause of
two seconds. There is no need to program any telephone number since the telephone exchange
takes care of that.
From keypad:
From phone:
001
#
Automatic test alarm/routine call
This function calls a test alarm/routine call receiver to verify the connection between the
ECII™ Flex and the alarm receiver. Automatic test alarm/routine call shall only be pro-
grammed if the ECII™ Flex is connected to an alarm central, the alarm central can verify that
the incoming test alarms/routine calls are correct. A test alarm/routine call is silent; no tones
are heard in the lift.
When the test alarm/routine call function is activated the first test alarm/routine call is sent 5
minutes after exiting programming mode and the following test alarm/routine call is sent 10
hours after the first. The third and following test alarm/routine call are sent every N x 24 hours
where N is the test alarm/routine call interval in days. Note that the automatic test counter is
reset every time an automatic test related parameter is changed and when the power is dis-
connected from the ECII™ Flex. If the ECII™ Flex has been out of power and the power re-
turns it will send the next test alarm/routine call after 10 hours.
If a test alarm/routine call fails the next attempt is made after 10 minutes. In total 10 attempts
are made. If a test alarm/routine call is received for instance in the third attempt the next test
alarm/routine call will be sent N x 24 hours after the last successful attempt. This means that
the ECII™ Flex automatically distributes the test alarms/routine calls to a time when the tele-
phone line of the alarm receiver is normally available.
162187 Manual FältCom ECII™ Flex